| Sl. No. | Item Description |
| 1 | PART A |
| 2 | DESCRIPTION |
| 3 | EQUIPMENT |
| 4 | WATER COOLED SCREW CHILLING MACHINES WITH VFD |
| 5 | Supply, Installation, Testing and Commissioning of Water cooled screw type water chilling machine with VFD each having a capacity as given hereunder at chilled water inlet/outlet temperature of 12.22°C/6.7°C, Fouling Factor 0.0005 FPS and condenser water inlet/outlet temperature of 32.2°C/36.4°C Fouling Factor 0.001 FPS, suitable for operation on factory charged refrigerant R-134a for screw type machine each comprising of the following complete as per specifications and as required complete in all respect to the entire satisfaction of EIC. |
| 6 | Screw type compressor semi hermetic complete with automatic capacity control safety switches, forced feed lubrication system |
| 7 | The semi hermetic compressor should be mono/ twin type. Capacity control range of compressor shall be from min.25% to 100% |
| 8 | Suitable capacity squirrel cage induction motor with class 'B'/'H' insulation suitable for operation on 415 +- 10% volts,50Hz, A.C. supply. |
| 9 | 1 No. suitable capacity Variable frequency drive for the above compressor motor complete with ammeter with CTs, over load protection, under voltage protection, protection against phase reversal & independent single phase preventers etc complete as required. with Active Harmonic Filters to achieve THDI & THDI not to exceed 5% at source |
| 10 | Necessary drive arrangement. |
| 11 | 1 Set - Lubrication device consisting of automatic electric oil pump, oil cooler, head tank, oil strainer, and automatic pressure regulating valve, oil heater, oil heater thermal switch etc. as per specifications. |
| 12 | 1 No. - Matching shell and tube water cooled condenser of M.S. shell and integrally finned copper tubes with Max. Pressure Drop of 6 mtrs with odd/even pass |
| 13 | 1 No. - matching shell & tube flooded type chiller of MS shell and copper tubes with Max. Pressure Drop of 3 mtrs with odd/even pass |
| 14 | 1 Lot - Refrigerant piping fittings, valves and accessories to inter connect compressor, condenser, chiller and expansion valve. |
| 15 | 1 Set - Microprocessor based control panel complete with accessories as per specifications. |
| 16 | Lot - Refrigerant line accessories comprising of safety valves, angle valve, liquid line indications, liquid level control etc. |
| 17 | Lot - Water flow switches at outlet of condenser & chiller, water drain, air purge valves, thermometers and pressure gauges wherever required. |
| 18 | Lot - Suction line and chiller factory insulated with minimum 19mm thick polyvinyl nitrile rubber insulation complete as required. |
| 19 | Lot- Frame work for mounting the above condenser, chiller compressor and motor with base plate complete with anti-vibration pads/springs. |
| 20 | Lot- Initial/first charge of refrigerant gas & compressor oil. |
| 21 | Lot- RCC / Cement concrete foundation for the chilling unit. |
| 22 | Lot-Anti Vibration pads in foundation for chiller machine to avoid vibrations to the building |
| 23 | Lot - Coupling Connections for both condenser and chiller to avoid vibrations |
| 24 | Screw type chilling machine described above, as per specifications and complete in all respects for the operating parameters as given under. |
| 25 | The evaporator and condender shall have ASME Stamping |
| 26 | Chiller & Compressor should be of same make and machine shall be AHRI Certified. |
| 27 | Minimum COP should be 5.8 The NPLV of VFD chiller should not be more than 0.39 KW/TR. The IKW/TR should not be more than 0.66 |
| 28 | Maximum IKW/ TR at operating conditions 0.66 KW/TR. |
| 29 | The price includes, loading/unloading and shipment till site Including Insurance Charges ,Unloading at site,RCC Foundation, placement of Chilling machine on the foundation, co-ordination during execution, rendering necessary guidance for execution, supervision, testing, commissioning and startup of above mentioned chiller. Radiographic Non Destructive Test for long seam welding of both evaporator and condenser shells shall be done and the test report of the same shall be verified during factory testing of chillers. |
| 30 | Chiller 220 TR (Actual Capacity) (2W+1S) |
| 31 | (Make: As per approved make list attached) |
| 32 | The Charges for above 220 TR x 1 no chiller got witness tested at AHRI certified test bed in OEM factory for 4 load points (100%, 75%, 50% & 25%)at the cost of the agency/ firm along with the Model & Serial No. of the Machine as per direction of EIC .The machine shall be accompanied with the 4 point test report duly certified by the OEM. No payment shall be released without the same . |
| 33 | Note : Vendor Shall Supply all chiller of same make at site, different brands are not allowed |
| 34 | Hot Water Generator |
| 35 | Supplying, installation, testing and commissioning of electrical HW generator equipped with sufficient number of electrical immersion heaters. The Hot Water Generator shall be of following capacity made of 8mm MS sheet and dish end made of 10mm MS having 16 gauge stainless steel lining with heaters arranged in banks and controlled by electronic Controller and Thermostats so that hot water is generated at 70 degree C with nominal variation including 75mm thick resin bonded fibre glass insulation of 24 kg/Cum density finished with 1.25mm thick aluminum sheet cladding including necessary electrical panel having suitable incoming and outgoing switchgears for heaters, automatic controls such as manual reset high temperature water outlet, step controller and recycling relay, 'ON' 'OFF' switch thermostats, pilot light, low water cutoff and other controls as per manufacturers recommendations including inlet and outlet connections for water as per specifications complete with pressure release valve, low level cut-out. Autovent sight-glass, foundation for Hot water generator as per specifications complete as required. All basic controls and terminals shall be located in an integral control cabinet factory wired and tested. The generator shall be suitable for 415 (+)/(-) 10% volts, 50 cycle, 3 phase power supply. The entire generator shall be factory assembled and tested at 350 PSI pressure. |
| 36 | The price includes loading/ unloading and shipment till site Including Insurance Charges ,Unloading at site,RCC Foundation, placement of HWG on the foundation, co-ordination during execution, rendering necessary guidance for execution, supervision, testing, commissioning and startup of above mentioned HWG. |
| 37 | 300.0 KW Actual Capacity Hot water generator (with Multiple Bank (1 Working + 1 Standby) |
| 38 | (Make: As per approved make list attached) |
| 39 | Hot water generator (Monsoon Reheating) |
| 40 | Supply,installation, testing & Commissioning of electrically operated Hot Water Generator of 80 KW actual capacity made of 8mm M.S. sheet and dish end made of 10mm M.S. having 16 gauge stainless steel lining with heaters arranged in banks and Controller and Thermostat so that suitable GPM hot water is generated at 50°C with nominal variation, including 75mm thick resin bonded fibre glass insulation of 24 Kg / CUM density finished with 1.25mm thick aluminium sheet cladding including necessary Electrical panel with BMS compatible having suitable Incoming and outgoing Switchgears for Boiler, automatic Controls including inlet and outlet connections for water complete with pressure release valve, low level cut-out, Autovent sight-glass as per specification complete as required. (Degree of protection IP52 with IS 2147) |
| 41 | The price includes loading/unloading and shipment till site Including Insurance Charges ,Unloading at site,RCC Foundation, placement of HWG on the foundation, co-ordination during execution, rendering necessary guidance for execution, supervision, testing, commissioning and startup of above mentioned HWG. |
| 42 | Heating Capacity 100KW (With Multiple Bank) |
| 43 | (Make: As per approved make list attached) |
| 44 | PUMP SETS |
| 45 | PRIMARY VARIABLE SPEED PUMPING SYSTEM |
| 46 | Supply, installation, testing and commissioning of PN16 rated Vertical Inline Split Coupled single stage centrifugal pump each capable of delivering the specified flow rate comprising the following and complete as per specifications. Casing (Volute) - Ductile Iron.Impeller - 316 SS - Statically and Dynamically BalancedCasing Gasket - Confined Non Asbestos FiberPump Shaft - 316 SS .Flush Line - Braided Stainless SteelMechanical Seal - Outside Balanced (the pump design shall meet the requirement of servicing / changing the mechanical seal without disturbing the pump shaft alignment) with external flushline. Motor Type - TEFC Squirrel Cage, Efficiency Class - I FIVE, Insulation - Class F, 415V ± 10% , 50Hz ± 5%, 3Ø AC Power Supply, RPM as per OEM standard. |
| 47 | VFD - Integrated motor mounted over Pump with IP- 55 protection. pump should operate through sensorless control or wireless DPT control.Pump Efficiency should be more than 75% Integrated fliter to meet EN61800-3 for RFI Control, Integrated DC link Reactor equivalent in performance to a 5% AC line reactor.All the VFD should display the dynamic head & flow rate of the pump using inputs from ultrasonic flow meter and digital pressure gauge or using sensorless alogorithms,( Per pump,1 flow meter and 2 pressure gauges to be supplied and integrated with motor mounted VFD driven pump for the display of flow and head on VFD). Pump manufacturer to supply Ultrasonic flow meter and digital pressure gauges along with the pumps supplied or can display individual flow and head per pump on respective VFD using sensorless alogorithms |
| 48 | The Price includes all clearance charges, unloading and shipment till site Including Insurance Charges ,Unloading at site,RCC Foundation, placement of PUMPs on the foundation, co-ordination during execution, rendering necessary guidance for execution, supervision, testing, commissioning and startup of above mentioned pumps. |
| 49 | The system shall be complete in all respects and suitable for following ratings and duty. |
| 50 | 528 USGPM * 40 M Head or as per actual at site with Min Efficiency. 75% for Chilled water circuit (2Working + 1Standby) |
| 51 | (Make: As per approved make list attached) |
| 52 | Microprocessor Based Pump Logic Controller for Primary variable pump |
