| 1 | SITC of star rated Aluminium wound distribution Transformer of following rating 11/0.433KV Delta-Star Connected, Vector Group Dyn 11,ONAN Cooled & as per BEE star - 1 & BIS approved as per IS 2026- 1977 & losses as defined as per 2014 (Fourth Revision) Level-1 . including standard accessories like conservator, silica gel breather, radiator, fins, HT cable box & LT cable boxes, temperature rise in winding/oil 35-40 degree C upto 200 KVA & 40-45 degree C for above 200 KVA, ISI marked drain valve, Dial type Temperature gauge, first filling of transformer oil as per IS :335-1953, Epoxy based paint, including carrying of pre-commission Testing & Charging of Transformer complete in all respect . The Transformer shall be subjected to routine factory tests (as per IS:2026 and IS:1180) including testing from CTL of discom before charging of transformer & complete installaion must be certified from Electrical Inspectorate office as per Indian Electricity rule, (CTL testing charges and Electrical Inspection charges shall be reimbursed by the department to the contractor). All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached200 KVA |
| 2 | Providing & Laying P.V.C. / XLPE insulated & P.V.C. sheathed Arrmoured Aluminium cable confirming to IS:1554 P-I / IS :7098 P - I of 1.1 KV with H4-Grade electrolytic aluminium conductor confirming to IS 8130 of purity >99.6 %, round / flat strip armouring of cables, Inner / outer sheath confirming to IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray(with cable tie) including testing etc. as required of following size. OEM must have it's own in house NABL accrediated Laboratory for testing procedure as per IS:10810.For additional technical parameters of product / work refer Annexure 'A'attached with this BSR |
| 3 | 150.0 Sq. mm ; 3.5 core |
| 4 | Providing & Laying XLPE insulated three core Armoured Aluminium cable for working voltage 11 K.V.(E) confirming IS :7098 P - 2 with H4- Grade electrolytic aluminium conductor confirming to IS: 8130 class-2 of purity >99.6 %, Insulation Screening: Extruded Semiconducting Compound followed by helically wrapped Copper Tape, round / flat strip armouring of cables , Inner / outer sheath PVC type ST-2 confirming to IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray including testing etc. as required of following size. OEM must have it's own in house NABL accrediated Laboratory for testing procedure as per IS:10810 All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attachedwith this BSR .3 core 95.0 Sq.mm |
| 5 | SITC of 11kV 630 Amps 21KA for 3 Sec. SF6 insulated, outdoor duty (IP54) , Extensible / Non extensible type Ring main unit (RMU) manually operated in combination of VCB modules and Load Break switch consisting of Copper busbar in SF6 insulated 304 (Non-Ferrite Non-Magnetic Grade) stainless steel enclosure of thickness 2.5mm with manometer. The HV switchgear and control gear should be confirming to IEC-62271-100, IEC-62271-200-2003 & IEC-60694-1996. The RMUshould be internal arc tested for 21KA for 1Second with IAC-AFL classification for gas tank. Vacum Interrupter of VCB should be RMU Manufacturer’s own make. Each feeder of RMU should have voltage presence indicator. . and compring of followings:- 1 no. microprocessor based Self powered numerical relay with over Current/ earth fault & short circuit protection with each VCB feeder. - 3 Nos. Protection CT shall be of Burden 2.5VA, ratio 50/1A, Class of Accuracy class 5P10 for O/C and E/F protection for each VCB.- 1 No. Manometer for each tank,- 1 nos. Fault Passage indicator,-Right angle boots for all the feeder Modules All the type test certificates as per IEC from Third party NABL / CPRI / ERDA accrediated lab to be submitted. (Cost of RCC Foundation / Steel Structure to be paid Extra) All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSRNon Extensible 3 way RMU with 1 no. VCB & 2 No. Load Break Switch |
| 6 | Supply & Installation of D.P. Structure With AIR BREAK SWITCH having following specifications A, B, C, D, E. All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . A) Double pole structure on 2 no ISMB ( I beam ) of size 150 x 75 mm, 10 mtr length using 7 no MS channel each of size 100 mm x 50 mm x 2500 mm complete in all respect with nuts, springs washers, clamps as required. B) Off load type gang operated 3-pole vertical flute type switch suitable for 11KV ; 400A ,3-ø, central post rotating double break isolator complete with MS hardware , copper moving & fixed contact ,assembly of 9 nos pin insulator ,GI pipe of suitable length for operation. C) 3nos Vertical / Horizontal mounted 11kv horn gap fuse set/drop out 11kv barrel fuses mounted on 6no pin insulators D) 3 piece non linear resistor type. lighting arrestor of approved make suitable for 3 wire, 11kv Overhead line with rated voltage of 9kv rms & nominal discharge current rating of 5 ka & complete with galvanized clamping arrangement GI bolts, nuts, washer etc as required. E) 3 no 11kv ACSR conductors mounted on pin type insularors as required. 6.GENERAL:The go shall be operated by hand operated liver properly earthed with provision for locking mounted at 3’ |
