| 1 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 2x1.5 sq.mm FRLS PVC insulated copper conductor single core cable of Polycab /Finolex /RR Kabels /Anchor /Salzer/ Apar/ Grandlay / eq. make to be approved by EIC in surface / recessed medium class PVC conduit (including cost of p/l of 25 mm dia PVC Conduits with allied accessories including cutting of walls /floors with hydraulic cutters and refacing to original position by way of cement plastering /pop / paiting etc complete job including cost of conduits and allied accessories like bends . fan deeps/Fan hooks with fastners etc ) , with 6Amps modular switch, modular plate of Schneider /ABB /L&T /Legrand /Simens/ eq. make to be approved by EIC , suitable GI box etc. as required. ( P+N) for Normal and invertor points per room is to be provided seperately).The Job further includes providing and fixing of heavy duty Metallic conceled deeps and Fan junction deeps of standard make dully isi marked (to be approved by EIC before installation) actual numbers to be provided as per site requirement and as per instructions of EIC complete job |
| 2 | Point wiring for 10 Amp Socket out lets with 3x2.5 sq mm (P+N+E) FRLs PVC insulated 660/1100 volt grade flexible stranded (50 strands of 0.25 mm dia.) copper conductor wires of Polycab/Finolex/Anchor/RR Cabels /Salzer/ Apar/ Grandlay/ eq. make to be approved by EIC, to be laid in recessed or surface conducting system (25 mm dia medium class PVC Conduits including cutting of walls /floors with hydraulic cutters and refacing to original position by way of cement plastering /pop / paiting etc complete job including cost of conduits and its allied accessories ,seperate conduit for each point ).The Job further Includes supply and fixing modular grid plate mounted flush mounted 2 no 240 volts 6-16 Amp 5 pin socket out let along with 2 No's of 6-16 Amp control Switch to be housed in 6-Way heavy duty GI Modular Box with modular cover plate of ABB /L&T / legrend /Simens/ eq. make to be approved by EIC , complete as per specification and as required . The Job includes providing and laying of circuit wiring of same size from DB to first switch in sub circuit Complete as required Complete Job including conduits ,Switches ,Sockets and complete circuit from DB Box to point (Two points may |
| 3 | Point wiring for 16 Amp Socket out lets with 3x4 sq mm (P+N+E) FRLS PVC insulated 660/1100 volt grade flexible stranded copper conductor wires of Polycab/Finolex/Anchor/RR Cabels /Salzer/ Apar/ Grandlay/ eq. make to be approved by EIC, to be laid in recessed or surface conducting system (25 mm dia medium class PVC Conduits including cutting of walls /floors with hydraulic cutters and refacing to original position by way of cement plastering /pop / paiting etc complete job including cost of conduits and its allied accessories ,seperate conduit for each point ) .The job further includes the cost of supplying and fixing modular grid plate mounted flush mounted 240 volts 16 amp 6 pin combined shuttered socket out let along with 240 volt 16 Amp control Switch of ABB /L&T / legrend /Simens/ eq. make to be approved by EIC to be housed in heavy duty 4-Modular GI Box of same make as of switches /sockets with p/f of modular cover plate , complete as per specification and as required with inter connection complete as per specifications and as required. The Job includes providing and laying of circuit wiring of same size from DB to first switch in sub circuit Complete as required Complete Job including conduits ,Switches ,Sockets and complete circuit from DB Box to point with out any looping and jointing |
| 4 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surfacel recessed medium class PVC conduit as required. Both the Sub main may be laid through a single pipe of 25 mm dia including its cost of pipe and allied accessories |
| 5 | 2 X 2.5 sq. mm earth wire |
| 6 | 2 X4 sq. mm + 1 X4 sq. mm earth wire |
| 7 | Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 8 | Supply and fixing of Indicators (Modular type) fitted on modular grid plate and GI Boxes complete job |
| 9 | Supply, Installation, Testing and Commissioning of 1200 mm sweep ceiling fans with down rod suitable for 230 V, 50 Hz, single phase ACSupply, earthing etc. complete as required.of Usha / Crompton Greaves / Orient /Helonix/ eq. make to be approved by EIC |
| 10 | Supply and fixing of Angle /Batten holders of GM /Eq make to be fitted on pvc round plate .The job includes p/f of 9 Watts LED Lamps of Philips /Crompton /Havels /Bajaj / eq. make to be approved by EIC ,including connections etc |
| 11 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required.(But without MCB/RCCB/Isolator).of Legrend /L&T /ABB /Simens /Schinder make dully isi marked complete with connections.of legrend /L&T /ABB /Havells/ eq. make to be approved by EIC |
| 12 | 12 way, Double door |
| 13 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioninq etc. as required of legrand / ABB /Schneider /L&T /Simens / eq. make to be approved by EIC |
| 14 | Supplying and fixing of 32-40 Amps rating DP 240/415 volts (10KA) of Legrend /L&T /ABB /Simens /Schinder make dully isi marked complete with connections.of Legrand / ABB /Schneider /L&T /Simens / eq. make to be approved by EIC |
| 15 | Supplying and fixing of 63 Amps rating DP 240/415 volts (10KA) of Legrend /L&T /ABB /Simens /Schinder / eq. make to be approved by EIC dully isi marked complete with connections |
| 16 | Supply,Laying,Testing & Commissioning of 16 sq.mm 2 - core Aluminium flat cable of Havells/ Grandlays / APAR / Polycab /Finolex /Anchor / eq. make to be approved by EIC , including cost thimbles on input aswell as output sides dully crimped with hydraulic crimping tool incl making of necessary connections |
| 17 | Providing of earthing with 19 mm dia GI rod having 4 ft long to be embedded in a pit with extending of earthing from pipe to panel by way of p/l of 8 No. SWG GI Wire from electrode to db Box laid through PVC Conduit Please Enable Macros to View BoQ information |