| 53 | SITC Separate (Not as apart of VFD) Microprocessor based Primary variable pump logic controller in IP 54 protection, to control following nos. Pumps. Suitable to operate on Sensorless/ wireless mode ( 3 wireless DP sensor to be consider for each zone) & Should be Modbus RTU/ BACnet enabled for communicating with BMS & RS-485 serial communication with Pump VFD. The staging of pumps should be based on efficiency (not on capacity) to ensure minimum operating cost. End of curve protection should be sensorless control based Power Rating: 230 V/ 1 ph/ 50 Hz Display: Minimum 4.3\\" backlit LCD Hand-Off-Automatic (H-O-A) control Secure front cabinet door with lock and key UL Listed and CSA Approved Remote or local start/stop mode of operation. 2-level (field and factory) password security Remote zone signals, zone faults, zone setpoint and active control zone Note : All above should be sourced from OEM as a single unit |
| 54 | For Chilled water pumpset (2W + 1S) |
| 55 | (Make: As per approved make list attached) |
| 56 | CONDENSOR WATER PUMPS (FIXED SPEED) |
| 57 | Supply, installation, testing and commissioning of PN16 rated Vertical Inline Split Coupled ( Long coupled Type ) single stage centrifugal pump each capable of delivering the specified flow rate comprising the following and complete as per specifications. Casing (Volute) - Cast Iron.Impeller - Gunmetal Bronze - Statically and Dynamically BalancedCasing Gasket - Confined Non Asbestos FiberPump Shaft - SS 316/416.Flush Line - Braided Stainless SteelMechanical Seal - Outside Balanced (the pump design shall meet the requirement of servicing / changing the mechanical seal without disturbing the pump shaft alignment) Motor Type - TEFC Squirrel Cage, Efficiency Class - IE3, Insulation - Class F, 415V ± 10% , 50Hz ± 5%, 3Ø AC Power Supply |
| 58 | The price includes loading/ unloading and shipment till site Including Insurance Charges ,Unloading at site,RCC Foundation, placement of PUMPs on the foundation, co-ordination during execution, rendering necessary guidance for execution, supervision, testing, commissioning and startup of above mentioned pumps. |
| 59 | 880 USGPM * 30 M Head or as per actual at site with Min Efficiency. 75% (2Working + 1Standby) |
| 60 | (Make: As per approved make list attached) |
| 61 | Hot Water Pump (Monsoon Reheating) |
| 62 | Supply,erection, testing and commissioning of monoblock Hot water centrifugal pump for hot water recirculation, pump set capable of delivering Min.130 GPM of water against 24 mtr head each comprising of the following and complete as required |
| 63 | 1 No. - monoblock type pump with bronze impellar and mechanical seal. |
| 64 | Duly insulated with 80 kg/cum density resin bonded fiber glass cladded with aluminium sheets of 0.5mm thickness and properly clamped to pump in two semicircular sections as per specifications. |
| 65 | 1 No. Suitable HP, TEFC squirrel cage induction motor(Eff-3) with class ' B' insulation, 3000 RPM (±10%) synchronous speed, operating on 415 Volts + 10 % , 3 phase , 50 Hz A.C. supply. |
| 66 | The price includes loading/ unloading and shipment till site Including Insurance Charges ,Unloading at site,RCC Foundation, placement of PUMPs on the foundation, co-ordination during execution, rendering necessary guidance for execution, supervision, testing, commissioning and startup of above mentioned Pumps. |
| 67 | Pump as above (1 working + 1stand by) |
| 68 | (Make: As per approved make list attached) |
| 69 | Cooling Tower (CTI Certified) |
| 70 | Supply, installation, testing and commissioning of CTI Approved standard Rectangular type FRP Induced Draught Counter flow cooling tower with Multi Cell. Motors shall be suitable for VFD's , IP65 and Premium efficiency of IE3 with neccessory accessories, FRP water basin, PVC fillings with integral louvers and drift eliminators, hot water distribution by gravity complete with statically and dynamically balanced axial flow Fans, Direct driven fans with TEFC induction motor and temperature sensor suitable for operation on 415 + 10% volts, 50 Hz. AC supply, suction screen, make up with float valve and quick fill arrangement, overflow and drain connections, suitable inspection ladder, access arrangement for cooling tower interior, MS supporting structure, anti-vibration mountings ,cement concrete foundation, steel/ mesonary supporting structure complete as per specifications as required. Design shall be as below ,IP 55 rated Locable Isolator Switch with cooling tower along with all Isolators for CT Complete in all respect. |
| 71 | WBT : at 85º F |
| 72 | WB Approach : 2.77º C Maximum |
| 73 | Hot water IN : 97.5 ºF |
| 74 | Hot water OUT : 90ºF |
| 75 | Water Flow Rate : 880 USGPM |
| 76 | The price includes loading/unloading and shipment till site Including Insurance Charges ,Unloading at site,RCC Foundation, placement of Cooling Tower on the foundation, co-ordination during execution, rendering necessary guidance for execution, supervision, testing, commissioning and startup of above mentioned Cooling Tower. |
| 77 | Heat Rejection Capacity : 3,432,000 BTU/hr (2W + 1S) |
| 78 | (Make: As per approved make list attached) |
| 79 | AIR HANDLING UNITS |
| 80 | Supply, installation testing and commissioning of Double skin air handlers, complete with thermal break profile ,the various sections, chilled water coils,centrifugal Forward/backward (Airofoil) curved blade fan and in Ceiling Mounted forward/Backward curved blade fan , direct driven/drive sets, squirel cage induction motor with minimum IE 3 efficiency, and vibration isolators and with Thermal Break profile as described in the specifications & AHU schedule. |
| 81 | Supply, installation testing and commissioning of AHUs as per the mentioned in AHU schedule. |
| 82 | AHU FOR OT's AND ICU ((All AHU Motors /controls Should be VFD and BMS Compitable ) |
| 83 | Supplying, installing, testing and commissioning of factory built weather Proof Floor Mounted /Ceiling suspended double skin type air handling units with thermal break profile made of 48+-2 mm thick panels consisting of pre plasticized G.I casing made of thickness 0.8 mm outside layer and Aluminium sheet of thickness 0.8mm inside layer with polyurethene foam (PUF) CFC Free insulation of density 40+-2 kg/m3 factory injected between them by injection moulding machine, complete with blower section with blower DIDW backward/Forward curved centrifugal fan of below mentioned static pressures for FM/CS AHU's, 6 row deep cooling & Heating coil,2 row deep Monsoon reheating coil, section with hydrophillic aluminium finned copper tubes (tube thickness not less than 0.5mm), Filter section with 50 mm thick flange type pre filter & MERV-13 fine filter on discharge or as per site requirement. , belt drive package with TEFC drive motor suitable for 415 ± 10% volts, 50 Hz, 3 phase, A.C supply,Mixing box with Aluminium Anodised Extruded dampers at fresh and return air cutouts, drain connections with drain valve, stainless steel drain pan, thermometers and pressure gauge at the inlet and outlet of cooling coil, necessary vibration isolation arrangement ,Light,etc,Whole unit should by AHRI Certified complete as per specifications of following capacity: |
| 84 | Including Hardware for hanging of AHU with GI thread rods, check nuts/washers |
| 85 | PAN type Humidifier: Thyrister Based Pan Type Humidifier for Humidification of dry ambient along with its all connecting wires for all FM type AHUs |
| 86 | Variable Frequency drive for for all AHU motors and all dampers must have BMS compatibale |
| 87 | CFM TYPE SP CC /TR |
| 88 | 1200 CS 100 (6+2) RD /3.0 along with HEPA Recovery Room + Change Rooms + Corridoor at 4th floor (a part of septic OT Area) |
| 89 | 2000 CS 100 (6+2) RD /5.5 along with HEPA filter for HDU at 2nd Floor |
| 90 | 2200 CS 110 (6+2) RD /6.0 along with HEPA filter for ICUs |
| 91 | 2700 CS 110 (6+2) RD /7.0 along with HEPA filter for ICUs |
| 92 | 3500 CS 110 (6+2) RD /10.0 along with HEPA filter for Minor OT at 2nd Floor |
| 93 | 4000 CS 110 (6+2) RD /10.0 along with HEPA filter for ICU & Isolation Room at 4th Floor |
| 94 | 3000 CS 110 (6+2) RD /8.0 Septic OT at First Floor (Hepa filters to be provided in OT Plenum) |
| 95 | 3000 CS 110 (6+2) RD /8.0 Septic Labour Ward at 2nd Floor along with Hepa Filters |
| 96 | 3100 CS 110 (6+2) RD /10.0 Delivery Room with HEPA filters for Epidural Room at Gr Floor |
| 97 | 4000 FM 125 (6+2) RD /10.0 for OT1 & OT2 at FF (Hepa filters to be provided in OT Plenum) |
| 98 | (Make: As per approved make list attached) |
| 99 | Floor Mounted AHU's (5.2) |
| 100 | Supplying, installing, testing and commissioning of factory built weather Proof Floor mounted double skin type air handling units with thermal break profile made of Min 32+-2 mm thick panels consisting of pre plasticized G.I casing made of thickness 0.8 mm outside layer and sheet of thickness 0.8mm inside layer with polyurethene foam (PUF) CFC Free insulation of density 40+-2 kg/m3 factory injected between them by injection moulding machine, extra 25mm acoustic insulation of opencell nitrile rubber with 0.8mm AL perforated sheet, complete with blower section with blower DIDW backward curved centrifugal fan for FM AHU's, 6 row deep cooling coil, section with aluminium finned copper tubes (tube thickness not less than 0.5mm), Filter section with 50 mm thick box type pre filter & microvee filter on common frame. , belt drive package with TEFC drive motor(IE-3) suitable for 415 ± 10% volts, 50 Hz, 3 phase and VFD Compatible, A.C supply,Mixing box with Aluminium Anodised Extruded dampers at fresh and return air cutouts.,drain connections with drain valve, stainless steel drain pan, thermometers and pressure gauge at the inlet and outlet of cooling coil, necessary vibration isolation arrangement etc, Whole unit should by AHRI Certified complete as per specifications of following capacity. |
| 101 | CFM TYPE SP CC /TR |
| 102 | 7000 FM 80 6.0 RD 17 |
| 103 | 9000 FM 80 6.0 RD /25 |
| 104 | 10500 FM 80 6.0 RD /25 |
| 105 | (Make: As per approved make list attached) |
| 106 | Ceiling Suspended AHU |
