| 1 | Dismantling cross-arms of M.S. channel or angle sections etc. complete and setting aside for re-use with in 50m, complete all as specified and as directed. |
| 2 | Dismantling of ACSR or AAC conductor from pole of any size and capacity, complete all as specified and as directed. |
| 3 | Dismantling insulators any type, any size, complete all as specified and as directed. |
| 4 | Supply and fixing LED Street light fitting 70 W 230 V AC Outdoor type with high pressure die cast aluminium hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in ultiple optics complete with IP 65/66 protection, complete all as specified and as directed. |
| 5 | Supply and fixing GI pipe, bracket for street light fittings made out of 40 mm dia GI Pipe medium grade 1.20 m long bent to required angle/shape with and including necessary clamps, nuts, bolts & washers of suitable size and two coats of aluminium paint with a base coat of red oxide primer, complete all as specified and as directed. |
| 6 | Supply and fix PVC insulated unsheathed copper cable of size 1.5 Sqmm 3 core FR PVC for service connections from junction box to light fitting, complete all as specified and as directed. |
| 7 | Supply and fix loop in loop out fuse junction box of size 205 x255x112 mm made out of thermo plastic Polycarbonate with IP 66/67 weather proof for outdoor installation (with knockouts of cable entry) protection with terminals and locking screw fitted with 5 Amps fuse cutout-01 No with 6A MCB, suitable for cable size 10 sqmm and fixing on steel tubular pole at a height not less than 1.5m above ground level with the help of clamps two nos of F1 20 x 3 mm and suitable nuts and bolts, complete all as specified and as directed. |
| 8 | M & L for cement concrete for foundation fillings and mass conctere type D2 1:4:8 using 40 mm graded aggregate, complete all as specified and as directed. |
| 9 | M & L for cement concrete for copying of poles using B1 1:2:4, 20 mm graded aggregate, smooth finishing without using extra cement, complete all as specified and as directed. |
| 10 | M & L for cement concrete for foundation fillings and mass conctere type C2 1:3:6 using 40 mm graded aggregate, complete all as specified and as directed. |
| 11 | M&L Steel tubular pole type 410 SP-31 9 mtr long swaged type complete with CI base plate and finial taper plug, plug, bolts, nuts and screws as specified swaged, complete all as specified and as directed. |
| 12 | Excavation in trenches in soft/loose soil not exceeding 1.5 mtr in width and not exceeding 1.5 mtr in depth for laying of cables up to proper level , complete all as specified and as directed. |
| 13 | Returning, filling in including spreading, leveling, watering and well ramming in layers not exc 25 cm in hard/dense soil, complete all as specified and as directed. |
| 14 | Removing surplus exacavated material from excavation not exc 50 meter and depositing where directed at a level not exc 1.5 meter above the starting point, complete all as specified and as directed. |
| 15 | Supply and filling dry river sand in trenches including spreading for cushioning of LT UG cable and punning down, complete all as specified and as directed. |
| 16 | M&L for well burnt as class ‘B’ bricks as mechanical protection to under ground cables laying with length of the bricks equal to the width of the trench, complete all as specified and as directed. |
| 17 | Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 95 Sq mm 3.5 core. (OH to Main Panel), complete all as specified and as directed. |
| 18 | Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 50 Sq mm 3.5 core.(Panel to Panel), complete all as specified and as directed. |
| 19 | Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 10 Sq mm 2 core. (For Bldg), complete all as specified and as directed. |
| 20 | Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 16 Sq mm 4 core. (For Security Lt Pole), complete all as specified and as directed. |
