| Sl. No. | Item Description |
| 1 | Material and labour for servicing / cleaning of Air cooled AC plants of 50 TR capacity, Chiller unit, cleaning and washing of cooling coil with fins using a chemical C-shine (Alkaline coil cleaner and brightener) and testing the unit (Once in a three Months) complete all as specified and as directed by Engineer-in-charge. LOCATION :- AKASH AIR COOLED AC PLANTS(Once in a three Months) |
| 2 | Material and labour for descaling of complete condenser units for central/ package type AC plants of condenser unit of Water cooled AC plantAC plant upt to 40 TR capacities by means of adding descaling chemical solution (HCL) or equivalent into the cooling tower sump as per requirements, and running the plant pump continuously till all the scale of pipes/shell are removed including removing side covers of condenser and cleaning the water tubes by means of nylon brushes till the scaling is removed and refixing of covers including replacement of neoprene rubber gasket and refixing pipe connection etc. to entire satisfaction of engineer-in-charge complete all as specified and as directed by Engineer-in-charge. LOCATION :- OLD, 3AC Igloo AC Plant AND NEW AC PLANT (Once in a three Months) |
| 3 | Material and labour for cleaning of cooling tower existing size, water basin and makeup tank with the help of chemical and nylon brush, removing and refixing of PVC finches after washing, cleaning of condenser pipe line ( inlet and outlet) including painting of out side of cooling tower with inlet and outlet pipe line with one coat synthetic enamel paint of colour approved by Engineer in Charge and inside painting of water tank of cooling tower using water proof black japan paint one coat including changing of unserviceable PVC guard, water distibutor, PVC pipe, and all connected minor items of up to 100 TR capacity of the AC plants at different locations complete all as specified and as directed. LOCATION :- OLD AND NEW AC PLANT |
| 4 | Material and labour for servicing of cooling coils and air filters of AHUs intalled at air conditioning plant by removing air filters and fixing after cleaning with air blower and water and cleaning agent , cleaning of cooling coilwith wire brush and air blower and water spray pump after spraying scale gun or equivalant chemical suitable for aluminium fins and straighting the fins of cooling coil by using suitable brush for any capacity of AHU complete all as specified and as directed by Engineer-in-charge. LOCATON :- NEW AC PLANT, OLD AC PLANT , 3 AC Igloo AC AND AKASH AC PLANTS AKASH |
| 5 | Material and labour for servicing / Cleaning and testing of Electrically Operated Pan type Humidifier capacity 9 KW alongwith all necessary items fitting and all suitable / all necessary electrical wiring from electrical panle to Humidifier complete all as specified and as directed by Engineer-in-charge. LOCATION :- AKASH AC PLANTS |
| 6 | Material and labour for servicing / Cleaning and testing of Pressurization unit in cold water line ( PSU-225 as per site) alongwith all necessary items fitting and all suitable / all necessary electrical wiring complete all as specified and as directed by Engineer-in-charge. LOCATION :- AKASH AC PLANTS |
| 7 | Material and labour for servicing / Cleaning and testing of Pressurization unit in Hot water line ( PSU-225 as per site) alongwith all necessary items fitting and all suitable / all necessary electrical wiring complete all as specified and as directed by Engineer-in-charge. LOCATION :- AKASH AC PLANTS |
| 8 | Material and labour for servicing , Cleaning , and Greasing , Chiller , HWG Pumps , AHU and CT Motors alongwith all necessary minor items/ fitting i.e bearing , star coupling , screws , nuts and bolts etc complete all as specified and as directed by Engineer-in-charge. LOCATION :- NEW AC PLANT , OLD AC PLANT AND AIR COOLED AC PLANTS AKASH |
| 9 | Supply and fixing in replacement PLC based control module with digital display of Package / Central type Water cooled / Air cooled AC plant unit suitable up to 50 TR capacity or as per site make / requirment having start / stop functions, settings option to change the seetings complete all as specified and as directed by Engineer-in-charge. LOCATION :- NEW AC PLANT , OLD AC PLANT AND AIR COOLED AC PLANTS AKASH |
