| 1 | Dismantling of old unserviceable flame proof fittings for height not exceeding 20 feet complete all as specified and directed |
| 2 | Material and labour for replacement of Supply and fixing LED light fitting 1x16/20 Watt flame proof, CMRI certified recommended for gas/ vapor group of IIA & IIIB, Zone 1 & 2 and IP 65 protection with die cast aluminum hosing with heat resistant toughened glass with LED tube light fixtures driver,holders, connector etc. Complete with all accessories prewired and including connecting up with three core flexible copper conductor cable with suitable size all accessories , complete all as specified and directed |
| 3 | Material and labour for replacement of Supply and fixing LED light fitting 2x16/20 Watt flame proof, CMRI certified recommended for gas/ vapor group of IIA & IIIB, Zone 1 & 2 and IP 65 protection with die cast aluminum hosing with heat resistanttoughened glass with LED tube light fixtures driver,holders, connector etc. Complete with all accessories prewired and including connecting up with three core flexible copper conductor cable with suitable size all accessories , complete all as specified and directed |
| 4 | Material and labour for replacement of CMRI certified LED flame proof well glass Luminaires (FLP-WP)-LM6 dies cast aluminium housing with heat resistant toughed glass IP 65 protection including lamp 35/40 w and all accessories complete all as specified and directed |
| 5 | Supply and fix in repair switch, flame proof, rotary type, with terminal box in LM6 ,10/16A single pole 250V . complete all as specified and directed |
| 6 | Supply and fix in repair switch, flame proof, rotary type, Direct Entry in LM6 ,10/16A double pole 250V .complete all as specified and directed |
| 7 | Material and labour for flame proof zone I&II Gas group IIA/IIB weather proof submain wiring with two runs using approved colour coding as per IS zero hologen flame retardent HFFR smoke free non toxic non corrosive PVC insulated unsheathed flexible coppper conductor cable 1.5 Sqmm single core 1100 volts and one run earth wire of 1.5 sqmm in and including ERW stove enamelled black rigid conduit of requied size but not less than 25 mmdia flame proof conduit accessories such tee bend elbow junction box complete all as specified and directed |
| 8 | Supply and fix flame proof zone I&II gas group IIA/IIB weather proof DB SPN 8 way with bus bar in cast aluminium LM-6 enclosure operated externally spring type knob complete with suitable incoming and outgoing cable entries with cable gland suitable for hazordous area and confirming to IS-2147/62 neoprene gasket geree of protection IP 65 suitable for MCB SPN 32 Amps-01 No MCB Sp-6-20-6 Nos complete all as specified and directed. |
| 9 | Material and labour for testing of earthing of any type scattared area at various location inside the cantt as per required intervals and submitt individual earth resitance results duly signed by all concern prior to claim payments complete all as specified and directed.NOTE : (i) Testing of earthing will be done by 3 Pole Fall of potential method.(ii) Cost of tools and materilas required to perform the test is demed to be included in the rate quoted.(iii) No payment shall be consider without satisfactory test result duly signed by all concern.(iv) A register of testing duly maintaining the periodicity location wise and test value shall be maintained and produced on Demand. |
| 10 | Material and labour in repair for Air termination, single pointed, aluminium rod 12mm dia and 300mm long to be fixed on horizontal lightning conductor with sutable fixing arrangement complete all as specified and directed. |
| 11 | Material and labour in repair for Air termination, single pointed, copper rod 12mm dia and 300mm long to be fixed on horizontal lightning conductor with sutable fixing arrangement complete all as specified and directed. |
| 12 | Taking out old GI/aluminium strip of any size and type in any height and any location complete all as specified and directed. Please Enable Macros to View BoQ information |
| 13 | Taking out old GI/aluminium strip of any size and type in any height and any location complete all as specified and directed. Please Enable Macros to View BoQ information |