| 107 | Supplying, installing, testing and commissioning of factory built weather Proof Ceiling Suspended double skin type air handling units with thermal break profile made of Min 32 +-2 mm thick panels consisting of pre plasticized G.I casing made of thickness 0.6 mm outside layer and sheet of thickness 0.6mm inside layer with polyurethene foam (PUF) CFC Free insulation of density 40+-2 kg/m3 factory injected between them by injection moulding machine, complete with blower section with blower DIDW backward/Forward curved centrifugal fan for CS AHU's, 6 row deep cooling coil, section with aluminium finned copper tubes (tube thickness not less than 0.5mm), Filter section with 50 mm thick box type pre filter & microvee filter on common frame. , belt/Direct drive package with TEFC drive motor(IE-3) suitable for 415 ± 10% volts, 50 Hz, 3 phase and VFD Compatible, A.C supply,Mixing box with Aluminium Anodised Extruded dampers at fresh and return air cutouts.,drain connections with drain valve, stainless steel drain pan, thermometers and pressure gauge at the inlet and outlet of cooling coil, necessary vibration isolation arrangement,Light, etc, Whole unit should by AHRI Certified complete as per specifications of following capacity: |
| 108 | CFM TYPE SP CC /TR |
| 109 | 1500 CS 55 6.0 RD /4.0 |
| 110 | 2000 CS 55 6.0 RD /5.0 |
| 111 | 2200 CS 55 6.0 RD /5.5 |
| 112 | 2800 CS 55 6.0 RD /7.0 |
| 113 | 3000 CS 55 6.0 RD /8.0 |
| 114 | 3500 CS 55 6.0 RD /8.0 |
| 115 | 3500 CS 55 6.0 RD /11.0 |
| 116 | 4000 CS 65 6.0 RD /10.0 |
| 117 | 4400 CS 65 6.0 RD /11.0 |
| 118 | (Make: As per approved make list attached) |
| 119 | Treated Fresh Air Units |
| 120 | Supplying, installing, testing and commissioning of factory built Ceiling Suspended/Floor Mounted double skin type air handling units with thermal breakprofile for design of 100% fresh air made of min 25 mm thick panels consisting of pre plasticized G.I. casing of thickness 0.8 mm outside layer and plane GI of 0.8mm inside layer with polyurethene foam (PUF) insulation of density 32 kg/m3 factory injected between them by injection moulding machine, complete with blower section with blower DIDW backward curved centrifugal fan, 8 row deep cooling with aluminium finned copper tubes (tube thickness not less than 0.5mm), Min MERV 7/10 Pre filter sections or as per norms , belt drive package with TEFC drive motor suitable for VFD & 415 ± 10% volts, 50 Hz, 3 phase, A.C supply, complete, drain connections with drain valve, light,stainless steel drain pan ,necessary vibration isolation arrangement etc, Whole unit shall be ahri certified ,complete as per specifications of following capacities : |
| 121 | CFM TYPE SP CC /TR |
| 122 | 2000 CS 70 8 RD /20 |
| 123 | AHU For Exhaust |
| 124 | Supplying, installing, testing and commissioning of factory built Floor Mounted/Ceiling suspended double skin weather Proof type air handling units made of 25 mm thick panels consisting of pre plasticized G.I. casing of thickness 0.6 mm outside layer and plane GI of 0.6mm inside layer with polyurethene foam (PUF) insulation of density 32 kg/m3 factory injected between them by injection moulding machine, complete with blower section with blower DIDW backward/Forward curved centrifugal fan, belt drive package with TEFC drive motor suitable for VFD & 415 ± 10% volts, 50 Hz, 3 phase, A.C supply, complete with canvass connections ,necessary vibration isolation arrangement etc, complete as per specifications of following capacity |
| 125 | 800 CFM 75 mm Static with Hepa Filter(H-13) of 99.77% to 3 Micron & Micro Vee Filters at discharge and Pre Filters with MERV 8 |
| 126 | 700 CFM 75 mm Static with Hepa Filter(H-13) of 99.77% to 3 Micron & Micro Vee Filters at discharge and Pre Filters with MERV 8 |
| 127 | 660 CFM 45 mm Static with Min MERV 7 Pre filter sections and MERV 14 Fine filters at discharge ) |
| 128 | 800 CFM 45 mm Static with Min MERV 7 Pre filter sections and MERV 14 Fine filters at discharge) |
| 129 | (Make: As per approved make list attached) |
| 130 | FAN COIL UNITS (Standard) |
| 131 | Supply,Installation , testing and commissioning of fan coil units of specified capacities and air flow as per the specifications, complete with auxillary drain pan |
| 132 | Fan coil unit shall be supplied with approved make of factory fitted adequately sized insulated (with nitrile foam) two way motorized valves , insulated brass ball valves-one with Y strainer, and the other without Y strainer complete with room thermostat for fan speed control , associated conduiting and wiring between the thermostat , 2 - way valve .etc. |
| 133 | Cost of fan coil unit shall be inclusive of approved make room thermostat (heating and cooling, with fan speed control), and associated MS conduiting and wiring etc.between the thermostat and two way valve, for a standard length of approximately 5-7 M per fan coil unit. |
| 134 | Providing and fixing in position the following Fan Coil units complete with all valves and accessories as described above. |
| 135 | 1.5 TR nominal capacity ( 600 CFM) |
| 136 | 2.5 TR nominal capacity ( 1000 CFM) |
| 137 | (Make: As per approved make list attached) |
| 138 | WATER COOLED CASSETTE ACS |
| 139 | Supply, installation, testing & commissioning of Water cooled Cassette Unit suitable for both heating/cooling with copper tube and aluminium finned cooling coil, low noise fan and motor with ON/OFF and 3 speed control and suitable for 1 phase, 230 + 6%V, 50 Hz electric supply, with cordless remote/corded control, fabric filter, drain pump, and decorative front grille. The Unit shall be complete with stainless steel duly insulated main and auxiliary drain pan. The unit shall be complete with electrical terminal strip, wiring in conduit upto thermostat box or any other advance technology. Unit shall have copper pipes for coil connection complete . The unit shall also have fresh air pocket provision. The front grill shall be 4 way type. The noise level at low speed shall be in the range of 38 to 42db & at high speed upto 45db. Noise levels are at a distance of 2M from the unit. (Note :Tonnage Variation allowed upto ±5%) : Note: Vendor should include the cost of of copper pipe connection upto 1m along with all accessories complete in all respect |
| 140 | 3.5-4.0 Tr Four way |
| 141 | AOP cell with NANOX & PLASMAOX technology & Bi Polar Ionizer. |
| 142 | SITC of Advanced Oxidation Pentplasma (AOP) cells comprising of UVC lamp 254 NM on NANO metallic compound target Alumninum matrix cell duly enclosed by a poly casing tube, with the capability to produce plasma Hydroxyl oxidizers along with anti microbial coating (EPA Approved). The unit shall have inbuilt multipin ion generator (+-10^6) pins along with ultrasonic radio frequency waves for pest repellancy. The UV-C lamp will be a low-pressure mercury type and of such intensity as to provide minimum performance as listed below. The UV-C lamp will produce only Germicidal UV (by definition this means 99.99% UV-C energy).The cell will have built in LED indication system stating the operation of the 3 technologies the UV lamp, ionizer and pest repellant. The power / control cabling between the Pentagon units and the power source / controls shall be included in the cost .The system shall be capable of reducing microbial bacteria, Covid 19 virus,virus and spores , VoC’, odors and particulates matter. The equipment shall conform to CE and ROHS. Standards certifications shall be submitted along with the technical submital. The Pentagon cells should be selected by considering a load factor calculation for each specific area where the equipment is to be installed. The wattage shall not be less than mentioned. The AOP/ Pentagon Cells Should be complete with Transformers, control cabling and Plug Top & necessary power cable. |
| 143 | Duct Mounted AOP with UVC Lamp System for following Air Flow's |
| 144 | Upto 1500 CFM |
| 145 | 1501 CFM to 6500 CFM |
| 146 | 6501 CFM to 15000 CFM |
| 147 | (Make: Ultrafresh, VS Eviropure, Ultrapure) |
| 148 | Temperature and RH sensor and adjuster package. |
| 149 | Supply,install-(grout),test and commission micro-processor based Room temperature, humidity sensor and remote adjuster package within a MS housing -wall ,suitable for mounting, and having a stainless steel cover plate.This package shall have a temperature and humidity display - red 2\\" high LED character for operation rooms, and other critical areas. |
| 150 | Sensor, adjuster (Snap acting humidistat/Proportional thermostat- Microprocessor based) and displayer package, as described above. |
| 151 | (Make: As per approved make list attached) |
| 152 | Pan Type humidifier and humidistat |
| 153 | Supply, install, test and commission snap acting humidistat . |
| 154 | Supply, install, test and commission wall / floor mounted Pan Type Humidifier package of following capacities. |
| 155 | 3.0 KW |
| 156 | (Make: As per approved make list attached) |
| 157 | EXPANSION TANK |
| 158 | Supply, Installation ,Testing and commissioning of MS.Open expansion tank with minimum thicknessof 3.0mm as per the specifications.The Open vessel expansion tank shall be complete with all accessories so as to make it ready for installation and commissioning on site.The tank shall be insulated with the approved method of insulation, and shall be complete with water make-up connection and system .The expansion tank will be supplied,Non return Valve ,Float valve,Ball Valves and interconnecting piping etc. |
| 159 | 2000 Ltr . Open Expansion Tank duly insulated and with all accessories. |
| 160 | AIR SEPARATOR |
| 161 | Supply,installation,testing and commissioning of Microbubble Air & Dirt Separator,with matching flanges, bolts, nuts & gasket, PN16 complete with flanged connection and as per the specifications as detailed earlier in the relevant section of specifications , and duly insulated with 50 mm thick TFF expanded polysterene and cladded with 26G aluminum sheet. |
| 162 | 200 mm Dia Air Separator, duly insulated. |
| 163 | (Make: As per approved make list attached) |
| 164 | Supplying, fixing, testing and commissioning of following valves, strainers, gauges in the chilled water plumbing duly insulated to the same specifications as the connected piping and adequately supported as per specifications. (Make: As per approved make list attached) |
| 165 | SITC Water Flow Switches (Brass body) . |
| 166 | SITC Auto Air Vent Valve 1/2\\". |
| 167 | PICV Valves |
| 168 | Supply, Installation, Testing & Commissioning of Insulated Two- way ball type pressure independent control valve with flanged end ISO7005-2, flow capacity as desired, Min.PN16, equal percentage flow characteristic, body GGG50 ductile iron with stainless steel ball. Non spring return rotary type modulating actuator, torque as required, close-off min pressure 700 kPa, power supply 24 V AC/DC, control signal 2-10 V DC, feedback signal 2-10 V DC, IP54. |