| 10 | Taking down old unserviceable expansion valve 13/20 TR compressor suitable for using upto 50 TR Air/water cooled centralised AC plant double unit complete all as specified and as directed by Engineer-in-charge. LOCATION :- NEW AC PLANT , OLD AC PLANT AND AIR COOLED AC PLANTS AKASH |
| 11 | Taking down old unserviceable Air vent valve 15 / 20 mm and supply and fixing testing of air vent valve 15 mm complete all as specified and as directed by Engineer-in-charge. LOCATION :- NEW AC PLANT , OLD AC PLANT AND AIR COOLED AC PLANTS AKASH |
| 12 | Material and labour for servicing / Cleaning and testing of HWG capacity 55 KW / 63 KW capacity safely, checking and replacement of burnt out / non working thermostate / suitable elements as per site conditions , all internal control wiring alongwith all necessary connections check and repair complete all as specified and as directed by Engineer-in-charge.Note :- Thermostate and elements paid separately. LOCATION :- NEW AC PLANT , OLD AC PLANT AND AIR COOLED AC PLANTS AKASH |
| 13 | Supply and installation in replacement Digital step contoller (PLC) of Hot Water Generator 55 KW / 63 KW capacity along with Voltmeter and ammeter with all necessary wiring / connection etc and testing complete all as specified and as directed by Engineer-in-charge. LOCATION :- NEW AC PLANT , OLD AC PLANT AND AIR COOLED AC PLANTS AKASH |
| 14 | Supply and fixing new scroll compressor of capacity 13 TR suitable for 39 TR Water cooled AC plant of make Blue Star including removing of refrigerent R-22 in an empty cylinder, flushing the system, carrying out nitrogen gas pressure testing and accordingly leak reparing(if any), vaccumising the system, charging the refrigerent - R-22 or as per site conditions including taking down unserviceable /burnt scroll compressor of capacity 13 TR complete all as specified and directed by Engineer- in- charge. Note:- Initial charge of refrigerent will be paid separately. LOCATION :- OLD AC PLANT AND NEW AC PLANT |
| 15 | Supply and fixing new scroll compressor of capacity 20 TR suitable for 60 TR (3 x 20 TR) or as per site conditon , air cooled plant of make Blue Star including removing of refrigerent empty cylinder R-407 or exising flushing the system with nitrogen gas pressure testing and leak repairing vaccumising the system 700 micron charging the refrigerent R-407c or as per per site requirment Including taking down unserviceable / burnt scroll compressor of capacity 20 TR complete all as specified and as directed by Engineer-in-charge. Note : Initial charge of refrigerent will be paid seperately. LOCATION :- AKASH AC PLANTS |
| 16 | Supply and charging refrigerent in existing compresser,using refrigerent R-22/R-407a/R-134 or as per site requirment in sealed container complete all as specified and as directed by Engineer-in-charge. LOCATION :- NEW AC PLANT , OLD AC PLANT AND AIR COOLED AC PLANTS AKASH |
| 17 | Material and labour for providing and fixing in replacement in position the mercury-in-glass industrial type thermometers gauges of existing specifications complete all as specified and as directed by Engineer-in-charge. LOCATION :- NEW AC PLANT , OLD AC PLANT AND AIR COOLED AC PLANTS AKASH |
| 18 | Material and labour for providing and fixing in replacement in position the industrial type pressure gauges complete all as specified and as directed by Engineer-in-charge. LOCATION :- NEW AC PLANT , OLD AC PLANT AND AIR COOLED AC PLANTS AKASH |
| 19 | Material and labour in replacement of fan belt any size or as per site requirment of suitable model for AHU motor complete all as specified and as directed by Engineer-in-charge. LOCATION :- NEW AC PLANT , OLD AC PLANT AND AIR COOLED AC PLANTS AKASH |
| 20 | Material and labour for liquid line filter drier suitable for any capacity of air / Water cooled scroll unit of make Blue star including removing of refrigerent empty cylinder R-407c / R-22 /R-134 or as per site requirment flushing the system with nitrogen gas pressure testing and leak repairing vaccumising the system 700 micron, charging the refrigerent of R-407 / R22 /R-134 or as per site conditions including taking down unserviceable liquid line filter drier complete all as specified and as directed by Engineer-in-charge. Note :- Refrigerent will be paid separately. LOCATION :- NEW AC PLANT , OLD AC PLANT AND AIR COOLED AC PLANTS AKASH |
| 21 | Supply and fixing in replacement AHU Pre Filter overall size as per site 610x305x50mm complete with all fittings as per site requirement complete all as specified and as directed by Engineer-in-charge LOCATION :- AKASH AC PLANTS |