| 21 | M/L for Earthing complete with galvanized steel earth plate electrode 60 x60 cm x 6 mm thick buried directly in ground (earth pit not less than 2.25 m deep below ground level) with top edge of the plate not less than 1.5 meter below normal ground level connected to GI earth lead wire 4 mm dia by means of bolts nuts, check nut and washers of GI and GI tubing 15 mm bore, medium grade for earth lead protection up to main earth test point and including concrete pit in PCC (1:3:6) type C 1 pre cast RCC (1:2:4) type B1 cover slab 450 x 450 x 50 mm reinforced with 8 mm dia TMT bars 100 C to C including one handle for lifting made out of 8 mm dia MS bar, wire mash, 20 mm bore GI tubing medium grade for watering ,charcoal and salt in alternate layers including excavation earth work complete all as specified and directed Electrical plate no 3 of SSR Part-I, complete all as specified and as directed. |
| 22 | M & L Earthing complete with galvanized earth plate electrode 600 x 600 x 6 mm burried directly in ground vertically to a depth of not less than 2.2M & L Earthing complete with galvanized earth plate electrode 600 x 600 x 6 mm buried directly in ground vertically to a depth of not less than 2.25 mtr below ground level connected to 32 x 6mm earth strip with nut, bolts and washers made out of galvanized iron mild steel and 40 mm dia GI pipe \\"light grade\\" for protection of earth lead and connected to control board or main switch or as directed by Engineer -in-Charge including earthing pit in PCC (1:3:6) type C1 for chamber & Pre-cast RCC cover of size 380 x 380 x 40 mm with one handle made out of 8 mm dia round bar, 20 mm dia GI pipe light grade for watering funnels , wire mesh and provided charcoal or coke of alternative layers of 15 cm including necessary earth work as Exc, R&F & removal etc, complete all as specified and as directed. |
| 23 | MS tubes, light grade, galvanised, 25 mm bore, laid in trenches or under floor or road or fixed with pole for protection of electric cable. (For security lt Pole), complete all as specified and as directed. |
| 24 | MS tubes, light grade, galvanised, 80 mm bore, laid in trenches or under floor or road or fixed with pole for protection of electric cable, complete all as specified and as directed. |
| 25 | Supply, install, testing and commissioning of LT feeder piller box outdoor type made out of 3.15 mm thick CRCA sheet and MS angle iron frame with weather proof canopy, mounted on PCC pedestal, cubical type, front and rear side openable, compartment type with hinged door ligting lugs 2 Nos, earthing strips at rear side, bottom detachable gland plate complete with suitable size zinc and passivated nut, bolts spring and washers and locking arrangement for each compartment, provision of air vent, dust and vermin proof, provision of cable alley with 400 amps rated aluminium bus bar having 1100 volts grade sleaving and internal connection should be provided with aluminium strips of suitable size and to accommodate and including the following MCCBS duly painted with 2 coats powder coating over a coat of anticorrosive red oxide primer should accomodate the following accessories. (Main Panel) |
| 26 | Incomer:200 Amp, 4 pole MCCB, 36 KA 415V,Digital Volt meter 0-500V with inbuilt selector switch - 01 No Digital Amp meter 0-500A with inbuilt selector switch & CT Coils- 01 NoSet of LED type indicating lamps - 03 No Aluminium Bus Bar 300 Amp TPN Outgoing160 Amp, MCCB 4 ,Pole 36 KA 415 V - 01 No 100 Amp, MCCB 4 ,Pole 36 KA 415 V - 02 No 63 Amp , MCCB 4 ,Pole 16 KA 415 V,- 03 No |
| 27 | Supply, install, testing and commissioning of LT feeder piller box outdoor type made out of 3.15 mm thick CRCA sheet and MS angle iron frame with weather proof canopy, mounted on PCC pedestal, cubical type, front and rear side openable, compartment type with hinged door ligting lugs 2 Nos, earthing strips at rear side, bottom detachable gland plate complete with suitable size zinc and passivated nut, bolts spring and washers and locking arrangement for each compartment, provision of air vent, dust and vermin proof, provision of cable alley with 400 amps rated aluminium bus bar having 1100 volts grade sleaving and internal connection should be provided with aluminium strips of suitable size and to accommodate and including the following MCCBS duly painted with 2 coats powder coating over a coat of anticorrosive red oxide primer should accomodate the following accessories. (Feeder PIllar No 01) |
