| 1 | ELECTRICAL WORKS |
| 2 | 1.10.1Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mmFRLS PVCinsulated copper conductor single core cable in surface / recessed medium class PVCconduit,with modular switch, modular plate, suitable GI box and earthing the point with 1.5sq.mm. FRLSPVC insulated copper conductor single core cable etc as required.Group A |
| 3 | 1.10.2Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mmFRLS PVCinsulated copper conductor single core cable in surface / recessed medium class PVCconduit,with modular switch, modular plate, suitable GI box and earthing the point with 1.5sq.mm. FRLSPVC insulated copper conductor single core cable etc as required.Group B |
| 4 | 1.10.3 Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mmFRLS PVCinsulated copper conductor single core cable in surface / recessed medium class PVCconduit,with modular switch, modular plate, suitable GI box and earthing the point with 1.5sq.mm. FRLSPVC insulated copper conductor single core cable etc as required.Group C |
| 5 | 1.11Wiring for twin control light point with 1.5 sq.mm FRLS PVC insulated copperconductor single core cable in surface / recessed medium class PVC conduit, 2 waymodular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm.FRLS PVC insulated copper conductor single core cable etc as required. |
| 6 | 1.17.3Supplying and drawing following sizes of FRLS PVC insulated copper conductor,single core cable in the existing surface / recessed steel/ PVC conduit as required.3 X1.5 sq.mm |
| 7 | 1.17.12Supplying and drawing following sizes of FRLS PVC insulated copper conductor,single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x2.5 sq. mm |
| 8 | 1.17.21Supplying and drawing following sizes of FRLS PVC insulated copper conductor,single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 4sq. mm |
| 9 | 1.17.30Supplying and drawing following sizes of FRLS PVC insulated copper conductor,single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 6sq. mm |
| 10 | 1.21.1Supplying and fixing of following sizes of medium class PVC conduit along withaccessories in surface/ recess including cutting the wall and making good the same incase of recessed conduit as required.20 mm |
| 11 | 1.21.2Supplying and fixing of following sizes of medium class PVC conduit along withaccessories in surface/ recess including cutting the wall and making good the same incase of recessed conduit as required.25 mm |
| 12 | 1.24.1Supplying and fixing following modular switch/ socket on the existing modular plate& switch box including connections but excluding modular plate etc. asrequired.5/6 amps switch |
| 13 | 1.24.4Supplying and fixing following modular switch/ socket on the existing modular plate& switch box including connections but excluding modular plate etc. asrequired.3 pin 5/6 amp socket outlet |
| 14 | 1.24.7Supplying and fixing following modular switch/ socket on the existing modular plate& switch box including connections but excluding modular plate etc. asrequired.TV antenna socket outlet |
| 15 | 1.25Supplying and fixing two module stepped type electronic fan regulator on the existingmodular plate switch box including connections but excluding modular plate etc. asrequired |
| 16 | 1.26Supplying and fixing modular blanking plate on the existing modular plate &switch box excluding modular plate as required. |
| 17 | 1.27.1Supplying and fixing following size/ modules, GI box alongwith modular base &cover plate for modular switches in recess etc as required.1 or 2 Module(75mmX75mm) |
| 18 | 1.27.2Supplying and fixing following size/ modules, GI box alongwith modular base &cover plate for modular switches in recess etc as required.3 Module (100mmX75mm) |
| 19 | 1.31Supplying and fixing suitable size GI box with modular plate and cover in front onsurface or in recess, including providing and fixing 3 pin 5/6 amps modular socketoutlet and 5/6 amps modular switch, connection etc. as required. (For light plugs to beused in non residential buildings). |
| 20 | 1.32Supplying and fixing suitable size GI box with modular plate and cover in front onsurface or in recess, including providing and fixing 6 pin 5/6 & 15/16 ampsmodular socket outlet and 15/16 amps modular switch, connection etc. as required. |
| 21 | 1.33Supplying and fixing 3 pin, 5 amp ceiling rose on the existing junction box/ woodenblock including connection etc as required. |
| 22 | 1.34Supplying and fixing brass batten/ angle holder including connection etc. as required. |
| 23 | 1.35Installation, testing and commissioning of wall bracket / ceiling fittings of all sizesand shapes containing up to two GLS/CFL/LED lamps per fitting, complete with allaccessories including connection etc. as required. |
