| 1 | Excavation in trenches in any type of soil not exc 1.5 mtrs wide and not exc 1.5 mtr in depth for laying of pipe/ cables/ poles etc and getting out in any type of soil complete all as specified and as directed. |
| 2 | Returning filling in any type of soil including spreading leveling watering and well ramming in layers n.exc 25 cm complete all as specified and as directed. |
| 3 | Removing excavated soils to a distance n.exc. 50 mtr and depositing where directed at a level not exc 1.5 m above the starting point complete all as specified and as directed. |
| 4 | M & L for laying of fine, clean sand (river sand) free from sharp materials and stone particals in trenches for cushioning of cable 8 cm thick under cable and 15 cm thick over the cable including gently punning complete all as specified and directed by E-in-C. Note:- The total thickness of sand shall be measured 18 cm after punning. |
| 5 | Supply and laying un-reinforced precast.concrete cable protection cover of class LV, type-1, flat size 250mm x 150mm x 40 mm, factory made of specified make, complete all as specified and directed by E-in-C. |
| 6 | Design, fabricate, supply, testing and commisioning of CPRI approved factory made LT Panel Board double door, out door type fabricated out of 3.15mm thick CRCA sheet steel for outer body and 2.00mm thick CRCA Sheet for inner partition walls, independent cabinate with cabinate doors for MCCBs, Bus Bars, cable trays, metering equipment, vertical type floor mounted on angle iron frame of ISA 45x45x5mm with minimum height of legs 45 cm, minimum IP-54 protection, comprising of solid aluminium bus bar 4 strips suitable of 800 Amps, suitablily grouted to PCC complete with internal wiring, epoxy powder coated, connections of cable ends with suitable size of aluminium cable lugs with the following accessories. (a) INCOMING :- (i) MCCB 400 Amps, 4 Pole, 415 V, 36 KA - 01 No,(b) OUTGOING :- (i) MCCB 160 Amps, 4 Pole, 415 V, 25 KA - 05 No, (ii) Digital volt meter of size 4\\"x4\\" - 01 No, (iii) Selector Switch for Amp/Volt Meter - 02 Nos, (iv) Current Transfer (CT) - 3 Nos, (v) Phase indicator lamp (RYB) set of three - 01 No |
| 7 | Design, fabricate, supply, testing and commisioning of CPRI approved factory made LT Panel Board double door, out door type fabricated out of 3.15mm thick CRCA sheet steel for outer body and 2.00mm thick CRCA Sheet for inner partition walls, independent cabinate with cabinate doors for MCCBs, Bus Bars, cable trays, metering equipment, vertical type floor mounted on angle iron frame of ISA 45x45x5mm with minimum height of legs 45 cm, minimum IP-54 protection, comprising of solid aluminium bus bar 4 strips suitable of 400 Amps, suitablily grouted to PCC complete with internal wiring, epoxy powder coated, connections of cable ends with suitable size of aluminium cable lugs with the following accessories. (a) INCOMING :- (i) MCCB 250 Amps, 4 Pole, 415 V, 36 KA - 01 No, (b) OUTGOING :- (i) MCCB 125 Amps, 4 Pole, 415 V, 25 KA - 03 No, (ii) Digital volt meter of size 4\\"x4\\" - 01 No, (iii) Selector Switch for Amp/Volt Meter - 02 Nos, (iv) Current Transfer (CT) - 3 Nos, (v) Phase indicator lamp (RYB) set of three - 01 No |
| 8 | Supply, laying & testing in repalcement cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) with stranded aluminum conductor, 1100V grade with stranded aluminium conductor of size 150 sqmm 3.5 core including taking down of old unserviceable UG cable/service wires complete all as specified and directed by E-in-C. |
| 9 | Description all as per item No 08 above but of size 120 Sqmm 3.5 core |
| 10 | Description all as per item No 08 above but of size 95 Sqmm 3.5 core |
| 11 | Description all as per item No 08 above but of size 70 Sqmm 3.5 core |
| 12 | Description all as per item No 08 above but of size 50 Sqmm 3.5 core |
| 13 | Description all as per item No 08 above but of size 35 Sqmm 3.5 core |
| 14 | Description all as per item No 08 above but of size 25 Sqmm 4 core |
| 15 | Description all as per item No 08 above but of size 25 Sqmm 2 core |
| 16 | Description all as per item No 08 above but of size 16 Sqmm 4 core |