| 169 | 65 mm dia |
| 170 | 50 mm dia |
| 171 | 40 mm dia |
| 172 | 32 mm dia |
| 173 | 25 mm dia |
| 174 | 20 mm dia |
| 175 | 15mm dia |
| 176 | (Make: As per approved make list attached) |
| 177 | Brass Ball Valves |
| 178 | SITC of Brass Ball Valves of dia 40mm with Strainer |
| 179 | SITC of Brass Ball Valves of dia 40mm without Strainer |
| 180 | SITC of Brass Ball Valves of dia 32mm with Strainer |
| 181 | SITC of Brass Ball Valves of dia 32mm without Strainer |
| 182 | SITC of Brass Ball Valves of dia 25mm with Strainer |
| 183 | SITC of Brass Ball Valves of dia 25mm without Strainer |
| 184 | (Make: As per approved make list attached) |
| 185 | VALVES/CONTROLS - PN-16 without Insulation (Make :as per approved make list attached). |
| 186 | Supplying, fixing, testing and commissioning of following valves, gauges and strainers for condenser water circulation as per specifications. |
| 187 | BUTTERFLY VALVE (MANUAL) with C I body SS disc nitrile sheet O - ring & PN 16 pressure rating as specified. |
| 188 | 250 MM DIA (Gear Box type) |
| 189 | BALANCING VALVE WITH BUILT IN MEASURING FACILITY with C I body flanged construction with EPDM coated disc with long pitch with protected out pipe insulation & PN 16 pressure rating for chilled / hot water circulation as specified. |
| 190 | 200 MM DIA |
| 191 | 150 MM DIA |
| 192 | Y- STRAINERS (PN-16) |
| 193 | Providing and fixing in position the following Insulated Y-Strainers |
| 194 | 200 mm dia |
| 195 | POT- STRAINER(PN-16) |
| 196 | Proiding and Fixing of Pot strainer with drain valve complete in all respect of following dia |
| 197 | 250 mm |
| 198 | NON - RETURN VALVE with duel plate of C I body SS plates vulcanized NBR seal flanged end & PN 16 pressure rating for chilled / hot water circulation as specified. |
| 199 | 200 MM DIA |
| 200 | SITC Water Flow Switches (Brass body) complete with copper control wiring at chiller outlet of each machine |
| 201 | AUTO AIR VENT |
| 202 | Supply, installation ,testing and commissioning of Auto Air vents,at the specified locations in the chilled water piping , alongwith isolation ball valves, as per approved makes |
| 203 | Auto air vent with isolating ball valves (15 mm dia) |
| 204 | CONDENSATE DRAIN PIPE |
| 205 | Providing and fixing and in position the following PVC pipes (Min. Thickness 3.0mm) for condensate drain duly insulated with minimum 6.0 mm 'O' Class Nirile rubber & duly secured with adhesive tape as per specification ,cut to required length and installed with all joints , including the necessary fittings. (For all the AHU/FCU units upto the main header in the shaft dor vertical risers |
| 206 | 65 mm dia |
| 207 | 50 mm dia |
| 208 | 40 mm dia |
| 209 | 32 mm dia |
| 210 | 25 mm dia |
| 211 | (Make: As per approved make list attached) |
| 212 | Factory Fabricated Duct - AL duct |
| 213 | Supply,Fabrication , Installation and testing of Aluminium sheet metal ducts in accordance with the approved shop floor drawings and specifications , and shall also confirm to the BIS specifications. The hardware shall be chrome plated or of stainless steel.All lateral and transverse joints shall be sealed with silicon based mastic sealant. |
| 214 | Aluminum Sheet thickness - 22 Gauge |
| 215 | Aluminum Sheet thickness - 20 Gauge |
| 216 | (Make: As per approved make list attached) |
| 217 | Fresh Air/Exhaust Air Louvers |
| 218 | Supply, Installation, Testing and Commissioning of extruded aluminium louvres with frame bird screeen 50 mm pre-filter with frame, mounting arrangement etc. as per specifications and drawings. |
| 219 | Fresh Air/Exhaust Louvers |
| 220 | (Make: As per approved make list attached) |
| 221 | HEPA Filters & OT Plenum for Laminar Flow |
| 222 | SITC of Aluminium white epoxy powder coated Factory Fabricated O.T. PLENUM (Aprox.size 6'x6') & HEPA Filters Having efficiency 99.97%down to 3 Micron ,I.P.D < 15 mm HG & F.P.D. = 50 mm HG, The Hight of OT Plenum should not be more than 290 mm |
| 223 | SITC of Aluminium white epoxy powder coated Factory Fabricated O.T. PLENUM (Aprox.size 8'x6') & HEPA Filters Having efficiency 99.97%down to 3 Micron ,I.P.D < 15 mm HG & F.P.D. = 50 mm HG, The Hight of OT Plenum should not be more than 290 mm |
| 224 | (Make: As per approved make list attached) |
| 225 | MECHANICAL INSULATION |
| 226 | DUCT LINE ACOUSTIC TREATMENT |
| 227 | Supply, Installation, Testing and Commissioning of Acoustic lining inside ducts/plenum using open cell nitrile rubber foam having microban anti-microbial/ anti fungal product protection and of 160-180 kg / m³ density as per ASTM D3575, class 1 ratingn As per BS476,PART-7, cut to required sizes and to be stuck to the inside of duct surfaces with adhesive as approved by the manufacturer. (Rubber based solvent). as per specifications |
| 228 | 15mm thick sound board for Floor Mounted AHU's |
| 229 | 10mm thick sound board for CS AHU's |
| 230 | (Make: As per approved make list attached) |
| 231 | DUCT LINE THERMAL INSULATION(Inside Conditions) |
| 232 | SITC of Physically / Chemically crosslinked polyethylene foam, with factory reinforced alupet foil facing, ANTI MICROBIAL/ANTI FUNGAL,HFC & CFC free , Negligible VOC level with Class O fire properties,with very low fire propagation of < 5.5 and passing E-84 at < 25/50, as per technical specification, the density of the foam should be not less than 25-30kg/m3 and the maximum thermal conductivity K should be 0.032W/mK@ 23 Deg C , the permeability resistance factor u shouldn't be less than 14000. The product shall have temperature range of –20oC to 115oC |
| 233 | 13 mm thick |
| 234 | (Make: As per approved make list attached) |
| 235 | DUCT LINE THERMAL INSULATION (Outside Conditions exposed to sun) |
| 236 | Physically / Chemically crosslinked polyethylene foam, with factory laminated heavy duty and ultra tough multi-layered composite aluminium foil facing, with puncture resistance of >400N and Class O fire properties as per BS 476 Part BS 476 Part 6 & 7 and as per the tender technical specification and density of the foam should be not less than 25 - 30 kg/m3 and maximum thermal thermal conductivity K should be 0.032W/mK@ 23 Deg C & the permeability resistance factor u shouldn't be less than 97000. |
| 237 | 25mm thick |
| 238 | ASSOCIATED ELECTRICAL WORKS |
| 239 | The rates for the distribution boards from the Breakers and instruments shall also include the following : |
| 240 | A ,Wiring for light / Fan points with 1.5 sq. mm PVC insulated copper conductor 1100 Volt grade stranded flexible FRLS wires of approved make in 1.6 mm thick 25 mm dia MS conduit including cost of providing & fixing saddles, hangers, supports,cutting chases and filling chases for recessed conduiting, and including the cost of providing and fixing a 6 amp 240 Volt Modular Plate type switches of approved quality, colour, make and design with moulded cover plate in zinc chromate passivated MS box and including the cost of running 1.5 sq. mm PVC insulated copper earth wire for loop earthing etc. complete |
| 241 | B TPN ACB’s / MCCB’s shall mean 3 pole ACB’s / MCCB’s with adequate size of neutral link |
| 242 | C All MCB’s shall be of minimum 10 KA breaking capacity or as metioned in BOQ. |
| 243 | D The breaking capacity of MCCB’s are mentioned panel wise. All MCCB’s shall be with thermal magnetic microprocessor releases as per BOQ and following |
| 244 | i. MCCB rating upto 250 Amps with thermal magnetic releases |
| 245 | ii. MCCB above 250 Amps with microprocessor releases. |
| 246 | All MCB’s used for protection of resistive and lightly inductive load shall be type “B” characteristic and inductive (motor) load shall be of type “C” characteristic. |
| 247 | F Degree of protection for following type of distribution panel enclosure shall be as per IS:13947-1993 |
| 248 | IP 42 for indoor panels. |
| 249 | ii. IP 55 for ODU panel. |
| 250 | G All MCCB’s shall be provided with operating mechanism for door interlock |
| 251 | H All hinged door shall be earthed through 2.5 sq mm tinned braided copper wire. |
| 252 | I Providing cable clamps / supports within distribution boards cable alley. |
| 253 | J Current density of aluminium shall be 1sq mm for 1.0 Amps for rated current of bus bars. |
| 254 | K Model, current capacity location and frame size of switchgear shall be written inside of the panel doors with paint / permanent marker as approved shop drawings / site requirment |
| 255 | L All meter shall be digital type. |
| 256 | M Current Transfomer shall be resin cast. |
| 257 | N All Panels Must be BMS Compatible |
| 258 | Main Electrical Panel |
| 259 | Design, fabrication, assembling, wiring, supply, installation, testing and commissioning of following LT panels fabricated out of 14 guage for load bearing and 16 gauge for non load bearing CRCA sheet steel in cubical formationwith reinforecment of suitable size angle iron and channel T iron flats. All steel material used in the construction of panels shall be powder coated. A solid busbar shall be provided at the bottom of the panel with two connecting eyes for termination. The boards shall be suitable for 415 volts, 50 Hz, 3 phase , 4 wire supply system. All the hardware used in the fabrication of the panel shall be galvanized with zinc passivation. The panel shall be compartmentalized to accommodate one feeder in each compartment. A vertcal cable alley of suitable width shall be provided to serve on or two vertical feeder sections. Also the opening between the busbar chamber and the feeder section shall be shrouded with bakelite / hylam sheet with min.3 mm thickness. |
| 260 | The panel drawing shall be approved before taking up the fabrication and Sall have compatible BMS for future requirment. |
| 261 | In All panels Each starter should have remote control compatibilty and interlocking facilities including auto manual switch, NO/NC contacts for control and must have auto manual operation suitable to take signal from fire alarm panel for automatic operation of fan in case of fire. All smoke /vent. fan panel the starters shall have suitable facility to operate with fire sensing control modules. |
| 262 | Plant Room Panel |
| 263 | 1 No.1600 amp EDO ACB 65 KA with Microprocessor release alonwith protection of S/c, E/F, etc |
