| 1 | Supply, laying and testing of XLPE electric power cable insulated, screened, PVC bedded, galvanised steel strip or wire armoured , (heavy duty) 11000 volt grade with stranded aluminium conductor of size 185 sqmm, 3.0 core complete all as specified and directed. Note:- Earth work including excavation, returning filling, removing of soil, etc will be measured and paid for separately under respective items of schedule. |
| 2 | Supply and joint Cable end jointing kit for 11 KV (earthed) grade cable for outdoor type termination Cold shrinkable type joint complete with all jointing material and accessories suitable for 3 core XLPE HT armoured aluminium conductor cable of size 185 Sqmm complete all as specified and directed. |
| 3 | Supply and joint Cable end jointing kit for 11 KV (earthed) grade cable for Indoor type termination Cold shrinkable type joint complete with all jointing material and accessories suitable for 3 core XLPE HT armoured aluminium conductor cable of size 185 Sqmm complete all as specified and directed. (For inside VCB) |
| 4 | Labour only for dismantling existing steel channels, nuts, bolts, washers on 11 Mtrs long HT pole and kept on store for schedule of credit complete all as specified and directed. |
| 5 | Labour only for dismantling existing ACSR conductor run on existing HT Pole 11 Mtr long complete all as specified and directed. |
| 6 | Labour only for dismantling existing HT Disc, Pin insulators any type complete all as specified and directed. |
| 7 | Dismantling existing PCC HT pole from under ground after demolition of PCC and making surface good complete all as specified and directed. |
| 8 | Labour and T & P for Erecting only dismantled HT pole retreived from Srl Item No 6 here-in-above as per site directed by Engr-in-Charge. Note: (i) Earth work i.e Excavation, Returning, Refilling, Removal, PCC measured and paid separately (ii) The pole required for HT cable with joints in every 500 mtrs due to water logging area breakers not catered. |
| 9 | Excavation in trenches n. exc. 1.5 mtr wide and n. exc. 1.5 mtr in depth for foundation of pole and laying of UG cable and getting out in any type of soil complete all as specified and directed. |
| 10 | All as per Srl item No 9 here-in-above but for soft/disintegrated rock complete all as specified and directed. |
| 11 | All as per srl item No. 9 here-in-above but depth exceeding 1.5 Mtr and not exceeding 3 mtr complete all as specified and directed. |
| 12 | Returning filling in, including spreading, watering and well ramming in layers not exceeding 25 cm thick in any type soil complete all as spd and directed. |
| 13 | Removing excavated material (soil) to a distance not exceeding 50 mtr and depositing where directed at a level not exceeding 1.5 mtr above the starting point complete all as spd and directed. |
| 14 | Material and labour for sand cushioning to under ground cables 8 cm thick before laying the cable and 15 cm thick after laying, stretching and testing the cable all as directed. (Note :Only punned thickness i.e 18cm shall be measered and paid). |
| 15 | Supply and laying HT cable cover un-reinforced precast of size 300mm x 180mm x 40mm class HVP, type 1 laying perpendicular to HT cable all as specified and directed. |
| 16 | M & L for PCC 1:4:8 Type D-2 (using 40mm grade crushed stone aggregates) as in foundation and mass concrete for foundation concrete of poles complete all as specified and directed. |
| 17 | M&L for PCC 1:3:6 type C-1 (using 20 mm graded crushed stone aggregate) as in mass concrete in foundations for stay/copings etc complete all as specified and directed. |
| 18 | M&L for road cutting for laying cable through GI Pipe of suitable size and after laying making the road surface good with PCC 1:4:8 type D-2 (using 40 mm graded crushed stone aggregate) and re-filling the gap remove the extra soil where directed complete all as directed by Engr -in- charge.(Note: GI pipe shall be measured separately) |
| 19 | Supply and fixing for lightning arresters expulsion type complete with all fittings transmission class, discharge capacity 65 kilo amps suitable for 11000 volts conforming to IS complete all as specified and directed. |
| 20 | Supply and fixing air break switch gang operated (GOD) triple pole with drop out fuses mechanically operated, mounted on insulators (15 insulators) polymer type & steel frame with operating mechanism & operating rod of GI pipe 25mm medium grade with necessary clamps to be operated from ground level 11 KV grade working pressures and current upto 400 amps etc complete all as specified and directed. |
| 21 | M & L earthing complete with galvanised steel earth plate electrode, 600x600x6mm thick burried directly in the ground (earth pit not less than 2.25 mtr deep below ground level) with top edge of the plate not less than 1.5mtr below ground level connected to galvanised iron wire 4mm dia as earth lead by means of bolts, nuts and washers of GI up to test point, GI tubing 15mm bore medium grade protection pipe, GI watering pipe 20mm bore light grade with funnel and wire mesh , charcoal , and salt precast PCC 1:2:4 (Nominal mix) cover with suitable steel handle, and angle iron 40x40x3mm frame for pit cover, PCC 1:2:4 pit including earth work in any type of soil, removal of surplus soil to a distance n.exc 50mtr and connecting, testing on completion all as shown on electric plate No 03 of SSR -2009 Part II complete all as directed. |
| 22 | Supply and fixing aluminum conductor steel reinforced (ACSR) for HT lines on PCC/steel tubular poles, streching without kinks and bends including aluminum binding wires of size weasel as per load complete all as spd and directed. |
| 23 | Material and labour for erection of Steel tubular swaged poles complete with cast iron base plate, finial taper plug, bolts, nuts & screws as specified type 410 SP-64 (12.0 metres long) complete all as spd and directed.(Note: Earth work shall be measured and paid separately) |
| 24 | M&L for Cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers welding, bending cold or hot drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of paint complete all as spd and directed. |
| 25 | M&L for anti-climbing device; spikes type fabricated out of M.S. bars (round, square and flat) including nuts, bolts, washers and welding in two halves made to shape to suit the cross section of the pole complete all as spd and directed. |
| 26 | M&L for danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with M.S. clamps, bolts and nuts of approved size, for HT, 25x20cm size complete all as spd and directed. |
| 27 | M&L for cradles, hexagonal/rectangular, fabricated with galvanised steel wire 3.15 or 4mm dia complete all as spd and directed. Please Enable Macros to View BoQ information |
| 28 | M&L for cradles, hexagonal/rectangular, fabricated with galvanised steel wire 3.15 or 4mm dia complete all as spd and directed. Please Enable Macros to View BoQ information |