| 1 | Excavation in Soil (any type) using Hydraulic Excavator CK 90 with hydraulic excavator of 0.9 cum bucket capacity including cutting, trimming bottom and side slopes, in accordance with requirements of lines, grades and cross sections,including all lifts and combined lead upto 30m.Earth filling under floors with surplus ordinary soil or soil containing gravel or kankar upto 40% excavated from outside the building plinth in 15 cm layers including ramming, watering and consolidating lead upto 30 metres |
| 2 | Providing and applying Anti Termite Treatment using pre constructional chemical treatment measures as per IS - 6313 - 2001 ( Part 2 ) & using Chemical containg chloropyrifos systemic insecticide diluted to manufacturer's specifications (i) In foundation pits, by treating the bottom & sides upto height of 300mm by uniformly spraying solution @ 5 Litre / Sqm (ii) In the refill earth on both sides of all built up walls @7.5 Litre / Running meter ( width - 300 mm, depth- 450 mm ) (iii) Before laying the floor, by uniformly sprinkling the top surface of the consolidated earth within the outer perimeter @ 5 Litre solution per Sqm. |
| 3 | Cement Concrete 1:4:8 with stone ballast of size. Using concrete mixer volumetric type. |
| 4 | Shuttering for faces of concrete foundations and foundation beam & plinth beam (vertical or battering) |
| 5 | Centering and shuttering for columns (Square or rectangular or poly gonal in plain) |
| 6 | Centering and shuttering for faces of walls, partitions, retaining walls and the like (vertical or battering including attached pilasters buttresses etc. |
| 7 | First class burnt brick work laid in cement sand mortar 1:6 in foundation and plinth. |
| 8 | Reinforced cement concrete M-25 mechanically batch mixed using batch type concrete mixer as per IS:1791 and vibrated by needle vibrator but excluding steel reinforcement centring and shuttering in foundation and plinth |
| 9 | Damp proof course 4 cm thick of cement concrete 1 : 2 : 4 with 2 coats of bitument 20/30 penetration at 1.65 kg per Sqm. laid hot and sanded. |
| 10 | Centering and shuttering for sides and soffits of beam, beams, launching girders, bressumers, lintels. |
| 11 | Centring and shuttering for stair cases with sloping with soffits including risers and stringers. |
| 12 | Centering and shuttering for flat surfaces such as suspended floors, roofs, landings, chajjas, shelves etc. |
| 13 | Extra rate for shuttering in each subsequent storey above the first. Storey work done in subsequent storey above the first storey up to height of 4 metres or part thereof up to the roof top level of that storey- First Floor |
| 14 | Extra rate for shuttering in each subsequent storey above the first. Storey work done in subsequent storey above the first storey up to height of 4 metres or part thereof up to the roof top level of that storey- Second Floor |
| 15 | First class burnt brick work laid in cement sand mortar 1:6 in first storey upto 4 metres above plinth level. |
| 16 | Extra for work done in additional storey upto 4 metre above the top of structural roof of lower storey for Brick Work/ Concrete Block/ Clay Block- For first floor |
| 17 | Extra for work done in additional storey upto 4 metre above the top of structural roof of lower storey for Brick Work/ Concrete Block/ Clay Block- For Second floor |
| 18 | Extra for work done in additional storey upto 4 metre above the top of structural roof of lower storey for Brick Work/ Concrete Block/ Clay Block- For Third floor |
| 19 | 115 mm thick brick wall with every fourth course reinforced with hoop iron laid in 1 :4 cement sand mortar in super structure. |
| 20 | Extra for 115mm/100mm thick walls for additional storey upto 4 meters above the top of structural roof of lower storey for Brick Work/ Concrete Block/ Clay Block-For first floor |
| 21 | Reinforced cement concrete M-25 mechanically batch mixed using batch type concrete mixer as per IS:1791 and vibrated by needle vibrator but excluding steel reinforcement centring and shuttering in superstructure |