| 17 | M&L for replacement of new generation energy saving and environmental friendly long life LED street light made up of innovative die cast aluminium housing high power LED as lighting source with IP - 66 power consumption 60 watt complete input voltage of 150-240 Volt (nominal rated voltage 240 Volt) complete including taking down of old unserviceable street light any type/any capacity including replacement of twisted 3 core copper cable of size 1.5 Sqmm dia for connecting phase, neutral and earth from junction box to LED light through copper connectos complete all as specified and directed by E-in-C. |
| 18 | Material and Labour for galvanised steel tubes light grade 40 mm bore for bracket of street/security light length 1.20RM including welding, bend to shape and fixed with two nos GI Clamps Size 40x3mm thick including nuts and bolts, washer complete all as specified and directed by E-in-C. |
| 19 | Material and labour for straight through jointing kit heat shrinkable type suitable for 1.1 KV XLPE cable size 25 to 50 sq mm 3.5 core fixed in repair complete all as specified and directed by E-in-C. |
| 20 | Material and labour for straight through jointing kit heat shrinkable type suitable for 1.1 KV XLPE cable size 70 to 95 sq mm 3.5 core fixed in repair complete all as specified and directed by E-in-C. |
| 21 | Material and labour for straight through jointing kit heat shrinkable type suitable for 1.1 KV XLPE cable size 120 to 185 sq mm 3.5 core fixed in repair complete all as specified and directed by E-in-C. |
| 22 | Material and labour for Aluminium strip 25 x 3.15 mm with saddles and fixing screws etc.for roof conductors and down conductors above ground fixed in repair complete all as directed |
| 23 | M&L for repair of denting reveting hinges, Legs locking arrangement welding work etc in existing Panels and Feeder Pillar Box including painting of LT panel outdoor/indoor off sizes removing existing old paint with the help of sand/emery paper etc. Preparing surfaces externally applying externally one coat synthetic enamel paint including cleaning and surface dressing upto 25 cm depth around 1 mtr of the panels complete all as specified and directed by E-in-C. |
| 24 | Supply and fix in replacement of aluminium lugs of size 25 sqmm complete all as specified and directed. |
| 25 | Supply and fix in replacement of aluminium lugs of size 35 sqmm complete all as specified and directed. |
| 26 | Supply and fix in replacement of aluminium lugs of size 50 sqmm complete all as specified and directed. |
| 27 | Supply and fix in replacement of aluminium lugs of size 70 sqmm complete all as specified and directed. |
| 28 | Supply and fix in replacement of aluminium lugs of size 95 sqmm complete all as specified and directed. |
| 29 | Supply and fix in replacement of aluminium lugs of size 120 sqmm complete all as specified and directed. |
| 30 | Supply and fix in replacement of aluminium lugs of size 150 sqmm complete all as specified and directed. |
| 31 | Supply and fix in replacement of aluminium lugs of size 185 sqmm complete all as specified and directed. |
| 32 | Supply and fix in replacement of aluminium lugs of size 240 sqmm complete all as specified and directed. |
| 33 | Material and labour in replacement of existing unserviceable danger notice board with pressed vitreous painted plate fabricated out out of 1.6 mm thick mild steel sheet vitreous enamelled white with letters figures and conventional skull and bones in signal red colour and fixed with MS clamp bolts and nuts of approved size LT 1.1 KV 20 X 15 cm size complete all as directed. |
| 34 | Supply and fix LED Post Top light 20 Watt, powder coated die cast aluminium housing PC deffuser efficient high output LED with IP-65 including all fixing arrangement,and elect connections complete all as specified and directed by E-in-C. |
| 35 | S&F Indicator Lamp-01 Set (Set of three) complete all as specified and directed by E-in-C. |
| 36 | S&F Digital volt meter of size 4\\"x4\\" complete all as specified and directed by E-in-C. |
| 37 | S&F Digital Amp meter of size 4\\"x4\\" complete all as specified and directed by E-in-C. |
| 38 | S&F Selector Switch for Amp/Volt Meter complete all as specified and directed by E-in-C. |
| 39 | Supply and laying galvanised tube light grade ISI marked of size 100 mm dia incl all fittings in trenches/fixed on pole/wall/floor or laid in position complete all as specified and directed. |
| 40 | Supply and laying galvanised tube light grade ISI marked of size 80 mm dia incl all fittings in trenches/fixed on pole/wall/floor or laid in position complete all as specified and directed. |
| 41 | Supply and laying galvanised tube light grade ISI marked of size 50 mm dia incl all fittings in trenches/fixed on pole/wall/floor or laid in position complete all as specified and directed. |
| 42 | M & L for road cutting incl necessary excavation 45 cm wide and 90 cm in depth as in trenches in any type of soils/rock for laying LT UG cable through pipe after laying /through the cable trenches will be filling top with PCC 1:3:6 type C-1 using 20 mm grdaeds stone aggregates from top over 15 cm thick hard good of broken boulders , 63 mm gauge over 15 cm bolders 100 mm dia over filled and rammed earth to make good the disburbed surface etc complete all as specified and directed by E-in-C. |
| 43 | Supply and laying Double wall corrugated HDPE duct pipe 50mm outer dia confirming to IS: 14930 (Part-II) of approved colour with fittings for cable protection complete laid in trenches or fixed on walls with clamps of suitable size all as specified and directed by Engineer-in-charge. |
| 44 | Supply and laying Double wall corrugated HDPE duct pipe 80mm outer dia confirming to IS: 14930 (Part-II) of approved colour with fittings for cable protection complete laid in trenches or fixed on walls with clamps of suitable size all as specified and directed by Engineer-in-charge. |
| 45 | S & F in replacement of MCCB, 04 Pole, capacity 63 Amps with ultimate breaking capacity 16 KA at 415 volts with fixed thermalsettings conforming to IEC 60947 Part-I/IS-13947 Part-I , (Ics=Icu=100%) in the existing panel with suitable connecting copper terminals at site complete all as specified and directed by E-in-C. |
| 46 | Description all as per item No 45 here in above but of capacity 100 Amps with ultimate breaking capacity 25 KA and ditto- |
| 47 | Description all as per item No 45 here in above but of capacity 125 Amps with ultimate breaking capacity 25 KA and ditto- |
| 48 | Description all as per item No 45 here in above but of capacity 160 Amps with ultimate breaking capacity 25 KA and ditto- |
| 49 | Description all as per item No 45 here in above but of capacity 250 Amps with ultimate breaking capacity 35 KA and ditto- |
| 50 | Description all as per item No 45 here in above but of capacity 400 Amps with ultimate breaking capacity 36 KA and ditto- |
| 51 | S & F in replacement of change over switch with advanced neutral, 63 Amps, 4 pole, AC 415 Volt, manual Change over insheet metal enclosure including side operating handle conforming to IS:13947 (Part-3) complete all as specified and directed by E-in-C. |
| 52 | Description all as per item No 51 here in above but of capacity 100 Amps and ditto- |
| 53 | Description all as per item No 51 here in above but of capacity 125 Amps and ditto- |
| 54 | Description all as per item No 51 here in above but of capacity 200 Amps and ditto- |
| 55 | Supplying and layingsynthetic Rubber insulated mats 2 mm thick for voltage upto 3.3 kv for electrical purpose as per IS 15652-2006, (superseding IS 5424) suitable for electrical shock safety of sizes 2m x 1m complete all as specified and directed by E-in-C. |
| 56 | M&L for earthing complete with galvanised steel earth plate electrode 60x60cmx6 mm thick burried directly in ground ( earth pit not less than 2.25 Mtr deep below ground level ) with top edge of the plate not less than 1.5 Mtr below normal ground level, connected to galvanised iron strip 32x6 mm as earthing lead by means of bolts, nuts, check nuts and washers of GI or steel all as shown in electrical plate No. 3 of SSR Part-I 2009 connected all as specified or indicated and testing on completion as directed by the Engineer-in-Charge including necessary excavation & earth work in any type of soil, funnel, PCC chamber ( 1 : 3 : 6) type C1, RCC pit cover , charcol, salt including provision of earth lead protected by 32 mm dia light grade GI pipe and 20 mm dia medium grade GI Pipe for watering complete all as specified and directed by E-in-C. Please Enable Macros to View BoQ information |