| 22 | Supply and, fixing in replacement AHU Pre Filter overall size as per site 610x305x50mm complete with all fittings as per site requirement complete all as specified and as directed by Engineer-in-charge LOCATION :- AKASH AC PLANTS |
| 23 | Supply and fixing and testing in replacement of AHU Secondary / BAG filter overall size as per site 610 x 610 x305mm and all fitting as per site requirment complete all as specified and as directed by Engineer-in-charge LOCATION :- AKASH AC PLANTS |
| 24 | Supply and fixing in replacement of AHU Secondary / BAG filter overall size as per site 610 x 610x305mm with all fitting as per site requirement amd testing complete all as specified and as directed by Engineer-in-charge. LOCATION :- AKASH AC PLANTS |
| 25 | Supply and fixing in replacement of AHU front filter overall size as per site 285 x 455 x 50mm and all fitting as per site requirment and testing, complete all as specified and as directed by Engineer-in-charge. LOCATION :- AKASH AC PLANTS |
| 26 | Supply and fixing in replacement AHU Pre Filter overall size as per site 595 x 290 x 50mm , box type or of existing size and testing complete including taking down unserviceable filters all as specified and as directed by Engineer-in-charge. LOCATION :- NEW AC PLANT |
| 27 | Supply and fixing in replacement AHU Pre Filter overall size as per site 595 x 595 x 50mm , box type or of existing size and testing complete including taking down unserviceable filters all as specified and as directed by Engineer-in-charge. LOCATION :- NEW AC PLANT |
| 28 | Supply and fixing in replacement AHU Pre Filter overall size as per site 305 x 610 x 50mm , box type or of existing size with all fittings and testing complete including taking down unserviceable filters all as specified and as directed by Engineer-in-charge. LOCATION :- OLD AC PLANT |
| 29 | Supply and fixing in replacement of AHU Pre Filter overall size as per site 610 x 610 x 50mm with all fitting as per site requirement and testing complete including taking down the unserviceable filters complete all as specified and as directed by Engineer-in-charge. LOCATION :- OLD AC PLANTS |
| 30 | Supply and fixing in replacement of AHU Pre Filter overall size as per site 305 x 610 x 305 mm with all complete fitting as per site requirement and testing complete including taking down the unserviceable filters complete all as specified and as directed by Engineer-in-charge. LOCATION :- OLD AC PLANTS |
| 31 | Supply and fixing in replacement of AHU Pre Filter overall size as per site 610 x 610 x 305 mm with all complete fitting as per site requirement and testing complete including taking down the unserviceable filters complete all as specified and as directed by Engineer-in-charge. LOCATION :- OLD AC PLANTS |
| 32 | Supply and fixing in replacement pressure switch (HP switch) upto 260 PSI NO and 190 PSI NC or as per site condition/requirements including removing of refrigerent empty cylinder and checking of pressure testing leak testing vaccume the system of 700 micron charging the refrigerent in the system complete all as specified and as directed by Engineer-in-charge. Note : Charge of refrigerent will be paid seperately. LOCATION :- NEW AC, OLD AC AND AKASH AC PLANTS |
| 33 | Supply and fixing in replacement of low pressure switch (LP switch) upto 25 PSI NO and 45 PSI NC including removing of refrigerent empty cylinder and checking of pressure testing leak testing vaccume the system of 700 micron charging the refrigerent in the system ccomplete all as specified and as directed by Engineer-in-charge. Note : Charge of refrigerent will be paid seperately. LOCATION :- NEW AC, OLD AC AND AKASH AC PLANTS |
| 34 | Disconnecting, dismantling the defective three phase induction motor 415 volts 50 Hz of any RPM for motor of following capacity and rewinding with super enamelled copper wire of best quality of existing size / gauge and weight including replacement of insulation material, varnish bearing connection plate and all other petty items required to make the motor in functional and reassembling the motor including installation commissioning and testing on full load complete all as specified and as directed by Engineer-in-charge.NOTE :- (i) Disconnecting and removing the electric motor from installed position and loading unloading, transporting to authorised/approved work shop(ii) Dismantling existing burnt winding from the motor and rewinding complete with super enamelled copper winding wire of existing guage including all material such as insulated paper sleeves tape varnish etc complete for class F insulation and including shaft metalising, bearing cover slieving , necessary replacement of cooling fan, nut-bolt etc(iii) Loading, unloading and transporting motor & reinstalling in position and in alignment including electric conection commissioning and testing in actual working condition for 8 hours continuosly to check the performance on full load and designed RPM to the complete satisfaction of Engr-in-Charge all as specified and directed |
