| 1 | Arranging for lifting of exiting submersible pumpset from existing borewell by arranging all acessories & tools such as chain pulley, plumbing & electrical tools required etc testing physical damages if any & ascertaining etc as reqd. | Arranging for lifting of exiting submersible pumpset from existing borewell by arranging all acessories & tools such as chain pulley, plumbing & electrical tools required etc testing physical damages if any & ascertaining etc as reqd. |
| 2 | Arranging for testing of decomissioned submersible pumset at work shop including loading , unloading transporting to work shop & returning the same to site etc as reqd i/c making water tight joint with minor materials etc as redq. | Arranging for testing of decomissioned submersible pumset at work shop including loading , unloading transporting to work shop & returning the same to site etc as reqd i/c making water tight joint with minor materials etc as redq. |
| 3 | Supplying & installation of 9 mtr RCC Pole for extending 1.1 KV power ariel bunched cable to staff quarters block & providing CC for installation etc as reqd. | Supplying & installation of 9 mtr RCC Pole for extending 1.1 KV power ariel bunched cable to staff quarters block & providing CC for installation etc as reqd. |
| 4 | S/F MS frame work made of angle iron / MS flat i/c cutting, welding, drilling holes, painting, grouting etc as reqd.( For cross arm on pole & bldg for stringing OHABC etc as reqd). | S/F MS frame work made of angle iron / MS flat i/c cutting, welding, drilling holes, painting, grouting etc as reqd.( For cross arm on pole & bldg for stringing OHABC etc as reqd). |
| 5 | Supplying of PVC insulated & PVC sheathed 1.1 KV power ariel bunched cable of size 3 x 50+ 1 x 35 + 1 x 16 Sqmm coated massanger wire suitable for arieal service connection i/c Supplying & fixing necessary clamps , hooks and spring arrangement, with suitable hardware arrangement at end points and intermedient points as applicable as per HESCOM requirements, testing and commissioning etc. as required. | Supplying of PVC insulated & PVC sheathed 1.1 KV power ariel bunched cable of size 3 x 50+ 1 x 35 + 1 x 16 Sqmm coated massanger wire suitable for arieal service connection i/c Supplying & fixing necessary clamps , hooks and spring arrangement, with suitable hardware arrangement at end points and intermedient points as applicable as per HESCOM requirements, testing and commissioning etc. as required. |
| 6 | Supplying of PVC insulated & PVC sheathed 1.1 KV power ariel bunched cable of size 3 x 35+ 1 x 25 + 1 x 16 Sqmm coated massanger wire suitable for arieal service connection i/c Supplying & fixing necessary clamps , hooks and spring arrangement, with suitable hardware arrangement at end points and intermedient points as applicable as per HESCOM requirements,testing and commissioning etc. as required. | Supplying of PVC insulated & PVC sheathed 1.1 KV power ariel bunched cable of size 3 x 35+ 1 x 25 + 1 x 16 Sqmm coated massanger wire suitable for arieal service connection i/c Supplying & fixing necessary clamps , hooks and spring arrangement, with suitable hardware arrangement at end points and intermedient points as applicable as per HESCOM requirements,testing and commissioning etc. as required. |
| 7 | Laying/Stringing/erecting of PVC insulated & PVC sheathed 1.1 KV power ariel bunched cable of size 3 x 50+ 1 x 35 + 1 x 16 Sq mm coated massanger wire with suitable hardware arrangement at end points and intermedient points as applicable as per HESCOM requirements i/c connection testing and commissioning etc. as required. | Laying/Stringing/erecting of PVC insulated & PVC sheathed 1.1 KV power ariel bunched cable of size 3 x 50+ 1 x 35 + 1 x 16 Sq mm coated massanger wire with suitable hardware arrangement at end points and intermedient points as applicable as per HESCOM requirements i/c connection testing and commissioning etc. as required. |
| 8 | Supplying and fixing of 50 mm dia UPVC/APVC for on surface of wall / pole for cable protection clamping etc. complete as reqd. | Supplying and fixing of 50 mm dia UPVC/APVC for on surface of wall / pole for cable protection clamping etc. complete as reqd. |
| 9 | Providing and fixing 6 SWG GI wire on surface or in recess for loop earthing along with existing surfaced / recessed conduit / sub main wiring / cable as required. | Providing and fixing 6 SWG GI wire on surface or in recess for loop earthing along with existing surfaced / recessed conduit / sub main wiring / cable as required. |
| 10 | S/F of 63 Amps Rewireable type Porcelain fuse cutouts - 3 Nos.with neutral link -1No in the existing meter box including interconnection with 10sq.mm flexible copper conductor cable etc as required. | S/F of 63 Amps Rewireable type Porcelain fuse cutouts - 3 Nos.with neutral link -1No in the existing meter box including interconnection with 10sq.mm flexible copper conductor cable etc as required. |
| 11 | Arranging for disconnecting exising transformer connection to main isolating the same for safety, extending the LT power supply (new) with connecting to the TC making suitable arrangement for safety of the installation & disconnection for review etc as reqd. | Arranging for disconnecting exising transformer connection to main isolating the same for safety, extending the LT power supply (new) with connecting to the TC making suitable arrangement for safety of the installation & disconnection for review etc as reqd. |