| 22 | Cement Concrete 1:3:6 with 40 mm guage stone ballast of size using cocrete mixer volumetric type |
| 23 | Reinforced cement concrete M-20 mechanically batch mixed using batch type concrete mixer as per IS:1791 and vibrated by needle vibrator but excluding steel reinforcement centring and shuttering in foundation and plinth. |
| 24 | Extra for R.C.C/PCC. work done in each subsequent storey above the first storey up to height of 4 metres or part thereof up to the roof top level of that storey-For First floor |
| 25 | Extra for R.C.C/PCC. work done in each subsequent storey above the first storey up to height of 4 metres or part thereof up to the roof top level of that storey-For Second floor |
| 26 | Extra for using computerised concrete batch mixing plant including carriage by transit mixer within 1 km lead (note: where concrete mixer is already included in the rate the same shall be deducted ) |
| 27 | Extra for pumping charges of Batch Mix Concrete / Ready mix conrete work (RMC) |
| 28 | Extra rate for enhancement in pumping power, addition of pipe length, scaffolding for handling the pipe arrangement for pumping of concrete in subsequent storey above the below storey up to height of 4 meters or part there of up to the roof top level of that storey- First floor |
| 29 | Extra rate for enhancement in pumping power, addition of pipe length, scaffolding for handling the pipe arrangement for pumping of concrete in subsequent storey above the below storey up to height of 4 meters or part there of up to the roof top level of that storey- Second floor |
| 30 | Cold twisted detormed (Ribbed/ Tor steel) Bars (Fe 500 grade as per IS 1786-2008) , for R.C.0 works, where not including in the complete rate of RCC including bending and binding placing in position complete |
| 31 | Extra for work done in each subsequent storey above the first storey for item No. 18.17, 18.18, 18.19-For first floor |
| 32 | Extra for work done in each subsequent storey above the first storey for item No. 18.17, 18.18, 18.19-For Second floor |
| 33 | Earth filling under floors with surplus ordinary soil or soil containing gravel or kankar upto 40% excavated from outside the building plinth in 15 cm layers including ramming, watering and consolidating leadupto 30 metres |
| 34 | Earth filling under floors with surplus ordinary soil or soil containing gravel or kankar upto 40% excavated from outside the building plinth in 15 cm layers including ramming, watering and consolidating lead .upto 30 metres |
| 35 | Base course of floor consisting of 100mm thick cement cocrete 1:8:16 and 100mm sand or stone filling. |
| 36 | Screed of 50mm thick cement concrete 1:8:16 to be laid below the topping using mechanical mixer for mixing of material |
| 37 | 10mm thick Cement Plaster 1:4 |
| 38 | 12.5mm thick cement plaster 1:5. |
| 39 | 20 mm thick cement plaster 1:5 in two coats work. |
| 40 | Extra for Plastering in each subsequent storey above the first storey upto 4 metre above plinth level-First floor |
| 41 | Extra for Plastering in each subsequent storey above the first storey upto 4 metre above plinth level-Second floor |
| 42 | Extra for Plastering in each subsequent storey above the first storey upto 4 metre above plinth level-Third floor |
| 43 | Supplying and fixing of Japani sheet frames (Chowkat) consisting of 18 gauge (1.25mm) thick steel sheet of the specified section (standard design latest), including iron lugs (hold fasts) iron hinges conforming to PWD specifications including bolts for fixing steps, lock notch provision for receiving tower bolts and finished, fixed in position including the cost of cement concrete 1:3:6 for filling in the frame and cement concrete 1:2:4 for lugs complete to the satisfaction of Engineer-in-charge. |
| 44 | Door and window frame of size 113mmx60mmx with 35mm wide single rebate |