| 264 | Multi Function Digital Meter class 1.0 Accuracy Schnieder series 64XX or equivalent of the same model in Elmeasure/ HPL/Reputed with CTs of the desired rating as per the load |
| 265 | Phase indicating lights RYB with control fuses. |
| 266 | Breaker ON/OFF/TRIP indicating |
| 267 | lights. Bus Bars |
| 268 | 2000 amp TPN Aluminum Bus Bar with heat shrinkable insulation colored sleeves. |
| 269 | Outgoings |
| 270 | 3 Nos. 400 amp, MCCB with an adjustable release, 50 KA with Rotary operating handles for Chiller |
| 271 | 3 Nos. MCCB for 25 KW or as per the rating of the Chilled water pumps by the Chiller Manufacturer (2Working + 1Standby) for primary Chilled water Pumps without starter as VFD to be available on Chilled water pump side with Digital Ampere Meter Class 1.0 with CT of suitable rating |
| 272 | 3 Nos MPCB for 27 KW or as per rating of the Condenser water pump and the Star Delta starter with Contactors as per the Cordination chart with O/L Relay, S/D Timer and SPP (2 working + 1 Standby)with Digital Ampere Meter Class 1.0 with CT of suitable rating |
| 273 | 3 Nos MPCB for 7.5 KW x 2nos or as per the manufactrer specifications for the cooling towers with the DOL starter with Contactor as per the Cordination chart with O/L Relay and SPP (2 working + 1 Standby) with Digital Ampere Meter Class 1.0 with CT of suitable rating |
| 274 | 2 Nos MPCB for 10KW or as per rating of the Monsoon Re-heating pump and the Star Delta starter with Contactors as per the Cordination chart with O/L Relay, S/D Timer and SPP (1 working + 1 Standby) with Digital Ampere Meter Class 1.0 with CT of suitable rating |
| 275 | 2 Nos. 450-600 amp, MCCB with an adjustable release, 36 KA with Rotary operating handles for HWG (1W plus 1Standby) with Digital Ampere Meter Class 1.0 with CT of suitable rating |
| 276 | 2 Nos. 200 amp, MCCB with an adjustable release, 36 KA with Rotary operating handles for HWG (1W plus 1Standby) with Digital Ampere Meter Class 1.0 with CT of suitable rating |
| 277 | 3 Nos DP MCB 6Amps 10 KA for supplying to various control equipment |
| 278 | 1 Nos MCCB upto 300 Amps for AHU distribution panel |
| 279 | 1 Nos, spare space MCCB upto 100 Amps |
| 280 | Unloading at site, placement of Panel on the foundation,Making foundation, co-ordination during execution, rendering necessary guidance for execution, supervision, testing, commissioning and startup of above mentioned Panel along with all accessories.The panel drawing shall be approved before taking up the fabrication from EIC |
| 281 | (Make: As per approved make list attached) |
| 282 | HVAC AHU Panel with Exhaust AHU along with VFD |
| 283 | Incoming |
| 284 | 1 No. 63 amp MCCB TP 25 KA with Rotary Mechanism and spreader links |
| 285 | Phase indicating lights with control |
| 286 | fuses. Breaker ON/OFF/TRIP indicating |
| 287 | lights. Bus Bars |
| 288 | 100 amp TPN Aluminum Bus Bar with heat shrinkable insulation colored sleeves |
| 289 | Multi function meter Digital with suitable CT type class 1.0 |
| 290 | Outgoings |
| 291 | 2 Nos. MCB TPN 6-32 Amps to supply to VFDs (AHU & Exhaust VFD) Rating of the TPN as per the VFD maximum load with Digital Ampere Meter Class 1.0 with CT of suitable rating |
| 292 | 2 Nos VFD of HP rating as per the AHU and Exhaust AHU with console or related interface to be working with the controller provided by the AC company, herein referred to as the DTS/DDC Controller with Digital Ampere Meter Class 1.0 with CT of suitable rating |
| 293 | 1 Nos DP MCB 16 Amps |
| 294 | 2 Nos. 6 A, MCB for UVC Lamp (if required) |
| 295 | Transformer or powersupply with MCB DP 6 Amps |
| 296 | (Make: As per approved make list attached) |
| 297 | Sub Panel for AHU Motors up to 5.5 KW |
| 298 | SITC of Wall mounted sub panel boards for AHUs, Blower with switch, starters, lamps inter connections, current operated single phase preventer, A/M switch etc. as per specifications and drawings and as required. |
| 299 | 1 No. incoming upto 32Amps 4 pole TP+NL MCB with Digital Mutli function Meter Class 1.0 with CT of suitable rating |
| 300 | RYB Indicators |
| 301 | 2 Nos. Push Buttons On/Off |
| 302 | 1 No. single phase preventor |
| 303 | 1 Nos. DOL starter with Power contactor and MPCB as incomer of the starter with SPP with Digital Ampere Meter Class 1.0 with CT of suitable rating |
| 304 | 1 No MCB DP |
| 305 | 2 Nos. 6 A or suitable, MCB for UVC (if required) |
| 306 | (Make: As per approved make list attached) |
| 307 | Sub Panel for AHU above 5.5 KW |
| 308 | SITC of Wall mounted sub panel boards for AHUs, Blower with switch, starters, lamps inter connections, current operated single phase preventer, A/M switch etc. as per specifications and drawings and as required. |
| 309 | 1 Nos. 63-100 Amps TP+NL MCCB 25 KA ICU=ICS=100% with Terminals, ROM and necessary accessories with Mutlifunction Meter Class 1.0 with CT of suitable rating |
| 310 | RYB Indicators |
| 311 | 2 Nos. Push Buttons On/Off |
| 312 | 1 No. single phase preventor |
| 313 | 1 Nos. Star Delta starter with Power contactor and MPCB as incomer of the starterwith SPP with Digital Ampere Meter Class 1.0 with CT of suitable rating |
| 314 | 1 No MCB DP |
| 315 | 2 Nos. 6 A or suitable, MCB for UVC lamp (if required) |
| 316 | (Make: As per approved make list attached) |
| 317 | Distribution Panel for Ventilation Axial Fans (Separate Supply or independent supply required from generator ) |
| 318 | Design, fabrication, assembling, wiring, supply, installation, testing and commissioning of Wall/Floor mounted sub ditribution panel board for Ventilation Axial Fans Powder Coated Enclosure made out of TATA make CRCA sheet having 2 mm for load bearing surfaces & 1.6 mm for non load bearing surfaces ,duly powder coated having Siemens grey colour.as per specifications and drawings and as required.OEM/Panel Builder should CPRI approved at least 70K |
| 319 | Incoming TPN MCCB FEEDER |
| 320 | 1 No 160-200A, TPN 50KA MCCB with TMD Release having O/L,S/C, protections (ICU=ICS=100%) |
| 321 | 1 No.Rotary Handle for 200A MCCB |
| 322 | 1 No.Spreader Links for 200A TP |
| 323 | 1 No.Aux. Contact Block |
| 324 | 1 No.Multifunction Meter with builtin Selector switch |
| 325 | 3 Nos.CT's 200/5A For Metering |
| 326 | 3 Nos Indication Lamp R-Y-B |
| 327 | 4 nos Control MCB 6A SP.10KA Type C |
| 328 | 3 nos CT Shorting Link |
| 329 | 4 nos Control Terminals |
| 330 | Out Going 16-63A TPN MCCB FEEDER |
| 331 | 25 Nos MCB TPN 16-40 amps |
| 332 | 25 Nos Indication Lamp ON |
| 333 | Panel |
| 334 | 400A rating TPN Aluminium Bus Bar of Electrolytic Grade E-91E Bus Bar Supports, Colour Coded PVC Heat Shrinkable Sleeves |
| 335 | Hardware (PVC Cahnnels/MCB Channels/Fibre- Glass Gaskets/ Sleevs/ nuts/ bolt/ washers/ cooling fans etc Including complete wiring,thimbles etc. |
| 336 | Unloading at site, placement of Panel on the foundation, co-ordination during execution, rendering necessary guidance for execution, supervision, testing, commissioning and startup of above mentioned Panel.The panel drawing shall be approved before taking up the fabrication from EIC |
| 337 | (Make: As per approved make list attached) |
| 338 | Sub Distribution Panels for AHU's |
| 339 | SITC of panel board made of 1.6mm for non load bearing /2.0 mm thick steel sheet for non load bearing sections duly powder coated complete with Metering, indicating lights, CTS contactors, A/M Switch for remote controls operation complete as per specifications and drawings and as required.The panel manufacturer shall have min 70 KA CPRI Certification |
| 340 | Incomer |
| 341 | 1 Nos. 260-300 Amps 36 KA MCCB TP+NL with ROM & Links |
| 342 | 1 No. 400 Amps aluminium conductor bus bar duly sleeved |
| 343 | 1 No. Multifunction meter with CTs as per requirment |
| 344 | 3 Nos. phase indicating lamps |
| 345 | Outgoing |
| 346 | 50 Nos MCB suitable for 1.1 to 3.7 KW or suitable DOL Starter for AHU having contactors, LED indicators for on/off , O/L Relay, SPP, etc. as per coordination chart |
| 347 | 6 Nos MCB suitable for 5.5 to 7.5 KW or suitable DOL Starter for AHU having contactors, LED indicators for on/off , O/L Relay, SPP, etc. as per coordination chart |
| 348 | 1 Nos MCB TPN 32 Amps 'C\\" Curve Spare and complete Wiring inclusive of thimbles,etc |
| 349 | Hardware (PVC Cahnnels/MCB Channels/Fibre- Glass Gaskets/ Sleevs/ nuts/ bolt/ washers/ cooling fans etc Including complete wiring, thimbles etc. |
| 350 | Unloading at site, placement of Panel on the foundation, co-ordination during execution, rendering necessary guidance for execution, supervision, testing, commissioning and startup of above mentioned Panel.The panel drawing shall be approved before taking up the fabrication from EIC |
| 351 | (Make: As per approved make list attached) |
| 352 | Ventilation |
| 353 | S/I/T/C of CEILING MOUNTED JET VENT FAN |
| 354 | Supply, installing, testing and commissioning of Ductless Ventilation / Axial type Jet fans as per attached specifications for normal ventilation & smoke exhaust . Each fan shall be complete with dual speed motor and die cast aluminium impeller. Casing shall be made of Hot dipped Galvanized steel. The Motor shall be run on the electrical power suitable for 415V/3Ph/ 50Hz. |
| 355 | Supply, installing, testing and commissioning of Ductless Ventilation / Jet fans as per Specifications for Normal Ventilation and Smoke Exhaust. . The complete fan assembly with its casing, impeller and motor ( not only motor or one of the item ) shall be sourced from one manufacturer and certified and tested as per EN12101-3-:2015/Indian Standared as per NBCC, 300 degree for 2 Hrs operation.Silencer lenght should be 2 d. . Each Jet Fan assembly shall connect to a composite PLC Panel controlled by CO Sensors / Fire Alarm System for Smoke Extraction Dia of fan 315 mm or suitable dia |
| 356 | (Make: As per approved make list attached) |
| 357 | S/I/T/C of LONG CASED TUBE/ VANE AXIAL FAN WITH IE3 MOTOR |