| 35 | (a) Induction Motor of Capacity up to 15 HP ( AHU Motor) LOC:- NEW AC, OLD AC AND AKASH AC PLANTS |
| 36 | (b) Induction Motor of Capacity up to 10 HP (Chiller Motor/ HWG motor) LOC:- NEW AC, OLD AC AND AKASH AC PLANTS |
| 37 | Disconnecting, dismantling of centrifugal monoblock pump set of up to 10 HP HP Capacity (Chiller Pump / HWG Pump) of any RPM and dismantling and replacement of defective parts such as impeller nut, glant, impeller key, gland packing water deflector bush bearings sleeve, gasket, volute stud and nuts suction and delivery flange and stud and nuts and all other petty items required to make the pumpset in functional and reassembling the pumpset including installation commissioning and testing complete all as specified and as directed by Engineer-in-charge. LOC:- NEW AC, OLD AC AND AKASH AC PLANTS |
| 38 | Disconnecting, dismantling the defective three phase CT Fan motor 415 volts 50 Hz of any RPM for motor of any capacity or as per site conditon and rewinding with super enamelled copper wire of best quality of existing size / gauge and weight including replacement of insulation material, varnish bearing connection plate and all other petty items required to make the motor in functional and reassembling the motor including installation commissioning and testing on full load complete all as specified and as directed by Engineer-in-charge.NOTE :- (i) Disconnecting and removing the electric motor from installed position and loading unloading, transporting to authorised/approved work shop(ii) Dismantling existing burnt winding from the motor and rewinding complete with super enamelled copper winding wire of existing guage including all material such as insulated paper sleeves tape varnish etc complete for class F insulation and including shaft metalising, bearing cover slieving , necessary replacement of cooling fan, nut-bolt etc(iii) Loading, unloading and transporting motor & reinstalling in position and in alignment including electric conection commissioning and testing in actual working condition for 8 hours continuosly to check the performance on full load and designed RPM to the complete satisfaction of Engr-in-Charge all as specified and directed LOC:- NEW AC, OLD AC PLANT |
| 39 | Disconnecting, dismantling the defective three phase Air coold AC Plant Chiller Unit Fan Motor 415 volts 50 Hz of any RPM and any capacity Motor or as per site conditon and rewinding with super enamelled copper wire of best quality of existing size / gauge and weight including replacement of insulation material, varnish bearing connection plate and all other petty items required to make the motor in functional and reassembling the motor including installation commissioning and testing on full load complete all as specified and as directed by Engineer-in-charge.NOTE :- (i) Disconnecting and removing the electric motor from installed position and loading unloading, transporting to authorised/approved work shop(ii) Dismantling existing burnt winding from the motor and rewinding complete with super enamelled copper winding wire of existing guage including all material such as insulated paper sleeves tape varnish etc complete for class F insulation and including shaft metalising, bearing cover slieving , necessary replacement of cooling fan, nut-bolt etc(iii) Loading, unloading and transporting motor & reinstalling in position and in alignment including electric conection commissioning and testing in actual working condition for 8 hours continuosly to check the performance on full load and designed RPM to the complete satisfaction of Engr-in-Charge all as specified and directed. LOCATION :- AKASH AC PLANT |
