Bids Are Invited For 3Ph,415V,50Hz,AC, Squirrel cage Induction motor,Rating: 15 kw,Pole: 2 ,RPM: 2950,Frame: 180ML ,Mounting:B3 , DOL starting, Application:Air Blower, Encl:IP55,Insulation Class-F, Temperature rise limited to Class-B,Duty:S1,Delta connected,Greasing facility: Required ,Energy efficiency:IE2.Conforming to IS-12615,Motor should be Bidirectional, Cooling fan shall be metallic,Vendor has to submit GA drawing with offer. Vendor has to submit GA drawing & Routine test certificate along with supply.Inspection clearance will be given after testing at site. Note: Vendors must confirm the technical specification mentioned in the given technical data sheet format (Annexure-1) & submit the same along with their offer , 3 Phase Sq. Cage Induction motor with following specification: 415V+/- 10%, 50Hz+/-3% 75KW, 280SM, 4 poles, Mounting-B3, S1 duty, IP55 enclosure, TEFC, Ins. Cl.: F, Motor TB mounted at TOP, Energy Efficient motor -IE3, confirming to IS 12615, Application: Slurry pump, Coupling: V belt with pulley, Method of starting-VFD, Motor manufacturing Year must be there in the Name plate and motor manufacturing should not more than one year from the date of dispatch. Note: Vendors must confirm the technical specification mentioned in the given technical data sheet format (Annexure-2)& submit the same along with their offer , 3 Phase Sq. Cage Induction motor with following specification: 415V+/- 10%, 50Hz+/-3%, 45 KW, Frame-225SM, 4 poles, Mounting-V5 (Vertical Down), S1 duty, IP-55 enclosure, TEFC, Ins. Cl:F, Motor TB mounted at Top, DOL starting, IE3, confirming to IS 12615, Application: Sump Pump. Note: Vendors must confirm the technical specification mentioned in the given technical data sheet format (Annexure-3)&submit the same along with their offeR , 3 Phase Sq. Cage Induction motor with following specification: 415V+/- 10%, 50Hz+/-3%, 45 KW, Frame-225M, 2 poles, Mounting-B3, S1 duty, IP-55 enclosure, TEFC, Ins. Cl:F, Motor TB mounted at Top, DOL starting, IE3, confirming to IS 12615, Application: Air blower. Note: Vendors must confirm the technical specification mentioned in the given technical data sheet format (Annexure-4)& submit the same along with their offer