| 358 | Supply, installation, testing and commissioning of Direct drive Long cased Tube/ VANE Axial fans complete with Hot dipped Galvanised Steel /Pre Galaavanised Steel Casing with spun flanges, adjustable pitch die cast aluminium impeller (Hub and Aerofoil blades) and IE3 motors. Casing position shall be as per the job requirement and shall be marked on the fan assembly.The complete fan assembly with its casing, impeller and motor ( not only motor or one of the item ) shall be sourced from one manufacturer and 300 degree C for 2 Hrs operation.The complete assembly must have certificate of consistency of performance by BSI .Motor Shall be suitable for 415 volts ± 10%, 50Hz ± 3 %, three phase A.C complete with starter having overload & single phase protection, support, mountings, vibration isolators, fire retardant flexible canvass connector 150 mm deep (Inlet & Outlet as required), bird screen (Inlet & Outlet as required), Including cost of Back draft Damper,Exhaust Louvers , : Fan must be licensed to bear AMCA seal for air performance and sound performance ad the claimed air and sound performance must be demonstrated in AMCA accredited laboratory as per AMCA publication 211 and 311 |
| 359 | Supply, installing, testing and commissioning of Single speed Long cased VANE Axial Fans of capacity 9600cfm @ 25 mm Static (for normalmode) Fans should be suitable for emergency mode operation (300 Deg / 2 Hrs) |
| 360 | (Make: As per approved make list attached) |
| 361 | S/I/T/C of LONG CASED TUBE /VANE AXIAL FAN WITH IE3 MOTOR (FOR FRESH AIR) |
| 362 | Supply, installation, testing and commissioning of Direct drive Tube VANE Axial fans complete with Hot dipped Galvanised Steel /Pre Galvanised/ MS Powder coated Casing with spun flanges, adjustable pitch die cast aluminium impeller (Hub and Aerofoil blades) and IE3 motors. Casing position shall be as per the job requirement and shall be marked on the fan assembly.The complete fan assembly with its casing, impeller and motor ( not only motor or one of the item ) shall be sourced from one manufacturer.MotorShall be suitable for 415 volts ± 10%, 50Hz ± 3 %, three phase A.C complete with starter having overload & single phase protection, support, mountings, vibration isolators, fire retardant flexible canvass connector 150 mm deep (Inlet & Outlet as required), bird screen (Inlet & Outlet as required) and including cost of Back draft damper ,GI construction fresh air louvers with min. 60 % free area , and painted in baked enamel shade with metallic frame work complete as per specification approved drawings and schedules. Louvers need to be suitable in order avoid rain water entry in to spaces @ 15 degree deflection with bird screen complete as per specification approved drawings and schedulesetc. & of following capacity. Fan must be licensed to bear AMCA seal for air performance and sound performance ad the claimed air and sound performance must be demonstrated in AMCA accredited laboratory as per AMCA publication 211 and 311. |
| 363 | Supply, installing, testing and commissioning of Single speed Long cased VANE Axial Fans of capacity 9600cfm @ 25 mm Static (for normalmode) Fans should be suitable for emergency mode operation (250 Deg / 2 Hrs) |
| 364 | (Make: As per approved make list attached) |
| 365 | S/I/T/C OF CO SENSORS |
| 366 | Supply, installation, testing and commissioning of CO Sensors (0 - 250 PPM detection Range) complete with hanging arrangments. (Make: As per approved make list attached) |
| 367 | CFD Analysis |
| 368 | Preparation and approval of CFD ( Computational Fluid Dynamics ) Analysis in Basement Areas ( both levels) .CFD analysis to decide the correct location and quantity of jet fans. CFD analysis will be carried out for both normal and fire mode ventilation situation considering 6/12 ACPH, airflow strategy and control strategy to confirm the operation logic. CFD analysis will model all the cars, car parking bays, beams, structures, columns, voids, shafts, ramps, proposed fresh air route, fresh air shaft, exhaust air shaft and preliminary location of jet fans shown in the drawing. CFD output will give complete simulation of ventilation scheme not limited to velocity profile, temperature profile, smoke temp and movement profile, CO level profile, air movement profile. The number of repeat simulations shall be carried out until satisfactory results are achieved. |
| 369 | Control Panel for Ventilation PLC Based |
| 370 | Supply,Installation,Testing and Commissioning Contol Panel Made out of TATA/SAIL/ESSAR/JINDAL/Reputed make sheet having thickness 2.0 mm for load bearing surfaces & 1.6 mm Non bearing surfaces duly processsed powder coated having Siemens grey colour as per following specifications complete in all respect |
| 371 | SITC of Electrical cum PLC Based Panel for Basement with MCB feeders with starters for 8 nos dual speed 3 phase Jet Fan fans of 1.7/0.34 kW each,MCCB feeders with starters for 4nos. Exhaust fans single speed of upto 7.5KW & 4 No Fresh Air Fan of upto 7.5 kw(optional). controlled by nos- upto 5 NO CO Sensors, with suitable incomer MCCB, VIF Meter on mains & on each feeder herein referred to as each O/G section to Jet fans as well as Exhaust with Amperemeter Digital, aluminium bus bar as per requirment, PLC logic controller with necessary internal control wiring etc, Material Make of Switchgear:ABB/ Schneider/ Siemens |
| 372 | (Make: As per approved make list attached) |
| 373 | Staircase,Lift Lobby & Lift Pressurisation Fans |
| 374 | Supply, Installation testing & Commissioning of AXIAL FLOW FAN complete with totally enclosed fan cooled motor direct driven, and fan shaft, motor mount as per the specifications. Fan motor shall be Class-F, suitable for 415 + 10% volts, 50 cycles, 3 phase power supply. The Axial fans shall be supplied with power pane. Fan capacity shall be as follows: |
| 375 | Casing shall be GI/hot dip galvanized to protect against corrosion. Length of the casing shall be greater than the length of fan & motor assembly.IMPELLER of axial fans shall be constructed from die cast aluminum. Profiles of impeller blade should be of aerofoil type to have high efficiency and low noise levels. Impeller must be statically and dynamically balanced as per ISO 1940 grade 6.3. Fan shall be selected based on best efficiency points with fan pitch angle selected in the middle range out of available whole range of fan pitch angle to allow possible fan speed adjustment on site. |
| 376 | Liftwell Pressurisation Axial Fan 17300cfm x 20mm sp |
| 377 | Staircase Pressurisation Axial Fan 23000 cfm x 25mm sp |
| 378 | Lift Lobby Pressurisation Axial Fan 2500 cfm x 20mm sp |
| 379 | Lift Lobby Pressurisation Axial Fan 5000 cfm x 20mm sp |
| 380 | (Make: As per approved make list attached) |
| 381 | SITC of Starter Panels- Supply /Exhaust Air Blower up to 7.5 KW) |
| 382 | 01 No. - 0-40 A TP MCB with Conforming to BIS 25 A DOL starter, overload relay, start/stop push buttons, ammeter (0-63A) on / off / trip indication lights with protection fuse, single phase preventer |
| 383 | Star Delta starter control panel must have MCB TPN, on off push button, on/off/trip indicators, potential free contacts for Fire Alarm for operation of the starter in case of fire, manual reset overload relays, earthing & armoured fire proof cabling from starter panel to fan motor with proper tray supports & BMS compatible. Starter panel with auto manual toggle switch,Timer based & facility to operate on remote signal from smoke control panel . |
| 384 | CABLING (POWER |
| 385 | Power Cabling and Earthing |
| 386 | Supply, installation, testing & commisioning of Aluminum/CU conductor cables PVC sheathed, armoured cables of 1.1 KV grade with termination glands and GI earthing, identification tags, clamps and saddles etc. |
| 387 | 3.5Cx300 Sqmm Al |
| 388 | 3.5Cx240 Sqmm Al |
| 389 | 3.5Cx150 Sqmm Al |
| 390 | 3.5C x70 Sqmm Al |
| 391 | 4C x35 Sqmm Al |
| 392 | 4.0Cx16 SqmmAl |
| 393 | 4.0Cx10 Sqmm Al |
| 394 | 4.0Cx 06 Sqmm Al |
| 395 | 4.0Cx04 Sqmm CU |
| 396 | 4.0Cx2.5 Sqmm CU |
| 397 | 2Cx04 Sqmm (Cu Conductor flexible) |
| 398 | (Make: As per approved make list attached) |
| 399 | Control Cabling |
| 400 | Supply, installation, testing & commisioning of Copper conductor , PVC insulated, PVC sheathed armoured cable of 1.1 KV grade (Which is Interconnecting wiring for the fire alarm system with the AHU and the smoke dampers and AHU to Control Consol Panel |
| 401 | 8C x 1.5 Sqmm |
| 402 | 3C x 1 Sqmm |
| 403 | 2C x 1 Sqmm |
| 404 | (Make: As per approved make list attached) |
| 405 | Supply, Laying, testing and commissioning of FRLS XLPE armoured cables for Electrical Power and controls from MCC/LSCP/PDB to respective Equipments with earthing, clamped on surface or on cable trays, structural supports and cable supports provided. The scope includes End Termination of cables with Double Compression type Brass Cable Glands and Copper Lugs, clamping of cables by ready made G.I. spacers, saddles or clamps fabricated out of GI. strip 3 mm thick, treasing and Clamping of Cable on cable tray or surface, supply of all clamping materials and hardware etc., providing cable tags made out of aluminium/PVC laminated strip and 75x20 mm in size with cable number and size punched on it. Cable tags shall be tied to cables at every 20 meter interval and at both the ends. MS Powder Coated Junction Boxes with Bolted type terminals of suitabel size shall be provided near all Fan Motors for termination of armoured cables. |
| 406 | 4C x 6 Sqmm Copper Cable ( For Fire Exhaust Fans) |
| 407 | 4C x 1.5 Sqmm Copper Cable ( For Jet Fans ) |
| 408 | Supply & laying of XLPE armoured copper conductor twisted shielded control cables 3C X 1.5 Sq.mm twisted shielded cables for CO sensors. |
| 409 | (Make: As per approved make list attached) |
| 410 | Under Deck Insulation |
| 411 | Providing & Fixing Underdeck Insulation with 50 mm thick TF Quality EPS of Density 20 Kg/M3 fixed to slab with good quality Black CPRX Compound. 28Gwirenet shall be tightened arround insulation so as avoid any kind of sagging, Ends of net shall be overlapping at least 25mm. Overlaps shall be screwed with galvanized screws to avoid rusting : (Make: As per approved make list attached) |
| 412 | SENSORS AND FIELD DEVICES |
| 413 | Differential Pressure Transmitter for OT Positive Pressure control (15 Pascal set point) complete with wall mounted fixtures / two side Tubing complete having measurement accuracy up to 0.05% or better |
| 414 | SITC Of Duct type temperature & RH sensor with +-2% Accuracy |
| 415 | CABLES |
| 416 | Supplying, installing, testing and commissioning of 2 Core X 1.0 Sqmm Shielded Flexible Copper Cable (per I/O points hard wired to DDC). |
| 417 | Supplying, installing, testing and commissioning of 4 Core X 1.0 Sqmm Shielded Copper Cable (per Soft I/O points to DDC). |