| 40 | Material and labour for taking out all old unserviceable PVC fills from cooling tower of capacity upto 100 TR and supply anf fixing of fills of size 300mm x 200mm x 150mm (Approx fils qty 80 -100 Nos)all required at site or existing size of fills at site conditions complete all as specified and as directed by Engineer-in-charge. LOCATION :- NEW AC AND OLD AC PLANT |
| 41 | Supply and fixing in replacement of air intake mesh suitable / as per existing size for covering of cooling tower alongwith all necessary items complete all as specified and as directed by Engineer-in-charge. LOCATION :- NEW AC AND OLD AC PLANT |
| 42 | Material and labour for replacement of sprinkler of 90/100 TR cooling tower including all necessary connections complete all as specified and as directed by Engineer-in-charge.. LOCATION :- NEW AC AND OLD AC PLANT |
| 43 | Taking down existing unsv existing any size of cable Supply,laying,jointing,testing of LT cable, XLPE insulated,PVC insulated armoured, with aluminium conductor ,1100V grade complete all as specified and directed for 4 core 16 sq mm. |
| 44 | Supplying ,laying,jointing,commossioning and testing of XLPE insulated, PVC insulated , armoured, with aluminium conductor ,1100 V grade cross sectional area 35 sqmx 4 core, laid in trenches/ along poles on walls in floor/ through roads etc including taking down existing unserviceable existing any size of cable complete all as specified and as directed by Engineer-in-charge.Note :- Excavation and earth work, sand cushioning, cable cover etc shall be measured and paid separately under appropiate items of this BOQ.Location :- NEW AC Plant panel to AHU 1 & AHU 2 |
| 45 | Excavation in trenches n. exc 1.5m wide and n. exc1.5m deep and getting out as in soft/loose soil including forming bottom surfaces to required level or slope for taking out existing cables,brick / PCC cable cover and relaying new/old cable complete all specified and as directed by Engineer- in-charge. |
| 46 | Material and labour for laying fine dry river sand in trenches 8cm deep before laying the cable and 15 cm after laying the cable for cushioning to cable for protection of cable complete all as specified and as directed by Engineer-in-charge. Note :- Punned thickness will be measured for payment. |
| 47 | Supply and laying factory made un reinforced precast concrete cable cover class LV, type-1, flat, size 250 x 150 x 40mm with ISI markcomplete all as specified and as directed by Engineer-in-charge. |
| 48 | Material and labour for removal of surplus excavated soil to a distance exc 50 m but not exc in 100 m and deposited where directed at a level n'exc 50 m above the starting point complete all as specified and as directed by Engineer-in-charge. |
| 49 | Material and labour for returning filling soil in trenches including spreading, leveling watering and well ramming in 25mm thick layer complete all as specified and as specified and as directed by Engineer-in-charge. |
| 50 | and supply and fixing of heating strip suitable for 13/20 TR or as per site conditons of compresser with all necessary connections including taking down old unservicable heating strips complete all as specified and directed by Engineer-in-charge. LOCATION :- NEW AC , OLD AC AND AKASH AC PLANTS |
| 51 | Supply, installation in replacement ,testing and commissioning electric rod heater of 6.12 KW for HWG/ of suitable Capacity of Hot water generator complete all as specified and as directed and as directed by Engineer-in-charge. LOCATION :- NEW AC , OLD AC AND AKASH AC PLANTS |
| 52 | Material and labour for preparation of old treated surface surface of MS / CI pipes inlet / out let pipes over 10 cm with or girth and applying two coat of synthetic enamel paint over a coat of red oxide as per colour code given by the deptt complete all as specified and as directed by Engineer-in-charge. LOCATION :- NEW AC , OLD AC AND AKASH AC PLANTS |
| 53 | Servicing / cleaning of unserviceable Y strainer upto 100mm size , including minor parts compete all as specified and directed by Engineer-in-Charge. LOCATION :- NEW AC , OLD AC AND AKASH AC PLANTS |
| 54 | Supply , installation in replacement and testing of temperature on / off controller, 8 Amps relay for compressor (Exsiting Model No SZ-7510T at site) with sensor connected in MAGs (No and Nc) complete all as specified and as directed by Engineer-in-charge. LOCATION :- NEW AC PLANTS |
| 55 | Supply and fixing in replacement super GEC 1.5 Sqmm 2 core copper white twin flate double layer insulation appliances wire , 23/52 complete all as specified and as directed by Engineer-in-charge.Loc :- NEW AC PLANT , For connection to sensor , AC plant panel to AC 1 MAG and AC 2 MAG |
