| 1 | Wiring for light / fan / exhaust fan / call bell point with 2 x1.5 sq. mm pvc insulated Copper conductor cable (FR) in pvc casing and capping complete with 6/10 amps modular type switch, cover plate, surface modular switch board including connection etc as required:- |
| 2 | Long Point :- |
| 3 | Medium Point :- |
| 4 | Providing and fixing of 3 pin 6/10 amps plug point with modular type 6/10 amps switch and socket including connection with 2x1.5 sq. mm PVC insulated Copper conductor cable (FR) on surface modular switch board, earthing the 3rd pin etc. as required:- |
| 5 | Providing and fixing of 3/6 pin 16/20 amps plug point with modular type 16/20 amps switch and socket including connection with 2x2.5 sq. mm PVC insulated Copper conductor cable(FR) on surface modular switch board, earthing the 3rd pin etc. as required:- |
| 6 | Wiring for circuit /Sub-main with following sizes PVC insulated copper conductor cable (FR) in PVC casing and capping etc. as required. |
| 7 | 2 X 1.5 sq mm |
| 8 | Wiring for Circuit/Sub-main with the following sizes of PVC insulated Copper conductor cable (FR) in existing PVC casing capping/ conduit in recess/surface including connection etc. as required:- |
| 9 | 1 X 1.5 sq mm |
| 10 | Supplying & installation of 400 mm sweep AC wall mounting fan with metal blade including connection etc as required:- |
| 11 | Supplying & installation of 380 mm sweep 900 rpm metalic body exhaust fan including connection etc as required (ISI marked) :- |
| 12 | Supplying & installation of shutter for 380/450 mm sweep metalic body exhaust fan in the existing hole as required:- |
| 13 | Making different sizes of hole in the wall for fixing of exhaust fan including finishing the same with cement plastering and painting etc as required: |
| 14 | Supply, Installation, testing and commissioning of Microprocessor based 2 loop panel, expandable up-to 4 Loop, with optional redundant network module, each loop shall have the capability of connecting 253 detectors & devices. The fire alarm control panel shall have built in degrade mode function. The panel should have inbuilt TCP/IP communication for Panel Program and Remote monitoring option through LAN or WAN communication. The panel shall be able to give location of all fire and more Fire /fault and Isolation conditions of addressable units via the address codes. The panel shall have the capacity of storing up to 3000 events. Further, the panel must be able to automatically switch ON /OFF respective control module whenever any alarm is triggered. The panel shall have a 320 x 240 dots monochrome LCD display with resolution and analogue output having User-defined fault message, up to 40 characters for fault description. The Panel protection category of IP30. The panel shall have a built-in power supply and battery charger along with maintenance free 28AH, 2 x 12-volt SMF Lead acid batteries capable of running for a minimum of 24 hours with battery charger complete as required. The panel shall be complied with EN54 standard ,Vds approved [MAKE : SIEMENS(CERBERUS-EN)/ HONEYWELL(ESSER)/PANASONIC /AUTRONICA] |
| 15 | Supply, Installation, testing and commissioning of Multicriteriadetector having inbuilt isolator in the detector or in base with forward, backward scattering technology having dual Smoke & heat sensors and integral indicator with 360 degree viewing angle. Detector shall communicate 4 danger levels for differentiated alarm activation and high tolerance to dust, dirt, temperature fluctuations and air currents. Detector should have unique address for communication and assigned through panel with Mounting Base as required with the protection category of IP41 and duly Approved EN54 standard ,Vds approved [MAKE : SIEMENS(CERBERUS-EN)/ HONEYWELL(ESSER)/ PANASONIC/AUTRONICA] |
| 16 | Supply, Installation, testing, and commissioning of Intelligent Analog Supply of Intelligent Analog Addressable Heat Detector(Static + ROR) having inbuilt isolator in detector or in base and integral indicator with 360 degree viewing angle. Detector shall communicate 4 danger levels for differentiated alarm activation. Detector should have unique address for communication and assigned through panel with mounting base as required with the protection category of IP51 and duly approved by EN54 standard ,Vds approved [MAKE : SIEMENS(CERBERUS-EN)/ HONEYWELL(ESSER)/ PANASONIC/AUTRONICA] |
| 17 | Supply, Installation, testing and commissioning of addressable Base for all types of detectors, fast connector terminals for easy installation of any cable type One External Indicator (LED) can be connected to the base, Cable entry from top or side. Duly approved with to EN54 standard ,Vds approved [MAKE : SIEMENS(CERBERUS-EN)/ HONEYWELL(ESSER)/ PANASONIC/AUTRONICA] Note: Detectors with In-Built Isolator may offer Standard Base |
| 18 | Supply, Installation, testing, and commissioning of Intelligent addressable manual call point with inbuilt turbo Isolator suitable for flush or surface mounting, call point shall include test key feature without removing the glass. Also, should have protection category of IP42, duly approved with EN54 standard ,Vds approved [MAKE : SIEMENS(CERBERUS-EN)/ HONEYWELL(ESSER)/ PANASONIC/AUTRONICA] |
| 19 | Supply, Installation, testing and commissioning of Intelligent addressable loop powered sounder with inbuilt Isolator, able to provide an sound level of 95 decibels at 2.4mtr height, shall have 7 rogrammable tones, 3 volume settings selectable from the panel and shall have the ability to switch between one tone for alert and one tone for evacuation. Shall have protection category of IP21 duly approved with EN54 standard ,Vds approved [MAKE : SIEMENS(CERBERUS-EN)/ HONEYWELL(ESSER)/PANASONIC/ AUTRONICA] |
| 20 | Supply and laying of 2 core1.5 Sqmm Armoured FRLS cable in PVC casing capping etc as required.[MAKE: Polycab / Finolex] Please Enable Macros to View BoQ information |