| 418 | Supplying, installing, testing and commissioning of 2 Core X 1.5 Sqmm Shielded Flexible Copper Cable (per DDC to Integrator). |
| 419 | Supplying, installing, testing and commissioning of CAT -6 Cable (per DDC to Integrator). |
| 420 | DSR 2025 (E&M) Items |
| 421 | Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 422 | Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required |
| 423 | Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required. |
| 424 | Providing and fixing 6 SWG dia G.I. wire on surface or in recessfor loop earthing along with existing surface/ recessed conduit/submain wiring/ cable as required. |
| 425 | Providing and fixing earth bus of 50 mm X 5 mm copper strip on surface for connections etc. as required |
| 426 | Hot dipped Galavnised Iron Cable Tray |
| 427 | Supplying & installing following sizes of perforated Hot Dipped Galavanised Iron cable tray (Galavnisation thickness not less than 50 microns) with perfoaration more than 17.5 % in convenient sections, joined with connectors, suspended from ceiling with GI suspenderes including GI Bolts & nuts etc. as required (U Shaped Tray) |
| 428 | 450mm(W) x50 mm(D) and 2.0 mm Thickness |
| 429 | 300mm(W) x 50 mm(D) and 1.5 mm Thickness |
| 430 | 150mm(W) x 50 mm.(D) and 1.5 mm Thickness |
| 431 | Supplying & installing following sizes of perforated Hot Dipped Galavanised Iron cable tray\\"bends\\" (Galavnisation not less than 50 microns) with perfoaration not more than 17.5 % in convenient sections, joined with connectors, suspended from the ceiling with GI suspenders including GI Bolts & nuts etc. as required |
| 432 | 450mm(W) x50 mm(D) and 2.0 mm Thickness |
| 433 | 300mm(W) x 50 mm(D) and 1.5 mm Thickness |
| 434 | 50mm(W) x 50 mm.(H) and 1.5 mm Thickness |
| 435 | CHILLED WATER PIPING |
| 436 | Supplying, laying/ fixing, testing and commissioning of following nominal sizes of chilled water piping plumbing inside the building (with necessary clamps, vibration isolators and fittings but excluding valves, strainers, gauges etc.),cut to required length, and installed with welded joints (USE RECTIFIER AS SPECIFIED), duly insulated with fire retardant quality expanded polystrene moulded pipe section of density 20 kg/cu.m after a thick coat of cold setting adhesive (CPRX compound) wrapping with 500g polythene faced hessain and finally applying 0.63mm aluminium sheet cladding complete with type3, grade 1 roofing feltstrip(as per IS:1322 as amended up to date) at joints repairing of damage to building etc. as per specifications and as required complete in all respect. |
| 437 | Note:-The Pipes of sizes 150 mm & below shall be M.S. ‘C’ class as per IS : 1239 and pipes size above 150 mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35 mm thick M.S. Sheet for pipes upto 350 mm dia. and from minimum 7mm thick MS sheet for pipes of 400 mm dia and above.(Make: As per approved make list attached) |
| 438 | 200 MM Pipe DIA with 75 mm Thick Insulation |
| 439 | 150 MM Pipe DIA with 75 mm Thick Insulation |
| 440 | 125 MM Pipe DIA with 50 mm Thick Insulation |
| 441 | 100 MM Pipe DIA with 50 mm Thick Insulation |
| 442 | 80 MM Pipe DIA with 50 mm Thick Insulation |
| 443 | 65 MM Pipe DIA with 50 mm Thick Insulation |
| 444 | 50 MM Pipe DIA with 50 mm Thick Insulation |
| 445 | 40 MM Pipe DIA with 50 mm Thick Insulation |
| 446 | 32 MM Pipe DIA with 50 mm Thick Insulation |
| 447 | 25 MM Pipe DIA with 50 mm Thick Insulation |
| 448 | (Make: As per approved make list attached) |
| 449 | SITC of Insulated VALVES/CONTROLS - PN-16 including cost of MS Flanges as per the Table(Make: Advance, Sant, Zoloto) |
| 450 | Supplying, fixing, testing and commissioning of following valves, strainers, gauges in the chilled water plumbing duly insulated to the same specifications as the connected piping and adequately supported as per specifications. |
| 451 | BUTTERFLY VALVE (MANUAL) with C I body SS disc nitrile sheet & O - ring & PN 16 pressure rating for chilled water /hot water circulation as specified. |
| 452 | 200 MM DIA |
| 453 | 150 MM DIA |
| 454 | 125 MM DIA |
| 455 | 100 MM DIA |
| 456 | 80 MM DIA |
| 457 | 65 MM DIA |
| 458 | 50 MM DIA |
| 459 | BALANCING VALVE WITH BUILT IN MEASURING FACILITY with C I body flanged construction with EPDM coated disc with long pitch with protected out pipe insulation & PN 16 pressure rating for chilled / hot water circulation as specified. |
| 460 | 150 MM DIA |
| 461 | 125 MM DIA |
| 462 | 100 MM DIA |
| 463 | 80 MM DIA |
| 464 | 65 MM DIA |
| 465 | 50 MM DIA |
| 466 | NON - RETURN VALVE with duel plate of C I body SS plates vulcanized NBR seal flanged end & PN 16 pressure rating for chilled / hot water circulation including insulation as specified. |
| 467 | 150 MM DIA |
| 468 | 80 MM DIA |
| 469 | Y - STRAINER of Ductile CI Body flanged ends with stainless steel strainer for chilled / hot water circulation including insulation as specified. |
| 470 | 150 MM DIA |
| 471 | 80 MM DIA |
| 472 | 65 MM DIA |
| 473 | 50 MM DIA |
| 474 | Providing & Fixing in position the industrial type pressur gauges with gun metal/brass valves complete as required |
| 475 | (Make: As per approved make list attached) |
| 476 | Providing & Fixing in position the mercury in glass industrial type thermometers |
| 477 | (Make: As per approved make list attached) |
| 478 | CONDENSOR WATER PIPING |
| 479 | Supplying, fixing, testing and commissioning of condenser water pipes of following sizes of MS 'C' class along with necessary clamps, vibration isolators and fittings such as bends,tees etc.but excluding valves, strainers, gauges etc. adequately supported on rigid supports duly painted/buried in ground excavation and refilling etc. as per specification and as required complete in all respect. |
| 480 | Note:-i)The Pipes of sizes 150 mm & below shall be M.S. ‘C’ class as per IS : 1239 and pipes size above 150 mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35 mm thick M.S. Sheet for pipes upto 350 mm dia. and from minimum 7mm thick MS sheet for pipes of 400 mm dia and above. ii) For under ground pipe : The pipe will be covered by applying 2-4mm thick Tarfelt sheet with required Adhesive, Accessories etc |
| 481 | 250 MM DIA |
| 482 | 200 MM DIA |
| 483 | (Make: As per approved make list attached) |
| 484 | VALVES/CONTROLS - PN-16 without Insulation , Make :Advance, Sant, Zoloto |
| 485 | Supplying, fixing, testing and commissioning of following valves, gauges and strainers for condenser water circulation as per specifications. |
| 486 | BUTTERFLY VALVE (MANUAL) with C I body SS disc nitrile sheet & O - ring & PN 16 pressure rating as specified. |
| 487 | 200 MM DIA (Gear Box type) |
| 488 | NON - RETURN VALVE with duel plate of C I body SS plates vulcanized NBR seal flanged end & PN 16 pressure rating for chilled / hot water circulation as specified. |
| 489 | 200 MM DIA |
| 490 | Ducting |
| 491 | Supply, installation, balancing and commissioning of fabricated at site GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, Splitler dampers,vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required and shall also confirm to the BIS specifications. |
| 492 | Thickness 0.63 mm sheet |
| 493 | Thickness 0.80 mm sheet |
| 494 | Thickness 1.00 mm sheet |
| 495 | Supply, installation, balancing and commissioning of fabricated at site GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, Splitler ampers,vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required and shall also confirm to the BIS specifications. |
| 496 | Thickness 0.63 mm sheet |
| 497 | Thickness 0.80 mm sheet |
| 498 | Thickness 1.00 mm sheet |
| 499 | (Make: As per approved make list attached) |
| 500 | Grilles/Diffusers/Dampers |
| 501 | Supply, installation, testing and commissioning of GI volume control duct damper complete with neoprene rubber gaskets, nuts, bolts, screws linkages, flanges etc, as per specifications |
| 502 | Supplying & fixing of powder coated extruded aluminium Supply Air Grills(curved/Flat) with aluminium volume control dampers as per specifications |
| 503 | Supplying & fixing of powder coated extruded aluminium Return Air Grills with louvers but without volume control dampers complete as required |
| 504 | Supplying, fixing testing commissioning of supply air diffusers of powder coated aluminium with aluminium volume control dampers with anti smudge ring & removable core. |
| 505 | Supplying, fixing testing commissioning of Return air diffusers of powder coated aluminium without volume control dampers with anti smudge ring & removable core. |
| 506 | Supplying, Fixing,testing and commissioning of fire dampers in supply air duct/main branch and return air path as and where required of required sizes i/c control wiring,the damper shall be motorized and spring return so as to close the damper in the event of power failure automatically and open the same in case of power being restored. The spring return action shall be inbuilt mechanism and not externally mounted. The damper shall also be closed in the event of fire signal complete as required and as per specifications. |
| 507 | Fire damper |
| 508 | Actuator |
| 509 | Supplying Fixing accoustic lining on wall and ceiling of AHU Room with 50 mm thick,density 30kg/Cu.m resing bonded glass fiber insulation friction fixed in 610mmx610mm frame work made of 25x50x50x50x25mm made out of 0.6mm thick GI sheet U shaped Channel and covered with reinforced fiber glass tissue and finished with 0.8 perforated aluminium sheet etc.complte as required and as per specifications |
| 510 | (Make: As per approved make list attached) |
| 511 | BUILDING MANAGEMENT SYSTEM (BMS) |
| 512 | CENTRAL CONTROL SERVER |
| 513 | Supplying Installation Testing ommissioning of Central Control Server System comprising of Intel® Xeon® CPU E5-2640 x64 (or better) compatible with dual and quad core processors, Windows 11 (Professional, Enterprise, Ultimate, 64 bit), WindowsServer 2013 R2 (Standard, Enterprise, 64 bit) 16 GB or more, Video card and monitor capable of displaying at 1024 x 768 resolution or better, Latest Microsoft Licence Version Operating System Loaded with MS OFFICE 2019 Professional, Word, EXCEL, PowerPoint, Outlook Express, Microsoft Team official version lifetime licences suitable for running BMS software complete etc. as required. (DSR Item No.42.1) |
| 514 | PC System |