| 56 | Supply and fixing in replacement butter fly valve of size 100 mm with rubber packing complete all as specified and as directed by Engineer-in-charge. |
| 57 | Supply and fixing in replacement butter fly valve of size 80 mm with rubber packing complete all as specified and as directed by Engineer-in-charge. |
| 58 | Supply and fixing in replacement butter fly valve of size 65 mm with rubber packing complete all as specified and as directed by Engineer-in-charge. |
| 59 | Supply and fixing in replacement butter fly valve of size 50 mm with rubber packing complete all as specified and as directed by Engineer-in-charge. |
| 60 | Supply and fixing in replacement butter fly valve of size 32 mm with rubber packing complete all as specified and as directed by Engineer-in-charge. |
| 61 | Supply and fixing in replacement butter fly valve of size15 mm with rubber packing complete all as specified and as directed by Engineer-in-charge. |
| 62 | Supply and fixing testing of water flow switch ( Flow rate 150 psi) as per existing make and model / suitable size including suitable wiring with control panel including taking down old unserviceable water flow switch of any size, complete all as specified and as directed by Engineer-in-charge. LOCATION :- NEW AC , OLD AC AND AKASH AC PLANTS |
| 63 | Supply and fixing in replacement Chilled water sensor as per existing make and type complete all as specified and as directed by Engineer-in-charge. LOCATION :- NEW AC , OLD AC AND AKASH AC PLANTS |
| 64 | Supply and fixing in replacement over load relay 9 to 15 amp complete all as specified and as directed by Engineer-in-charge. |
| 65 | Supply and fixing in replacement of over load relay 20 amp complete all as specified and as directed. |
| 66 | Supply and fixing in replacement DOL starter for 5.5/3.5 KW motor or as per site requirment complete all as specified and as directed by Engineer-in-charge. |
| 67 | Supply and fixing in replacement terminal connecting plate suitable for 15/10/7.5 HP/5 HP/3HP/2HP monoblock pumpset complete all as specified and as directed by Engineer-in-charge. LOCATION :- NEW AC , OLD AC AND AKASH AC PLANTS |
| 68 | Supply, laying and testing MS ERW pipes 80 mm bore having wall thickness 6.00 mm confirming to IS 3589 (1981) thickness, laid in trenches/ alongwall/ under road /on surface etc including cutting bending and welding as per site requirement and specials with flanged and drilled ends, jointing materials like nuts, bolts and gasket etc including dimantling/taking down/out existing unserviceable MS pipe, complete all as specified and as directed by Engineer-in-charge. Note:- Excavation and earth work shall be measured and paid separately under appropiate items of this schedule. LOCATION :- NEW AC PLANT |
| 69 | Supply, laying and testing MS ERW pipes 50 mm bore having wall thickness 6.00 mm confirming to IS 3589 (1981) thickness, laid in trenches/ alongwall/ under road /on surface etc including cutting bending and welding as per site requirement and specials with flanged and drilled ends, jointing materials like nuts, bolts and gasket etc including dimantling/taking down/out existing unserviceable MS pipe, complete all as specified and as directed by Engineer-in-charge. Note:- Excavation and earth work shall be measured and paid separately under appropiate items of this schedule. LOCATION :- NEW AC PLANT |
| 70 | Supply and fixing in replacement AC contactor upto 63 Amp 415 volts complete all as specified and as directed by Engineer-in-charge. |
| 71 | Supply and fixing in replacement AC contactor 100 Amp 415 volts complete all as specified and as directed by Engineer-in-charge. |
| 72 | Supply and fixing in replacement over load relay 9 to 15 amp complete all as specified and as directed by Engineer-in-charge. |
| 73 | Supply and fixing in replacement of over load relay 6 to 10 amp complete all as specified and as directed by Engineer-in-charge. |
| 74 | Supply and fixing in replacement of air fire damper suitable as per site conditition complete all as specified and as directed by Engineer-in-charge. |
| 75 | Supply and fixing fire resistant canvas , for HVAC system , Ducting alongwith openable and closeable way for recording of tempreture through AHU complete all as specified and directed by Engineer-in-Charge. LOCATION :- NEW AC , OLD AC AND AKASH AC PLANT |