| 7 | Supply and fixing of 100 Amp, 11kV Horn gap fuse set IS 9385 on existing DP structure with 6 nos 24kV/22kV post insulator (IS:5350 part III), hot dipped hard ware,fuse wire of required size etc. complete in all respect as per Discom specification etc. as required.All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attachedwith this BSR . |
| 8 | Supplying and making one end termination with Nickel plated heavy duty brass single compression gland (as per IS 12943-1990)) SIBG type consisting of Check Nut, Gland Body, Metal Washer(3 Nos.), Outer Seal Rubber Ring, Compression Nut, heavy duty aluminium lugs (as per IS 8309 -1993) duly crimped with crimping tool, PVC tape as per IS 8337-1976 of following size of PVC insulated & PVC sheathed/ XLPE aluminium conductor cable of 1100 volt grade as required.All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR .3.5 x 95.0 sq.mm |
| 9 | 3.5 x 150.0 sq.mm |
| 10 | Plate Earthing as per IS:3043 with copper Earth plate of purity >95% of size 600mm x 600mm x 3.0mm by embodying 3 mtr. below the ground level with 20 mm dia.G.I. 'B' class watering Pipe ,including all accessories like nut, bolts, reducer, nipple, wire meshed funnel, and Heavy duty weather proof poly-propylene earth pit chamber with lockable Jam free lid suitable for safe working load 5000 Kg or more of size Top Dia. 225 to 260 mm, Bottom Dia 300 to 350 mm. and Height 250 to 300mm. and embodying the pipe complete with alternate layers salt and coke/ charcoal, testing of earth resistance for value of 5 ohms or less as required & must record by engineer in-charge during site visit and ensure to enter in measurment book. All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 11 | S & Making Heat shrinkable type Tubular sleeve version outdoor straight through joint for following size of PVC/ XLPE insulated aluminium conductor cable of 1.1 KV grade as required. All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR.3/3.5/4 x 70.0 sq.mm-150 sq.mm |
| 12 | Add Extra for Laying of one number XLPE power cable of 11/33 KV (Earthed) voltage grade direct in ground including excavation of trench of size 120 cm (Depth) x 35 cm(Width) , with procedure as per following points:- (a) Make a river sand bed of height 125 mm along the trench, (b) Lay the cable in the middle of the trench, (c) Provide river sand bed of height 125 mm on top of the cable. (d) Lay the protective Common burnt clay F.P.S. Bricks of Class designation 75 / Sand stone slabs of 50 mm thickness and 225 mm wide just above the sand bed vertically across the cable ( Approx. 9 no. Bricks per Mtr.), (e) Backfill the excavated soil leaving 300 mm from the Ground level, (f)Lay the Cable warning tape and again back-fill the remaining portion of the trench upto the ground level and compacting the earth |
| 13 | Add Extra in Item no. 62.3 if Excavation done in Hard Rock / CC road / TAR Roadand making Good the same |
| 14 | Supply and fixing of 11kV, 400 Amp 3 pole, central pot rotating double break type isolator (IS:9921 part I toV) without earth blade operating mechanism with GI spring loaded reverse loop type fixed contact, solid hard drawn electolytic copper tubular moving contact with silver/ nickel plated at end points, 9 nos post insulator of 12 kV (IS:2554 & IS 5350 part III), hot dipped galvanising hard ware, nut, bolts etc complete in all respect as per Discom specification etc. as required. All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 15 | SITC of 3 /4 pole current limiting Moulded case circuit breaker (MCCB) made of flame retardent & heat resistant material having following current rating, short circuit breaking capacity at 440/415 V, 50 Hz; O/L & S/C settings , conforming to IS/IEC 60947 P -2 :2003 with front face and centralised adjustable, trip free mechanisum, true contact position indicator, line load interchangeability, designed for both horizontal & vertical mounting without any adverse effect on electrical performance, suitable for operation upto 55 degree and without derating upto 40 degree, pollution degree 3, having positive isolation capability, push (test) to trip, trip time less then 10 ms under s/c condition, Breaking capacity Ics = 100% ICU. U imp =8 KV, rated insulation voltage 690 V. provision for UVR , shunt trip , earth fault trip, door interlock, pad lock & rotary handle , including making connections etc. as required.OEM shall have submit NABL / CPRI / ERDA accrediated lab type test certificate before execution All as per pre approved by Engineer in-charge. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR. 4 pole MCCB With Thermal Magnetic release 250 Amp , 35 kA,adjustable O/L & adjustable S/C setting, Please Enable Macros to View BoQ information |