| 1 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required. Group-A |
| 2 | Wiring for light/ power plug with 2X4 sq. mm FRLS/HFFR PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit along with 1 No. 4 sq. mm FRLS/HFFR PVC insulated copper conductor single core cable for loop earthing as required. |
| 3 | Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. |
| 4 | 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
| 5 | 4 x 10 sq. mm + 2 x 6 sq. mm earth wire |
| 6 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor single core cable in the existing surface/recessed steel/PVC conduit as required.1 x 1.5 sq. mm |
| 7 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.25 mm |
| 8 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. |
| 9 | 5/6 A switch |
| 10 | 3 pin 5/6 A socket outlet |
| 11 | 15/16 A switch |
| 12 | 6 pin 15/16 A socket outlet |
| 13 | Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required. |
| 14 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required |
| 15 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providng and fixing 2 nos. 3 pin 5/6 A modular socket outlet and 2 nos. 5/6 A modular switch, connections etc. as required. (For light plugs to be used in non residential buildings). |
| 16 | Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required. |
| 17 | 1 or 2 Module (75mm x 75mm) |
| 18 | 4 Module (125mm x 75mm) |
| 19 | 6 Module (200mm x 75mm) |
| 20 | 8 Module (125mm x125mm) |
| 21 | Supply and erection of sheet metal Double Door Distribution Boards IP 43-IK09 metal door (dust protected) as per IS 8623-1&3, IEC 61439-1&3 suitable for flush mounting with fully insulated copper busbars, shrouded neutral bars, earth bars, cement spill protector, color-coded interconnecting wire set, cable ties, blanking plates and circuit identifications label and of required no. of ways for mounting miniature circuit breakers/ RCBO's/ RCCB's in the distribution board (For SP&N distribution board with provision DP MCB's/ RCCB's/ RCBO's as incomer and SP MCB's as outgoings and for TP&N horizontal distribution board with provision TPN/ FP MCB's/ RCCB's/RCBO's as incomer and SP MCB's as outgoings) as per PWD General specifications including connections with suitable size of thimbles and bonding to existing earth etc. |
| 22 | 6 way ( 4+18), (Double door) (TPN type) |
| 23 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 24 | 12 way , Double door |
| 25 | Providing & Fixing of 240/415 V AC MCB with positive isolation of 10 kA breaking capacity (B/ C/D tripping characteristic as per type of load and site requirement) 4 KV impulse withstand voltage, ISImarked IS 8828(1996) / conforming to IEC 60898-1 2002, IEC 60947- 2, low watt losses, trip free mechanisum , energy limiting of class 3 as per IEC, minimum phase termination capacity of 35sq.mm. ,conductor line load reversibility , IP 20 contact protection and fitted in existing distribution board/sheets, minimum electrical operation 20,000 upto 20 A rating and 10,000 upto 63 A, 5000 for 80 A & above rating including making connections, testing etc. as required. OEM shall have submit NABL / CPRI / ERDA accrediated lab type test reports & All as per pre approved by Engineer in charge. |
| 26 | Single pole 6/10/16/32 Amp |
| 27 | Single pole and neutral 63 Amp |
| 28 | TPN 63 Amp |
| 29 | Supplying & fixing of LED Batten Tube fitting 600mm size 10/11 watt Aluminium housing with 1000 Lumens and min lumens efficiency 100 lumens/watt P.F >.90 |
| 30 | Supplying, installation, Testing & Commissioning of 18- 22 watt LED surface mounted Batten light of following body material and construction as per IS : 10322 with driver (Replaceable) as per the requirement with Driver efficiency >85% ,Operating voltage AC 140-270 Volt, freq 50/60 hz, Operating temp range -15 deg to 40 deg centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80, Flicker free, (flicker should be below 5 %), life time (LED,Driver & electrical circuitary), of minimum 50000 Burning Hours with , 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin), SDCM(Standard Deviation ColorMatching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard and trade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c connections with 1.5 sq mm FRLS, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output . LM79 & LM80 Test report from NABL lab for all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminum housing such that LED junction temperature shall not rise above 90°C). Powder coated die cast / Extruded aluminium Body (Thickness ≥ 1.20 mm) |