| 76 | Supply, installation and testing LED Solar light fitting 20 Watt including lithium ion battery, solar panel, charge controller with dusk soen sensor complete fixed on 100 mm bore GI pipe medium grade at height of 8 m from ground level and embedded 1.5 m in PCC including excavation, Earth work, PCC 1:3:6 Type C-2 in foundation of pole, PCC 1:2:4 type B-I as in coping and applying two coats of aluminium paint on GI pipe above coping and black bituminious paint for the portion embedded in PCC complete all as specified and directed by Engineer-in-Charge. |
| 77 | Supply and fixing in replacement MCB TPN 40-100 Amp 415 volt , 10kA complete all as specified and as directed by Engineer-in-charge. |
| 78 | Supply and fixing in replacement MCCB 160 Amp, 4P, 415 volt , 36KA complete all as specified and as directed by Engineer-in-charge. |
| 79 | Supply and fixing in replacement MCCB 200Amp, 4P, 415 volt , 36KA complete all as specified and as directed by Engineer-in-charge. |
| 80 | Supply and fixing in replacement of MCCB 400 Amp, 4P, 415 volt , 36KA complete all as specified and as directed by Engineer-in-charge. |
| 81 | Supply and fixing brass float valve using inside Pan type hudifire all as specified and directed by Engineer-in-Charge |
| 82 | Material and labour for servicing, setting, Dust cleaning and testing of VFD (Cat Part No - 25A-D017N104 ) of AHU Panel , Power 7.5 KW/10 HP , 3 Phase alongwith all minor wiring, screws, etc complete all as specifed and directed by Engineer-in-Charge. |
| 83 | Supply and fixing in repair rotational moulded polyethylene water storage tank (cylindrical vertical tank with close top) f 1000 Ltr capacity, triple layer with and including 20mm dia ball brass valve, high pressure, with polythene float and fly nut complete, screwed for 20 mm bore dia iron pipe or brass ferrule,and Gl tank nipple etc, complete all as specified and directed by Engineer-in-charge. LOCATION :- AKASH AC PLANTS |
| 84 | Supply, fixing and testing of VFD for AHU Motor as per existing Model/Capacity or as per site condition alongwith all connected items complete as directed by Engineer-in-charge. LOCATION :- AKASH AC PLANTS |
| 85 | Supply, installation and testing of chiller Pump cpacity upto 10 HP proper fixing with existing motor , or as per exisitng size or Model etc complete all as directed by Engineer-in-Charge. LOCATION :- AKASH AC PLANTS |
| 86 | Supply, fixing and testing of Humidifier DB as per existing make / Model alongwith all MCBs , wiring etc complete as directed by Engineer-in-Charge.LOCATION :- AKASH AC PLANTS |
| 87 | Supply , installation and testing of Damper Actuator for control of Air alongwith with connected items etc or as per existing size / make / model complete all as directed by Engineer-in-Charge. LOCATION :- AKASH AC PLANTS |
| 88 | Supply , installation and testing of Honewell size 65mm dia or as per existing or site condition , complete all as directed by Engineer-in-Charge.LOCATION :- AKASH AC PLANTS |
| 89 | Supply , installation and testing of Honewell size 32mm dia or as per existing or site condition , complete all as directed by Engineer-in-Charge.LOCATION :- AKASH AC PLANTS |
| 90 | Material and labour for earthing complete with galvanized steel earth plate electrode 600mm x 600mm x 6mm thick buried directly in ground (earth pit not less than 2.25 meters deep below normal ground level) with top edge of plate not less than 1.5 meter deep below normal ground level connected to galvanized earth strip of size 25 x 6 mm, 7.5m long means of bolts, nuts, check nuts and washers of galvanized iron or steel all as shown in electrical plate No 3 of SSR part I connecting to earthing test point and testing on completion with and including PCC pit in mix 1:3:6 type c1 with RCC 1:2:4 type B-1, 40mm thick cover reinforced with 6mm dia MS bars 3 Nos both ways with lifting book made out of 6mm dia bar, watering arrangement with funnel and wire mesh and 20mm bore light grade GI watering pipe, common salt and charcoal filling, necessary excavation and earth work, complete including taking out unserviceable earthing complete all as specified and as directed by Engineer-in-charge. |
| 91 | Supply and fixing Pump Coupling alongwith all minor connected items or as per existing size or as per site condition complete all as directed by Engineer-in-charge. LOCATION :- AKASH AC PLANTS |