| 28 | Incomer:160 Amp, 4 pole MCCB, 36 KA 415V - 01 No,Digital Volt meter 0-500V with inbuilt selector switch - 01 No Digital Amp meter 0-500A with inbuilt selector switch & CT Coils- 01 NoSet of LED type indicating lamps - 03 No Aluminium Bus Bar 200 Amp TPN Outgoing100 Amp MCCB - 01 40 Amp MCB DP - 20 Nos |
| 29 | Supply, install, testing and commissioning of LT feeder piller box outdoor type made out of 3.15 mm thick CRCA sheet and MS angle iron frame with weather proof canopy, mounted on PCC pedestal, cubical type, front and rear side openable, compartment type with hinged door ligting lugs 2 Nos, earthing strips at rear side, bottom detachable gland plate complete with suitable size zinc and passivated nut, bolts spring and washers and locking arrangement for each compartment, provision of air vent, dust and vermin proof, provision of cable alley with 400 amps rated aluminium bus bar having 1100 volts grade sleaving and internal connection should be provided with aluminium strips of suitable size and to accommodate and including the following MCCBS duly painted with 2 coats powder coating over a coat of anticorrosive red oxide primer should accomodate the following accessories. (Feeder Pillar No 02) |
| 30 | Incomer:63 Amp, 4 pole MCCB, 36 KA 415V - 01 No,Digital Volt meter 0-500V with inbuilt selector switch - 01 No Digital Amp meter 0-500A with inbuilt selector switch & CT Coils- 01 NoSet of LED type indicating lamps - 03 No Aluminium Bus Bar 200 Amp TPN OutgoingMCB DP 40 AMP Outgoing -20 NOs |
| 31 | Supply, install, testing and commissioning of LT feeder piller box outdoor type made out of 3.15 mm thick CRCA sheet and MS angle iron frame with weather proof canopy, mounted on PCC pedestal, cubical type, front and rear side openable, compartment type with hinged door ligting lugs 2 Nos, earthing strips at rear side, bottom detachable gland plate complete with suitable size zinc and passivated nut, bolts spring and washers and locking arrangement for each compartment, provision of air vent, dust and vermin proof, provision of cable alley with 400 amps rated aluminium bus bar having 1100 volts grade sleaving and internal connection should be provided with aluminium strips of suitable size and to accommodate and including the following MCCBS duly painted with 2 coats powder coating over a coat of anticorrosive red oxide primer should accomodate the following accessories. (Feeder Pillar No 03) |
| 32 | Incomer:100 Amp, 4 pole MCCB, 36 KA 415V - 01 No,Digital Volt meter 0-500V with inbuilt selector switch - 01 No Digital Amp meter 0-500A with inbuilt selector switch & CT Coils- 01 NoSet of LED type indicating lamps - 03 No Aluminium Bus Bar 250 Amp TPN Outgoing63 Amp, MCCB 4 Pole 16KA 415 V - 01 NoMCB SPN 40 AMP Outgoing -20 NOs |
| 33 | Supply, install, testing and commissioning of LT feeder piller box outdoor type made out of 3.15 mm thick CRCA sheet and MS angle iron frame with weather proof canopy, mounted on PCC pedestal, cubical type, front and rear side openable, compartment type with hinged door ligting lugs 2 Nos, earthing strips at rear side, bottom detachable gland plate complete with suitable size zinc and passivated nut, bolts spring and washers and locking arrangement for each compartment, provision of air vent, dust and vermin proof, provision of cable alley with 400 amps rated aluminium bus bar having 1100 volts grade sleaving and internal connection should be provided with aluminium strips of suitable size and to accommodate and including the following MCCBS duly painted with 2 coats powder coating over a coat of anticorrosive red oxide primer should accomodate the following accessories. (Feeder Pillar No 04) |
| 34 | Incomer:63 Amp, 4 pole MCCB, 16 KA 415V - 01 No,Digital Volt meter 0-500V with inbuilt selector switch - 01 No Digital Amp meter 0-500A with inbuilt selector switch & CT Coils- 01 NoSet of LED type indicating lamps - 03 No Aluminium Bus Bar 100 Amp TPN Outgoing63 Amp, MCCB 4 Pole 16KA 415 V - 01 NoMCB SPN 40 AMP Outgoing -20 NOs |