| 24 | 1.38Supplying and fixing call bell/ buzzer suitable for single phase, 230 volts, complete asrequired. |
| 25 | 1.50.1Installation of exhaust fan in the existing opening, including making good the damageconnection testing, commissioning etc. as required.Upto 450 mm sweep |
| 26 | 1.53.1Supplying and drawn of UTP 4 pair CAT 6 LAN cable in the existing surface/recessedsteel/PVC conduit as required1 run of Cable |
| 27 | 1.55.1Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bellpoint ( without independent switch etc.) with 1.5 sq. mm FRLS PVC insulated copperconductor single core cable in surface/ recessed PVC conduit, and earthing the pointwith 1.5 sq. mm FRLS PVC insulated copper conductor single core cable etc. asrequired.Group A |
| 28 | 1.56Supplying and fixing suitable size Gl box with modular plate and cover in front onsurface or in recess, including providng and fixing 2 Nos. 3 pin 5/6 A modular socketoutlets and 2 Nos. 5/6 A modular switches, connection etc. as required. (For lightplugs to be used in non residential buildings |
| 29 | 2.2.14Providing and fixing following rating and breaking capacity MCCB withthermomagnetic release and terminal spreaders in existing cubicle panel boardincluding drilling holes in cubicle panel. making connections. etc. as required.125 Amp, 36 KA |
| 30 | 2.3.4Supplying and fixing following way, single pole and neutral, sheet steel, MCBdistribution board, 240 volts, on surface/ recess, complete with tinned copperbus bar, neutral bus bar, earth bar, din bar, interconnections, powder paintedincluding earthing etc. as required. (But without MCB/RCCB/Isolator)16 way, Double door |
| 31 | 2.4.2Supplying and fixing following way, horizontal type three pole and neutral, sheet steel,MCB distribution board, 415 volts, on surface / recess, complete with tinned copperbus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted includingearthing etc. as required. (But without MCB/RCCB/Isolator)6 Way (4+18), Doubledoor |
| 32 | 2.4.3Supplying and fixing following way, horizontal type three pole and neutral, sheet steel,MCB distribution board, 415 volts, on surface / recess, complete with tinned copperbus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted includingearthing etc. as required. (But without MCB/RCCB/Isolator)8 way(4+24), Doubledoor |
| 33 | 2.5.1Supplying and fixing of following ways surface/ recess mounting, vertical type, 415volts, TPN MCB distribution board of sheet steel, dust protected, duly powder painted,inclusive of 200 amps tinned copper bus bar, common neutral link, earth bar, din barfor mounting MCB's (butwithout MCB's and incomer ) as required .(Note : Vertical type MCB TPDB isnormally used where 3 phase outlets are required.)4 WAY(4+12), DOUBLE DOOR |
| 34 | 90.11.1.18Supply and installation of sheet steel, phosphatised and painted, dust and verminproof enclosure of MCB DB including copper /brass bus bar, neutral link, earth busand DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchorbolts or fixed in recess including cutting hole on the wall , making good the damages,colour washing etc. as required4 way (8+12) - double cover TPN vertical DB withprovision for fixing MCCB as incomer and SP/ TP MCB as outgoing (IP 42/43) |
| 35 | 2.10.1Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, \\"\\"C\\"\\" curve, miniaturecircuit breaker suitable for inductive load of following poles in the existing MCBDB complete with connections, testing and commissioning etc. as required.Single pole |
| 36 | 2.12.1Supplying and fixing following rating, double pole, 240 volts, isolator in the existingMCB DB complete with connections, testing and commissioning etc. as required.40amps |
| 37 | 2.13.1Supplying and fixing following rating, four pole, 415 volts, isolator in the existingMCB DB complete with connections, testing and commissioning etc. as required.40amps |
| 38 | 2.13.2Supplying and fixing following rating, four pole, 415 volts, isolator in the existingMCB DB complete with connections, testing and commissioning etc. as required.63amps |
| 39 | 2.13.3Supplying and fixing following rating, four pole, 415 volts, isolator in the existingMCB DB complete with connections, testing and commissioning etc. as required.100amps |
| 40 | 2.14.2Supplying and fixing following rating, double pole, (single phase and neutral),240volts, residual current circuit breaker (RCCB), having a sensitivity current 30 milliamperes in the existing MCB DB complete with connections, testing andcommissioning etc. as required.40 amps |
