| 1 | S&F Dimmable smart LED Street Light fitting of 45 Watt with occupancy detection, operates in a default demmed mode at 25% of its rated wattage ensuring minimum energy consumption during inactivity and automatically switches to 100% brightness upon detecting motion or occupancy, providing full illumination only when needed including inbuilt Dynamic Power Saving Device that automatically switches off to 50% of the rated wattage on pre-set time interval including necessary fixing arrangement including taking down existing complete all as specified and directed by Engr-in-Charge. |
| 2 | S&F Dimmable smart LED Street Light fitting of 60 Watt with occupancy detection, operates in a default demmed mode at 25% of its rated wattage ensuring minimum energy consumption during inactivity and automatically switches to 100% brightness upon detecting motion or occupancy, providing full illumination only when needed including inbuilt Dynamic Power Saving Device that automatically switches off to 50% of the rated wattage on pre-set time interval including necessary fixing arrangement including taking down existing complete all as all as specified and directed by Engr-in-Charge. |
| 3 | S&F Intelligent smart LED Flood Light fitting of 50 Watt which automatically switches to 100% brightness upon detecting motion using inbuilt microwave sensor, normal mode of operation is at 30% of its rated wattage when first switched on including necessary fixing arrangement including taking down existing complete all as all as specified and directed by Engr-in-Charge. |
| 4 | S&F Intelligent smart LED Flood Light fitting of 120 Watt which automatically switches to 100% brightness upon detecting motion using inbuilt microwave sensor, normal mode of operation is at 30% of its rated wattage when first switched on including necessary fixing arrangement including taking down existing complete all as all as specified and directed by Engr-in-Charge. |
| 5 | S&F Intelligent smart LED gate Light fitting of 25 Watt with Dusk Dawn sensors that automatically switches on when ambient Lux levels go below 40 Lux and switches off at Lux levels above 50 Lux including necessary fixing arrangement including taking down existing complete all as all as specified and directed by Engr-in-Charge. |
| 6 | S&F Shockproof Filament wound poles (GRPF) of 3 Mtr height conical pole flange type, manufatured using sophisticated multi axes siemens controlled CNC filament winding machines using E class fibers having glass content of 65 to 70%. Top OD 100mm and bottom OD 145mm, tolerance of +/- 1mm, throughout thickness of 6mm with overall tolerance for length +/- 25mm and tolerance for overall thickness +/- 0.5mm. Wind speed sustainability to be 180 KMPH. Poles to be finished on the outside UV inhabitors in accordance with ASTM G 154, Izod impact strength of 80 K/Jm². Flammability test which confirms to V0 rating UL 94. Base Plate should be 300 x 300 mm, 16 mm thick in GFRP material alongwith TUV certification and batchwise test report including necessary excavation and PCC of suitable size to fixing of poles, removal of excavating materal and taking down existing GI pipe pole of any type/ size all as specified and directed by Engr-in-Charge. |
| 7 | S&F LED post top lantern of 40 watt made in die-cast aluminium with innovative glare free indirect lighting distribution, IP 65 protection suitable for outdoor including all fixing accessories to fix this light on GRPF pole and taking down existing post top lantern of any type and size all as specified and directed by Engr-in-charge. Make/ Model - BRIL 40W LED WW of Bajaj or equivalent in Havells, crompton, Philips. |
| 8 | S&F Single pointed Air Termination aluminium rod 12mm dia and 300mm long including necessary fixing arrangement including taking down existing complete all as directed |
| 9 | Supply and fixing Aluminium Strip 25 x 3.00 mm complete with saddle and fixing screw, epoxy insulators for roof or down conductor or fixed to pole or any other indicated situation for loop earthing etc, as required including making test point and testing complete all as directed. |
| 10 | M&L for Test point terminal block made of gun metal or phosphorus bronze size 75mm x 75mm x 25mm, drilled and screwed including 03 Nos 8 mm dia 25 mm long hexagonal head screws with suitable enclosure made out of 3 mm thick CRCA sheet box all as specified and as directed. |
| 11 | Material and labour for earthing complete with galvanized steel earth plate electrode 600mm X 600mm X 6mm buried directly in ground vertically to a depth not less than 2.25 meter below normal ground level (with top edge of earth plate not less than 1.5 meter below ground level) connected to galvanized iron earth lead wire 4mm dia, (main earthing lead ) by means of galvanized bolts, nuts and washers all as shown in electrical plate no 3 of MES Schedule Part-I (2009) with connected to earth test point & to main switch board with & including adequate quantity of charcoal dust and common salt alround earth plate & 15 mm dia GI pipe light grade for earth lead protection pipe for suitable length and GI pipe 20 mm dia medium grade for watering pipe with funnel & wire mesh including necessary earth work and PCC (1: 3 : 6) type C-1 for earth pit and 40 mm thick pre-cast RCC cover in 1 : 2 : 4 type B1 with 3 Nos 8 mm dia TMT bars both ways complete all as specified & directed. |
| 12 | Excavation in trenches not exceeding 1.5 mtr wide and not exceeding 1.5 mtr depth for taking out/for laying under ground cables/pipes etc and getting out any type soil all as dircted |
| 13 | Returning filling in including spreading, levelling, watering and well ramming in layers |
| 14 | Removing excavated soil to a distance n-exc 50 mtr and depositing where directed at a level n-exc 1.5 mtr above the starting point |
| 15 | Supply and spreading fine river sand in trenches for cushioning of under ground cable/filling cable ducts all as directed by Engr-in-Charge at site Note : - Only punned thickness shall be measured for payment purpose |
| 16 | Supply and lay burnt brick sub class ‘B’ of standard size laid in trenches as protection to cables all as directed. |
| 17 | M&L for Boring of holes under road, pavement, hard standing by trenchless technology technique for 40-80 mm dia pipe . |
| 18 | Supply and fixing GI pipe light grade for cable protection , laid in trenches or fixed on pole/wall for passing LT cables of sizes 40 mm dia including taking out old rusted pipe all as specified and directed.. |
| 19 | Supply and laying LT UG cable XLPE insulated heavy duty electric cable with aluminium stranded conductor, 1100 volts grade, cross sectional area 6 sq mm 2 core including taking out old unserviceable cable all as directed. |
| 20 | All as per item No 19 above but 10 sq mm 2 core Please Enable Macros to View BoQ information |
| 21 | All as per item No 19 above but 10 sq mm 2 core Please Enable Macros to View BoQ information |