| 31 | Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 32 | Supply installation testing and commissioning of Ceiling Fan 3 Star Rated with Voltage Range 90 V to 300 V,Min. Air Delivery 212 CMM,Service Value 5.3 Cu.m/min/watt,Aluminium Blades ,including wiring the down rods of standard length(Upto 45 cm)with 1.5 sq.mm FR PVC insulated,copper conductor,single core cable including providing and fixing phenolic laminated sheet cover on the Fan Box etc as Required. |
| 33 | 1200mm |
| 34 | Exhaust fan 300 mm size (Metalic) |
| 35 | LED Street light fixture, powder coated pressure die cast aluminium body (System lumen efficacy ≥105 <120 lm/Watt) Supplying, installation, Testing & Commissioning of Street light LED fixture powder coated pressure die cast aluminium body with driver as per the requirement with Driver efficiency >85%, Input voltage: 140-270 Volt AC, frequency 50/60 hz, Operating temp range -5 0C to 50 0C, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC61000-3-2, P. F.≥0.95, IP-66,IK-10, CRI >70, under voltage and over voltage protection, EMIEMC As per CISPR -15, lenses for beam angle as per IESNA type I/II/III as per the width of the road and the project requirement., suitable to fit in up to65mm dia pipe, life time (LED, Driver & electrical circuitry) of minimum 50000 Burning Hours with70% of initial Lumen maintained till life endsas per LM80 extrapolation IES TM-21-11 report,CCT 3000°K / 4000°K / 5700°K /6500°K (As perANSI Bin),SDCM (Standard Deviation ColourMatching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copperconductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output.LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink ofaluminium housing such that LED junction temperature shall not rise above 90°C). |
| 36 | 100 Watt |
| 37 | Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 Meter long etc.with charcoal/ coke and salt as required. |
| 38 | Providing and fixing of 25 mm x 5 mm copper strip on surface or in recess for connections etc. as required. |
| 39 | Providing and fixing 4.00 mm dia copper wire on surface or inrecess for loop earthing as required. |
| 40 | SITC of wall/free standing floor mounted dust and vermin proof compartmentalized cubical panel for electrical Works, made out of CRCA sheet. Other parameters required as per point (a) Thickness of sheet shall not be less than 1.6 mm up to 600 mm length/width of any compartment and be of 2.0 mm above 600 mm. Load bearing structure shall be of 2.0 mm thick sheet supported by base M.S. channel if required. Side walls and cable alley compartment shaving bolted type doors with/without detachable extension type structure (b) Panel shall be duly treated for derusting in 7 tank process with de phosphating and with powder coating of minimum 70 microns on both side of panel in desired shade The panel having PU/Neoprene rubber gasket of not less than 3mm thickness, required hardware, separate detachable gland plate M.S. base channel (min 75mm), hinged door with locking arrangement for equipment/switchgear c) Interconnection between bus bar and switch gears/cable shall be rigidly supported and made out by flexible copper wires (upto 125 amp) and by solid bus bar (> 125). (d) Only outer area on all sides shall be measured & panel to be fabricated only from CPRI approved fabricator CPRI Test certificates to be submitted) All as per pre approved by Engineer in charge. |
| 41 | Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required. (Thermal Magnetic type, Adjustable type) |
| 42 | 100 Amp, 30 KA, FP MCCB ICU = 100% ICS |
| 43 | ON Load Change Over Switch FP 100 amp. (Front operated) |
| 44 | Aluminium Bus Bar 200 Amp set of 4 strips 18\\" |
| 45 | Aluminium Bus Bar 300 Amp set of 4 strips 18\\" |
| 46 | Digital Metering devices, comprising of Voltmeter, Ammeter, Selector Switch, Indicating Lamp, CT Set etc. |
| 47 | Supplying & laying of PVC insulated and PVC sheathed/ XLPE Aluminium power cable of 1.1 KV grade of following size on surfaces/ direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required. (Armoured cable) |
| 48 | 35 sq. mm 3.5 core Please Enable Macros to View BoQ information |