| 41 | 2.15.2Supplying and fixing following rating, four pole, (three phase and neutral), 415volts, residual current circuit breaker (RCCB), having a sensitivity current 30milli Amperes in the existing MCB DB complete with connections, testing andcommissioning etc. as required.40 amps |
| 42 | 2.15.3Supplying and fixing following rating, four pole, (three phase and neutral), 415volts, residual current circuit breaker (RCCB), having a sensitivity current 30milli Amperes in the existing MCB DB complete with connections, testing andcommissioning etc. as required.63 amps |
| 43 | OD40829/2026-2027Supply and Fixing 100 A 'C' curve TP MCB : Supplying and fixing 100 Arating Triple pole , 415 V, 10 kA, “C” curve, miniature circuit breakersuitable for inductive load of following poles in the existing MCCB DB/ MCB DBcomplete with connections, testing and commissioning etc. as required |
| 44 | OD40830/2026-2027Supply and Fixing 40A to 63 A 'C' curve TP MCB : Supplying and fixing40A to 63 A rating Triple pole , 415 V, 10 kA, “C” curve, miniaturecircuit breaker suitable for inductive load of following poles in the existing MCCBDB/ MCB DB complete with connections, testing and commissioning etc. as required. |
| 45 | 5.6Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick includingaccessories, and providing masonry enclosure with cover plate having lockingarrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt asrequired |
| 46 | 5.17Providing and fixing 4.00 mm dia copper wire on surface or in recess for loop earthingas required. |
| 47 | 90.16.1.2Supply and drawing bare earthing conductors of the following sizes along with wiring/cables and giving connection as required2.65 mm copper conductor (12 SWG) |
| 48 | 5.14Providing and fixing 25 mm X 5 mm copper strip on surface or in recess forconnections etc. as required |
| 49 | 9.1.2Supplying and making end termination with brass compression gland and aluminiumlugs forfollowing size of PVC insulated and PVC sheathed / XLPE aluminium conductorcable of 1.1 KVgrade as required.2 X 10 sq. mm (19mm) |
| 50 | 9.1.20Supplying and making end termination with brass compression gland and aluminiumlugs forfollowing size of PVC insulated and PVC sheathed / XLPE aluminium conductorcable of 1.1 KVgrade as required.3 1/2X25 sq.mm (28mm) |
| 51 | 9.1.22Supplying and making end termination with brass compression gland and aluminiumlugs forfollowing size of PVC insulated and PVC sheathed / XLPE aluminium conductorcable of 1.1 KVgrade as required.3 1/2 X 50 sq. mm (35mm) |
| 52 | 9.1.32Supplying and making end termination with brass compression gland and aluminiumlugs forfollowing size of PVC insulated and PVC sheathed / XLPE aluminium conductorcable of 1.1 KVgrade as required.4 X 10 sq. mm (25mm |
| 53 | 9.1.33Supplying and making end termination with brass compression gland and aluminiumlugs forfollowing size of PVC insulated and PVC sheathed / XLPE aluminium conductorcable of 1.1 KVgrade as required.4 X 16 sq. mm (28mm) |
| 54 | 90.4.1Supply and installation of suitable size MS rod type fan clamp in the RCC slab as perIS 732 as required. |
| 55 | 90.4.5.4 Supply, Installation, testing and commissioning of ceiling fan of following sizesincluding wiring the down rods of standard length (up to 30 cm) with 1.5 sq. mmFRLS PVC insulated, copper conductor, single core cable etc. as required.1200mm sweep - ceiling fan complete with service value minimum 4.0(cubmeter/minute/Watt), Air delivery minimum 210(cubic meter/minute), Copper windingsuitable for 230V/240V single phase AC supply |
| 56 | 90.10.3.15Supply and Fixing the following modular switches & accessories in the existingfront plates and giving necessary connections as required (RoHS compliant )32A DPswitch with indicator |
| 57 | 90.12.7.3Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armouredaluminium power cable, 1.1 KV grade of the following sizes using clamps noted alongwith the cables, spacing of clamps not exceeding 60cms, making good the damages ,colour washing etc. as required.2 core 10 sq mm with factory made clamp |
| 58 | 90.12.7.27Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armouredaluminium power cable, 1.1 KV grade of the following sizes using clamps noted alongwith the cables, spacing of clamps not exceeding 60cms, making good the damages ,colour washing etc. as required.3.5 core 25 sq mm with factory made clamp |
| 59 | 90.12.7.29Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armouredaluminium power cable, 1.1 KV grade of the following sizes using clamps noted alongwith the cables, spacing of clamps not exceeding 60cms, making good the damages ,colour washing etc. as required.3.5 core 50 sq mm with factory made clamp |