| 515 | Supplying Installation Testing Commissioning of Client PC System comprising of PC Hardware with inimum11th Gen Intel® I7 processor CPU E5-2640 x64 (or better), compatible with dual and quad core processors minimum 3.1 Ghz and 8GB or higher RAM, Hard Drive Space of 256 GB SSD or better, Video card and monitor capable of 1920 x 1080 pixel resolution or better with Ethernet adapter (10/100/1000 Mbps with RJ-45 connector) with 2 GB or higher Graphics card suitable for BMS System complete etc. as required. |
| 516 | Laser Jet printer |
| 517 | Supplying Installation Testing Commissioning of LaserJet printer having printing resolution 1200 x 1200 dpi, (dot/inch) or better, 21 to 30 ppm printing speed (LaserJet) complete etc. as required |
| 518 | LED Display |
| 519 | Supplying, Installation, Testing and Commissioning of following size LED display (LED monitor) industrial grade with 840x2160 resolution or better, USB playback, bluetooth and miracast connectivity, 4X HDMI 2.0, DP 1.2, HDR 10/10+, brightness: 500-nits or better, Video wall mode should be available,contrast ratio: 1200:1, OPS slot, viewing angle (H/V): 170°/ 170°, response time less than 12ms, Display control shall be on monitor screen and programmable with remote (remote shall be supplied with system), Key Board, Optical Mouse, etc. as required. |
| 520 | 32 inch or larger |
| 521 | Software for Building Management System :Supplying Installation Testing Commissioning of Necessary Software (UL listed) Packages containing Building Management with Capability of Collection, Storage, Processing and Controlling all the Data. Software shall support Open Standard Protocols like XML, BACnet, Modbus, Lon works etc. and without the use of Proprietary Protocols, with Enterprise Level Database Like MS SQL complete Lifetime Licenced & capable to collect, store & access all points from Fire Alarm Systems, IT Systems, Automation Systems, HVAC System, Lift, Energy management, Water Management System, etc. to create & monitor historical & event data, event management data, alarm management data & reporting data, Email Alerts for Critical alarms for all the systems. |
| 522 | The scope includes additional software required by BMS software (to enable a standard Web browser) to be resident on the DDC/client machine (manufacture-specific browsers shall not be acceptable). User log-on identification and password shall be required & a minimum three-layered security system(User interface Level, Application Level and Data Base Level) to be deployed for safety. The supplied computer software shall employ objectoriented technology (OOT) for representation of all data and control devices within the system |
| 523 | This data shall reside on a server for all database access (Systems requiring proprietary database and user interface programs shall not be acceptable). All components and controllers supplied under this contract shall be true “peer-to-peer” communicating devices (Components or controllers requiring “polling” by a Master / Global / Host to pass data shall NOT be acceptable). Physical connection of BACnet/MOD BUS devices shall be via Ethernet at all levels. The License must be provided by default. The BMS software shall be complete in all respect to cater the following different numbers of points managed in the installation. |
| 524 | For Upto 500 point included |
| 525 | Touchscreen Color portable operator terminal:Supplying Installation Testing ommissioning of following sizes Touchscreen Color portable operator terminal capable of connecting to one of the controllers on the communication bus and view parameters of the complete system. The terminal should be capable of viewing /changing parameters and trends, the specified parameters as per requirement etc. as required. |
| 526 | 7\\" Touch screen |
| 527 | DDC CONTROLLERS |
| 528 | Supplying Installation Testing Commissioning of IP Based DDC controller capable of fully “stand- alone” operation i.e. In the event of loss of communication with other DDC’s or Control Station, they shall be able to function on their own. The controllers shall consist of dual/quad core 32 bit microprocessors with EPROM based operating system on BACNET. The network Topology shall not allow single point failure. Each DDC on field level shall have embedded TCP/IP (10/100Mbps) connectivity so that it can be hooked into the Local Area Network (LAN) provided by the client or on dedicated network . Each DDC can be accessed from the Graphical User Interface (GUI) or from a standard Web browser (WBI) by connecting the server alongwith inbuilt web browser. All controllers shall accept 230V+/- 10%, 50Hz Uninterrupted power supply provided by end user. Controller shall support DHCP addressing over Local Area Network (LAN) so that the static IP requirements get reduced however a single static IP shall be provided for system so that it can be hosted on to internet in consultation with end user |
| 529 | The microprocessor based DDC’s shall be provided with power supply, analoge to Digital and Digital to analoge converters with memory and capacity to accommodate input/output (I/O) hardware points (with or without an expansion board). Each DDC should have own board and shall accept 0-10 V /4-20mA input signal having Minimum 20% spare capacity considered for expansion. Each DDC on field level should have minimum 128MB RAM & 64MB Flash memory. Following type of All controllers should be mandatorily BTL approved with B-BC profile complete etc. as required |
| 530 | DDC Controller-Type-I (Support upto 32 Points) Considering 4 /5nos AHU on one controller |
| 531 | DDC Controller-Type-II (Support upto 64 Points) Considering 1 nos AHU or other equipments on one controller |
| 532 | EXPNSION IO MODULE |
| 533 | Supplying Installation Testing ommissioning of following type of input output (IO) expansion module complete etc. as required. |
| 534 | I/O Module with 4 UIO channels |
| 535 | Enclosure for DDC |
| 536 | Supplying Installation Testing Commissioning of following sizes Powder coated wall mounted lockable and secure enclosure for DDC panel made of 16 SWG sheet steel IP -55 rated with proper internal mounting accessories for DDC such as DIN Rails, terminal block for cable terminations, well dressed for all internal cabling, ferruling, tagging etc. The DDC panels shall have power supply and connections for other peripheral equipment, switchgear protections, isolation transformer, earthing, relays, fuses, auxiliary power output socket & lamp etc. as required. |
| 537 | 600mmX600mmX200mm or suitable at Site |
| 538 | Integration Unit |
| 539 | Supplying Installation Testing Commissioning following type 3rd party Integration unit to provide the interface between Ethernet LAN and the 3rd party field control devices or any other devices which need to be integrated. These shall also provide supervisory capability of functions over the devices connected to it. The purpose of using these units should be limited to integrate the devices only. The Unit must have two onboard Ethernet port, minimum 2/3 on board RS485 ports. The Integration unit should have inbuilt 4GB memory for program storage. The Unit must communicate over TCP/IP with communication speed of 10/100MBPS. The Integration unit should be capable of handling multiple protocol simultaneously such as Bacnet, Modbus, SNMP restricted to single protocol. All integrators should be mandatorily BTL listed. The integration unit shall be housed in suitable size sheet steel enclosure made of 1.6mm thick CRCA sheet, lockable front door with glass, arrangement for cable entry and duly powder coated complete etc as required |
| 540 | Integrator for 500 Points |
| 541 | Field Devices |
| 542 | Supplying Installation Testing Commissioning of following Field Devices including connection etc. as required |
| 543 | Water Differential Pressure (DP) Switch for Pump Status |
| 544 | High/Low Level Switch for Tank Level Monitoring |
| 545 | Air DP Switch for Fan Run Status. |
| 546 | Duct CO2 Sensor, 0-2000ppm, 0-10V/4-20mA Output |
| 547 | Outside Temp & Humidity Sensor with radiation shield.Measuring Range: Temp:- -15 to 50 0C & RH 0-100%, Accuracy: +/- 1 0C +/- 3% |
| 548 | Immersion Temp Sensor for CHW line. Measuring range: -30 to 110 0C, Accuracy: +/- 1.3 0C |
| 549 | Water Pressure Sensor . Accuracy:+/-0.3% FSL |
| 550 | Duct type temperature sensor Measuring range: -30 to 110 0C, Accuracy: +/- 1.3 0C |
| 551 | Differential pressure switch for filters & Blower |
| 552 | Operation and Maintenance Charges |
| 553 | (Part B) Comprehensive Maintenance & Operation Charges (24hrsx7days) for first 2 years during defect liabilty period from the date of handing over the system |
| 554 | Operation & Comprehensive Maintenance charges for Central AC system including routine and preventive maintenance with parts including consumables such as gas, oil, filters and break down maintenance of high & low side of the air conditioning plant comprising of all the machinery Including deployment of 01 No AC Mech. cum Operator & 2 No Helpers in single shift of 8.0 hrs and 1 No helper as reliever or As per minimum requirement by Department for 24x7 in 3 shifts |
| 555 | 1st Year ( Operation + Free of cost Comprehensive maintenance with parts) |
| 556 | 2nd Year ( Operation + Free of cost Comprehensive maintenance with parts) |
| 557 | (Part C) Comprehensive Maintenance & Operation Charges (24hrsx7days) for 3 Years After completing first 2 years defect liabilty period |
| 558 | Operation & Comprehensive Maintenance charges for Central AC system including (routine and preventive maintenance with parts , consumables such as gas, oil, filters) break down maintenance of high & low side of the air conditioning plant comprising of all the machinery during THREE years. Including deployment of 01 No AC Mech. cum Operator and 1 No Operator as reliever & 2 No Helpers in single shift of 8.0 hrs . |
| 559 | 3rd year (Operation Cost +1.5 % of the capital cost for Comprehensive maintenance with parts) |
| 560 | 4th year (Operation Increase 10% + 5% increase i.e 1.575 % of the capital cost for Comprehensive maintenance with parts ) |
| 561 | 5th year (Operation Increase 10% +5 % increase i.e.1.65375 % of the capital cost for Comprehensive maintenance with parts ) Please Enable Macros to View BoQ information |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |
Copyright © 2026 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail