| 1 | Distribution wiring in 2 x 22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire (Poly cab/Finolex/Havells /MESCAB/KEI) in 20mm size PVC rigid conduit 'FR' (Make-Polycab/Precision), with 1x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire for ECC, to light/fan/call bell points with Piano Key type switch fixed on MS CRC sheet metal (16 SWG) switch board cum JB on wall complete with 2 no. suitable size “Ph & N” copper bar incl. bakelite/Perspex (wall matching color) top cover 3 mm thick and incl. 175mmx100mmx65mm inspection box, making earthing attachment, painting the MS box and mending good the damages to original finish a) Average run 9 mtr |
| 2 | Distribution wiring in 1.1 KV grade 22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) in 20mm size PVC rigid conduit 'FR' (Precision make), with 1.1 KV grade 1 x 22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire as ECC, to 5A 3 pin flush type plug socket & Piano Key type switch fixed on MS CRC sheet metal (16 SWG) switch board cum JB on wall incl. bakelite/Perspex (wall matching color) top cover 3 mm thick and incl. painting the MS box and mending good the damages to original finish. a) On Board |
| 3 | Distribution wiring in 1.1 KV single core stranded 'FR' PVC insulated & unsheathed copper wire (Poly cab/Finolex/ Havells/ MESCAB/KEI) in 20mm size PVC rigid conduit 'FR' (Precision make) incl. necy. fittings as required |
| 4 | a) 2 x 36/0.3 (2.5 sqmm) + 1 x 22/0.3 (1.5 sqmm) ECC |
| 5 | b) 2 x 56/0.3 (4 sqmm) + 1 x 36/0.3 (2.5 sqmm) ECC |
| 6 | Supplying and delivery of LED Industrial Batten light made of CRCA Sheet Body (Thickness ≥ 0.50 mm) and construction as per relevant IS, along with LED lamp (Opal finish polycarbonate housing with Aluminium end-cap) voltage AC 140-270 Volt, freq 50/60 hz, Operating temp range 0oC to 40o C, internal surge protection of 2.5 KV(internal) with Short & Open circuit protection , THD < 10% , P. F.≥0.9, IP20, CRI >80, and minimum 40000 Burning Hours (Life projection shall be calculated as per TM-21 methodology), CCT 5700°K /6500°K, and Fixture shall be of relevant BIS standard and trade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing, with Minimum 5 year OEM warranty. All test report except L80 should be from 3rd party NABL accredited Lab as per BIS shall be submitted. (System lumen efficacy ≥115 lm/Watt) a) Single fittings along with S/F of 1 no. 18-20 W LED lamp as per specification [Approved by CE(Planning),PWD] |
| 7 | b) Twin fittings along with S/F of 2 no. 18-20 W LED lamps as per specification [Approved by CE(Planning),PW |
| 8 | Fixing only single /twin fluorescent light fitting complete with all accessories directly on wall/ceiling/ HW round block and suitable size of MS fastener. |
| 9 | Supply & fixing 240V, 12 wt,CDL,B22, LED Lamp on the existing place as per direction of EIC. ( Make- Havells/Philips/ Cromton) |
| 10 | Supply & Delivery of 230 V, 50 Hz, single phase, 85 watts, 18\\" (450mm), speed 1325 rpm (minimum), Bracket Fan and class of insulation: B, 4 nos. metal (Aluminium alloy) blades, copper winding, steel/Al body with metal back cover. Power Factor not less than 0.9 and minimum air delivery 110 cu.m/min (minimum), including capacitor with safety pin,nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for compliant to IS 374:2019 and external connections with 1.5 sq.mm FR, PVC insulated copper conductor single core cable and earthing etc. as required. [Approved by CE(Planning),PWD] |
| 11 | Fixing only cabin fan on wall/ceiling by S&F rag bolts, nuts & washers (6 mm dia x 62 mm long) or as reqd. incl. S&F 24/0.20 PVC insulated flexible copper wire 0.5 mt. length [C-4/19] |
| 12 | Supply & delivery of 230 V, 50 Hz, single phase, 52 watts, 48\\" (1200 mm) Sweep, speed 320 rpm (minimum), A.C. Ceiling Fan and class of insulation: B, 3 nos. metal (Aluminium alloy) blades, 30 cm long down rod (14 SWG & higher thickness), 2 nos. canopies, safety rope, copper winding, steel/Al body. Power Factor not less than 0.9 and minimum air delivery 210 cu.m/min (minimum), without Regulator including capacitor with safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for compliant to IS 374:2019 and external connections with 1.5 sq.mm FR, PVC insulated copper conductor single core cable and earthing etc. as required. [Approved by CE(Planning),PWD] |
| 13 | Supply & fixing Electronic Socket type fan regulator on existing sheet metal switch board with backelight/ perpex top cover by serew after making housing for regulator knob by cuttingbackelight/ perpex top cover including making necessary connections. [Make: Anchor] |
| 14 | Fixing only ceiling fan complete with blades, canopy, fork, rubber bush etc. incl. S&F connecting wire for down rod upto 30 cm incl. painting the rod with approved paint and making necessary connection as required by 2x1.5 sqmm flexible copper wire. |
| 15 | Supply & delivery of 230 V, 50 Hz, single phase, 48 watts, 12\\" (300 mm) Sweep, speed 900 rpm (minimum), A.C. Exhaust Fan and class of insulation: B, 4 nos. metal (Aluminium alloy) blades, copper winding, steel/Al body. Power Factor not less than 0.9 and minimum air delivery 1145 cmh (minimum) capacitor with safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for compliant to IS 374:2019 and external connections with 1.5 sq.mm FR, PVC insulated copper conductor single core cable and earthing etc. as required. [Approved by CE(Planning),PWD] |
| 16 | Fixing only exhaust fan after making hole in wall and making good damages and smooth cement finish etc. as practicable as possible and providing necy. length of PVC insulated wire and making connection for exhaust of following diameter: a) 30 cm (12\\") |
| 17 | Supply & Fixing GI sheet (20SWG) metal Cowl with MS flat iron frame & GI wire mesh on wall with necy. bolts & nuts (6 mm dia x 62 mm long) a)30 cm Exhaust fan (12\\") |
| 18 | Supply & Fixing 240 V, 25 A, 3 pin Modular type plug socket (Make-Schneider/Legrand- Myrius/Arteor), without plug top and switch with 2 Module GI /PVC Modular type switch board with top cover plate flushed in wall and making necy. connections with PVC Cu wire and earth continuity wire etc. |
| 19 | Supply & Fixing 240 V,25 A, 3 pin Modular type plug topwith indicator (Make-Schneider/Legrand-Murius/Arteor) & necy. Connections. |
| 20 | Supply & Fixing 240 V, 25A Modular starter (Make-Schneider/ Legrand-Murius/Arteor) on 2 module GI Modular type switch board with top cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc. |
| 21 | Supply & Fixing 240 V, 4 nos. 6A, plug socket with separate 4 nos. 6 A Piano key type switch, indicator & 16A kit-kat flush type fuse (Brand approved by EIC) on sheet metal switch board embedded in wall incl. S & F 240x200x65mm MS (16SWG) switch board and bakelite/perspex top cover of 3mm thick by Brass screws after making housing for switch by cutting bakelite/perspex cover and making necessaryconnections as required. |
| 22 | Supply, Installation, Testing, and Commissioning of air-cooled Hi-Wall split type air conditioners of following capacities comprising Indoor and Outdoor Unitswith factory-charged Rotary/Scroll compressors (R-32/R-410A) including surface/concealed copper refrigerant piping insulated with closed-cell elastomeric nitrile rubber insulation and wrapping tape (up to 3 m), FRLS type copper power cable (up to 3.5 m) with suitable plug top, 3 meters of drain pipe, and wireless remote control with suitable battery. The system shall operate on 230V, 50Hz (±tolerance as per applicable standard), single-phase AC supply,providing cooling, dehumidification, and air circulation functions conforming to IS-1391 (Part-II ) with all amendments, and shall be capable of efficientperformance at outdoor ambient temperatures up to 50°C, with a minimum 5- year OEM warranty on both the compressor and PCB. The system shall beinstalled with S&F appropriate fixing arrangements as per OEM recommendations, including wall openings, mending well the damages and making necessary connections including T&P & labour etc as required complete in all respect as per the direction of EIC. [O-General/Daikin /Hitachi/MitsubishiElectric/Mitsubishi Heavy duty industries as per approved by EIC/authority). Cooling Capacity- 6.1 kW (Minimum) , Air Flow Rate:800 CFM (Minimum) Minimum ISEER - 5.0, BEE level - 4-Star(min) |
| 23 | Supply & installation of extra add-on items-HVAC grade 5/8\\" ( For suction) & 1/4\\" ( for Discharge) copper refrigerant pipe with 9mm thick the nitril rubber, insulation including shaddle, screw, insulation tape,Fastner etc for above AC machine as per direction of EIC. |
| 24 | Supply & laying Soft Drawn PVC Drain Pipe 19mm dia with proper supports & brackets as per direction EIC. |
| 25 | Supply & Laying 1.1KV,grade,3 core 4sqmm flexible copper cable with screw, saddle, drill macchine, nut bolt etc all necessary items needed for connection. (From starter to AC out door connection) (Make-Havells/KEI/polycab/Fenolex as per approved by EIC) |
| 26 | Add 18% GST (on Item No. 01.00 to 23.00) |
| 27 | Add 1% CESS (on Item No. 01.00 to 23.00) |
| 28 | N.B. : 1) Sl. No. 24.00 is variable depending on the total cost of the actual work on which 18 % GST to be calculated during measurement of the work (item No. 1.00 to 23.00) 2) Sl. No. 25 is variable depending on the total cost of the actual work on which 1 % CESS to be calculated during measurement of the work (item No. 1.00 to 24.00) Please Enable Macros to View BoQ information |