| 92 | Taking up condenser / Evaporator from AC plant and transporting to existing make / approved manufacture workshop and removing old unserviceable copper tube from evaporator / condenser of Air cooled AC Palnt and supply, fixing testing and commissioning copper tube cell for existing size and capacity and nos of copper cell for condenser / evaporator suitable for 50 TR Air cooled scroll unit complete all as specified and as directed by Engineer-in-charge. LOCATION :- AKASH AC PLANTS |
| 93 | Taking up condenser / Evaporator from AC plant and transporting to existing make / approved manufacture workshop and removing old unserviceable copper tube from evaporator / condenser of Water Cooled AC Palnt and supply, fixing testing and commissioning copper tube cell for existing size and capacity and nos of copper cell for condenser / evaporator suitable for 38.1 TR Water Cooled scroll unit complete all as specified and as directed by Engineer-in-charge. LOCATION :- NEW AC PLANT |
| 94 | Taking out damaged / leakage copper cooling coil circuits inside AHU and transporting to approved manufacture workshop and removing old UNSV / damaged copper tube of any Capacity of AHU and supply, installations and testing and commissioning copper tube cell of existing size or as per site requirement complete all as directed by Engineer-in-charge. LOCATION :- NEW , OLD AND AKASH AC PLANTS |
| 95 | Supply and installations in replacement of NRV proper fixing of Chiller / Condensor / Hot Water Pump Pipe line as per existing size or as per site conditions complete all as directed by Engineer-in-charge. LOCATION :- NEW AC PLANT |
| 96 | Supply and fixing in replacement of VFD for Chiller motor/Condensor Motor/ Hot water Generator Motor or as per existing Model/Capacity or as per site condition alongwith all connected items and testing complete as directed by Engineer-in-charge. LOCATION :- NEW AC PLANT |
| 97 | Supply and fixing HTC Digital Hydrometer as per requirement in AC Shed for Noted tempreture parametes complete all as specified and as directed by Engineer-in-charge . |
| 98 | Compressive maintenance and repairs to AC plants including attending break down complaints and stand by duty on the days of VIP visits for the following capacity Air Conditioners, electrically operated with automatic / manual dual controlled operation located in the various technical complex bldg all as specified and directed by Engineer-in-charge. |
| 99 | (a) Scroll type Water Cooled AC plant 2 x 39 TR and 1 x 39 TR Standby at New Ac Plant Tech Area. Make:- BLUE STAR |
| 100 | (b) Scroll type Water Cooled AC plant 2 x 37.5 TR and 1 x 37.5 TR Standby at OLD AC Plant Tech Area. Make:- BLUE STAR |
| 101 | (c) Scroll type Air cooled AC Plant 2 x 50 TR ( 01 x Stand By) total 24 Nos AC Plants at AKASH Complex , Make:- Blue Star |
| 102 | Notes FOR ITEMS SER NO 96.1,96.02 and 96.03 :- (i) The rate quoted by the contractor include the rate for inspection / maintenance and testing of Air Conditioning Plant only through the authorised OEM service engineer, checking of water flow, over heating of compressor, serviceability of all components like refrigerant gas pressure switch (High/Low) sensors, condenser / chiller water flow switches, crank case heater, thermostatic expansion valve, electric controle centre micro computer control system, PCBs, SMPS, MCCB, MCBs control wiring alongwith all connected items of plant etc.(ii) The duration of the checking is once in every month throughout the currency of contract through OEM authorized service engineer/dealers.(iii) Periodical test report to be submitted monthly through the authorized OEM service engineer duly signed.(iv) Report of monthly inspection maintenance carried out by the contractor also to be submitted on every inspection / maintenance and after rectification of any breakdown.(v) Apart from the monthly periodic inspection the contractor is liable for conducting inspection/maintenance/repair on call basis through the OEM if required. On call the contractor is required to attend the complaint within 24 hrs. Not attending the complaint within 24 hrs contractor shall liable to pay a penalty Rs 2000/- per day.(vi) The components/spares/consumables required for AC plants will be measured and paid separately under the relevent items here in above mentioned. Please Enable Macros to View BoQ information |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |
Copyright © 2026 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail