| 1 | Details of Work. |
| 2 | Following works are to be done at 220 KV Sub-Station Banda & 132 KV Sub Station Atarra for replacement/shfiting of different old & obsolete 132 KV feeder control & relay panel by new panels with all cost of man, T&P and miscellaneous consumable items as per direction of supervising engineer/incharge as per detail given below :- |
| 3 | Dismantling of following old control panels installed in control room by opening of cable connections, earthing flats, nuts, bolts etc. including safe disconnetion of Bus Bar protection scheme, synchronising scheme & TBC scheme and cable loop panel to panel cables connection etc. & making of new loop connection (temporary) for other healthyness of running control panels as required. The work also includes indentification of the control cables providing suitable ferrules etc. for later use shifting of the panels from control room to place/site store at S/S. (One job per feeder/transformer) |
| 4 | 132 KV Banda-Banda 2nd Circuit C&R panel at 220 KV S/S Banda |
| 5 | 132 KV Banda-Atarra Circuit C&R panel at 132 KV S/S Atarra |
| 6 | Installation of following new control panels in control room after shifting from storage place, its grouting & earthing and termination of control cables in control and relay panels descable schedule including providing & fixing of cable glants of appropriate sizes and ferrules etc. with all other associated works as per technical specification including safe reconnection of Bus Bar protection scheme, Synchronising scheme & TBC scheme and panel to panel Cables connection etc. The work also includes control cables connections as required between control panels for looping. The commissioning of the control panel shall be done Jointly with T&C wing including troubleshooting as needed/necessary. Also inter connection diagram as per new control panel shall be submitted and got approved by the concerned supervising engineer/incharge before start of work. After completion of work schedule shall be provided as executed mentioning TB No. & ferrules for each control panel on A4 size 100 gsm with clear print. (One job per feeder/transformer) |
| 7 | 132 KV Banda-Banda 2nd Circuit C&R panel at 220 KV S/S Banda |
| 8 | 132 KV Banda-Atarra Circuit C&R panel at 132 KV S/S Atarra |
| 9 | 132 KV Atarra-Karvi C&R panel at 132 KV S/S Atarra |
| 10 | Safely Loading of 132 KV C& R panel at 132 KV S/S Naraini with help of Hydra |
| 11 | Safely Carriage of 132 KV C& R panel from 132 KV S/S Naraini to 220 KV S/S Banda |
| 12 | Safely Unloading of 132 KV C& R panel at 220 KV S/S Banda with help of Hydra |
| 13 | Safe Dismantling of Existing R,Y, B Phases 132 KV Lighting Arrestors by opening of Jumper, Earthing & Surge Counter taking due precautions and safety measures at 132 KV S/S Banda. |
| 14 | Safe Dismantling of existing 03 Nos. ALP Structure by proper opening of Nuts and Bolts and removing of Earthing flats and proper stacking of ALP Structure at 132 KV S/S Banda. |
| 15 | Erection of 03 Nos. ALP structure in New Foundation Structure (Foundation Structure is already erected). The work also includes proper earthing of the ALP Structure as per standard UPPTCL drawing at 132 KV S/S Banda. |
| 16 | Making earthing of LAs including work of digging of soil upto 1 meter depth or as per requirement, removal of stone and brick work/ RCC if required making 06 Nos. Holes in soil across structure of 132 kV Side LA. Fabrication minimum 3 meter long electrode from 40 mm at 132 KV S/S Banda. |
| 17 | Erection of 03 nos. Lightning Arrestors . The work includes Jumpering of the LAs and Earthing of the Surge Counters as per standard UPPTCL drawing at 132 KV S/S Banda. |
| 18 | Carriage of 132 kV CT from 220 kV S/S Banda store to Switchyard Area and Replacement of Y phase CT of 40 MVA T/F-I at 220 KV S/S Banda. Work include dismantling & Erection of 132 kV CT with the help of Hydra /Crane & removing the cable connection & then rewiring work, opening of Jumper & rejumpring work and all associated work for completion of Job. |
| 19 | Shifting of Various Material laying in the switchyard area at 132 KV S/S Banda to store area with the help of Hydra/Crane |
| 20 | Rates qouted by the bidders shall be without taxes. Taxes applicable if any to paid extra Please Enable Macros to View BoQ information |