| 60 | 90.12.7.40Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armouredaluminium power cable, 1.1 KV grade of the following sizes using clamps noted alongwith the cables, spacing of clamps not exceeding 60cms, making good the damages ,colour washing etc. as required.4 core 10 sq mm with factory made clamp |
| 61 | 90.12.7.41Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armouredaluminium power cable, 1.1 KV grade of the following sizes using clamps noted alongwith the cables, spacing of clamps not exceeding 60cms, making good the damages ,colour washing etc. as required.4 core 16 sq mm with factory made clamp |
| 62 | OD37166/2026-2027S/F CAT 6 RJ 45 Modular Computer Jack : Supply and fixing of modular type CAT6RJ 45 Computer Jack on modular GI box & cover plate and giving connectionsetc.as required. |
| 63 | OD37167/2026-2027Supply, marking and crimping of RJ45 connectors /sockets with boot to the CAT 6Cable as required |
| 64 | OD37168/2026-2027Supply and fixing UTP Cat 6 Patch chord of 1 M length of Govt. approved brand asrequired |
| 65 | OD37169/2026-2027Supply and fixing UTP Cat 6 Patch chord of 2 M length of Govt. approved brand asrequired. |
| 66 | OD37264/2026-2027Supply and fixing of 16 Port (10/100/1000 MBPS) Unmanaged Network Giga switch,giving connections etc. complete as required. |
| 67 | OD37263/2026-2027S/F of Patch Panel : Supply and fixing of 16 Port CAT6 RJ 45 UTP Unshielded Wallmount/Rack mount Patch Panel of Govt. approved brand as required. |
| 68 | OD37172/2026-2027Supply and providing 4U cabinet of approved make powder coated with glass panelfront door including giving connection etc complete as required |
| 69 | OD37266/2026-2027Supply and fixing of 400mm Wall Fan : Supply and fixing of 400 mm sweep wall fanwith three positions and pulling cords and giving connection etc. as required |
| 70 | OD37267/2026-2027Supply of 225mm Exhaust Fan : Supply of 225 mm sweep light duty exhaust fansuitable for operation on 220/ 240V, 50 Hz, single phase AC supply etc. as required |
| 71 | OD37173/2026-2027Supply of 20W LED batten/ tube light fittings : Supply of 20W Surface mounting typeLED lenier batten/ tube light fittings with output of 2000 lumen, made out of CRCAbody with white acrylic cover etc. as required |
| 72 | OD37176/2026-2027S/F of 12 W LED Bulb : Supply and fixing of 12 W LED Bulb in the existing bulbholder as required |
| 73 | OD40701/2026-2027Supply of 12 W surface LED down lighter : Supply of square/round shaped 12 W lowglare, surface mounting type, integral LED down light fittings with white powdercoated Die cast aluminium body with anodised aluminium reflector etc.as required |
| 74 | OD37179/2026-2027Supply of 10 W LED bulkhead luminaire : Supply of 10 W, low glare LED bulkheadluminaire with Die cast aluminium Frame, anodized aluminium reflector etc.asrequired. |
| 75 | OD37180/2026-2027SITC of 100 W LED street light fittings : Supply, installation, testing andcommissioning of 100 watts LED street light fittings made up of pressure die casthousing with prismatic polycarbonate diffuser and individual LEDs with secondaryoptics and IP65 protection with complete accessories etc. to the existing GI pipe as perthe direction of engineer in charge as required |
| 76 | OD37397/2026-2027Supply and Laying of 3 core 4 sq.mm flat Submersible cable : Supplying and layingPVC Insulated and sheathed 3 core 4 sq.mm flat submersible cable with annealed plainelectrolytic copper conductor as per IS 8130/1934 insulated and sheathed withelectrical grade PVC compound as per IS 5831/1984 generally conforming to IS694/1990, including all minor civil works such as chipping of floor / chasing of wallsetc. making good the damages and giving connections, as required. |
| 77 | OD37398/2026-2027SITC of 2 HP submersible pumpset : Supplying, erection, testing and commissioningof 2 HP submersible pumpset suitable for operation on 240V, 50Hz single phase ACsupply with control panel and all accessories and giving connection etc. as required. |
| 78 | OD37396/2026-2027SITC of Three phase KSEB Meter board : Fabrication, supply, installation, testing& commissioning of cubicle type energy meter board made out of 2 mm thickMS sheet, Powder coated, including provision for fixing KSEB three phase energymeter/CT meter, providing & fixing of 3 nos 125 A cut out fuse, neutral link andone number 125A TP &N Switch Disconnector Fuse unit and provision forlocking the incoming & Metering section etc. all as per KSEB/Kerala StateElectrical Inspectorate standards as required. Please Enable Macros to View BoQ information |