| 35 | Supply, install, testing and commissioning of LT feeder piller box outdoor type made out of 3.15 mm thick CRCA sheet and MS angle iron frame with weather proof canopy, mounted on PCC pedestal, cubical type, front and rear side openable, compartment type with hinged door ligting lugs 2 Nos, earthing strips at rear side, bottom detachable gland plate complete with suitable size zinc and passivated nut, bolts spring and washers and locking arrangement for each compartment, provision of air vent, dust and vermin proof, provision of cable alley with 400 amps rated aluminium bus bar having 1100 volts grade sleaving and internal connection should be provided with aluminium strips of suitable size and to accommodate and including the following MCCBS duly painted with 2 coats powder coating over a coat of anticorrosive red oxide primer should accomodate the following accessories. (Feeder Pillar No 05) |
| 36 | Incomer:63 Amp, 4 pole MCCB, 16 KA 415V - 01 No,Digital Volt meter 0-500V with inbuilt selector switch - 01 No Digital Amp meter 0-500A with inbuilt selector switch & CT Coils- 01 NoSet of LED type indicating lamps - 03 No Aluminium Bus Bar 100 Amp TPN Outgoing63 Amp, MCCB 4 Pole 16KA 415 V - 01 NoMCB SPN 40 AMP Outgoing -20 NOs |
| 37 | Supply, install, testing and commissioning of LT feeder piller box outdoor type made out of 3.15 mm thick CRCA sheet and MS angle iron frame with weather proof canopy, mounted on PCC pedestal, cubical type, front and rear side openable, compartment type with hinged door ligting lugs 2 Nos, earthing strips at rear side, bottom detachable gland plate complete with suitable size zinc and passivated nut, bolts spring and washers and locking arrangement for each compartment, provision of air vent, dust and vermin proof, provision of cable alley with 400 amps rated aluminium bus bar having 1100 volts grade sleaving and internal connection should be provided with aluminium strips of suitable size and to accommodate and including the following MCCBS duly painted with 2 coats powder coating over a coat of anticorrosive red oxide primer should accomodate the following accessories. (Feeder Pillar No 06) |
| 38 | Incomer:63 Amp, 4 pole MCCB, 16 KA 415V - 01 No,Digital Volt meter 0-500V with inbuilt selector switch - 01 No Digital Amp meter 0-500A with inbuilt selector switch & CT Coils- 01 NoSet of LED type indicating lamps - 03 No Aluminium Bus Bar 100 Amp TPN Outgoing63 Amp, MCCB 4 Pole 16KA 415 V - 01 NoMCB SPN 40 AMP Outgoing -20 NOs |
| 39 | Supply, install, testing and commissioning of LT feeder piller box outdoor type made out of 3.15 mm thick CRCA sheet and MS angle iron frame with weather proof canopy, mounted on PCC pedestal, cubical type, front and rear side openable, compartment type with hinged door ligting lugs 2 Nos, earthing strips at rear side, bottom detachable gland plate complete with suitable size zinc and passivated nut, bolts spring and washers and locking arrangement for each compartment, provision of air vent, dust and vermin proof, provision of cable alley with 400 amps rated aluminium bus bar having 1100 volts grade sleaving and internal connection should be provided with aluminium strips of suitable size and to accommodate and including the following MCCBS duly painted with 2 coats powder coating over a coat of anticorrosive red oxide primer should accomodate the following accessories. (Feeder Pillar No 07) |
| 40 | Incomer:63 Amp, 4 pole MCCB, 16 KA 415V - 01 No,Digital Volt meter 0-500V with inbuilt selector switch - 01 No Digital Amp meter 0-500A with inbuilt selector switch & CT Coils- 01 NoSet of LED type indicating lamps - 03 No Aluminium Bus Bar 100 Amp TPN Outgoing63 Amp, MCCB 4 Pole 16KA 415 V - 01 NoMCB SPN 40 AMP Outgoing -20 NOs |
| 41 | Note:- Schedule of credit Rs 7886.00 will be deducted from total amount quoted while accepting the bid. Details of schedule of credit is given in tender documents. Please Enable Macros to View BoQ information |