| 45 | Supplying and fixing of Japani sheet frames (Chowkat) consisting of 18 gauge (1.25mm) thick steel sheet of the specified section (standard design latest), including iron lugs (hold fasts) iron hinges conforming to PWD specifications including bolts for fixing steps, lock notch provision for receiving tower bolts and finished, fixed in position including the cost of cement concrete 1:3:6 for filling in the frame and cement concrete 1:2:4 for lugs complete to the satisfaction of Engineer-in-charge. |
| 46 | Doors and windows frame of size 151mm x 60mm with 35 mm wide double rebate weighing 3.95 kg per meter. |
| 47 | Terracing consisting of tiles 22.86 cm x 11.43 cm x 3.81 cm laid over 25mm mud plaster, 75 mm mud filling on another layer of 25 mm mud plaster including two coats of bitumen laid hot @ 1.65 Kg. per Sqm. on top of R.C.C slab including grouting with cement sand mortar 1:4 and top surface to be left clear after wire brushing etc. |
| 48 | Extra for providing & fixing steel beeding of approved shape steel tube beeding size 12mm x 12mm, 18 gauge of approved shape and section with screw for fixing of glass panes instead of glazing clips and metal slash putty/ in steel doors, window & ventilators complete in all respects |
| 49 | Cement concrete 1:2:4 gola 10cm x 10cm concave quadrant along junction of roofs with parapet wall finished smooth, where specially specified. |
| 50 | Extra for every additonal storey for flooring-For First Floor |
| 51 | Extra for every additonal storey for flooring-For Second Floor |
| 52 | Top Khurra 0.6mx0.6m for rain water pipe in 25mm thick cement concrete 1:2:4 over 50.00 thick cement concrete 1:8:16 |
| 53 | Bottom khurra on ground 1.2m 0.6m consisting of bricks on edge laid in cement mortar 1:3 over 7.5 cm cement concret 1:8:16 including 12.5mm thick cement plaster 1:3 |
| 54 | Providing and fixing on wall face unplasticised Rigid PVC rain water pipes (working pressure 2.50 kgf / cm²) conforming to IS : 4985, including jointing with seal ring (i) Single socketed pipes. |
| 55 | U-PVC pipes (working pressure 2.5 kgf. / sqcm) Single socketed pipe 160 mm dia. |
| 56 | Providing and fixing 160 mm dia. U.P.V.C bend for Rain water pipe as per IS:14735 including jointing complete as per specifications and to the entire satisfaction of Engineer- in- charge. |
| 57 | UPVC 160 mm bend |
| 58 | Providing and fixing 160 mm dia. U.P.V.C Coupling/Sockete for Rain water pipe as per IS:14735 including jointing complete as per specifications and to the entire satisfaction of Engineer- in- charge. |
| 59 | UPVC 160 mm socket |
| 60 | Public Health Services |
| 61 | CONCEALED IN WALL: Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes as per IS 15778 (ISI marked with the prior approval of Engineer-in Charge), having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings i/c fixing the pipe with clamps at 1.00 m spacing including jointing of pipes & fittings, with one step CPVC solvent cement and testing of pipes complete as per direction of Engineer-in-Charge. |
| 62 | CPVC SDR 11 Pipe & fitting 20 mm o/d |
| 63 | SDR 11 CPVC pipes & fittings 25mm o/d |
| 64 | Cutting chase in brick walls in cement or in floor for embedding G.I.or C.I pipes line and making good the same to its original condition. |
| 65 | Size 75 mm x 75 mm |
| 66 | Providing & placing in position on terrace (at all floor levels) HDPE water storage tanks of approved make (to the approval of Engineer - in-charge) with cover with suitable locking arrangement and making necessary holes for inlet, outlet and over flo pipes but without fittings and base support for tank. |
| 67 | 1000 Ltr x4 nos. |
| 68 | Providing and fixing in position automatic brass ball valves in tanks. |
| 69 | 40 mm i/d Brass ball valve with plastic ball with G.I. socket |
| 70 | Sub head-2 Sewerage System |
| 71 | Providing and fixing in position singel socket SWR UPVC soil waste or antisyphonage pipes as per IS 13592 of E.D.C manufacture or of any other reputed firm including cutting, jointing, wastage, but excluding cost of jointing. |
| 72 | 110mm o/d single socket SWR UPVC pipe lines laid complete |
| 73 | Providingand fixing inpositionSWR UPVC special for soilwastevent or anti syphonage pipes as per as per IS- 14735 including cuttingandwastageetc.cuttinghoIesinwaIIs roofs or floors etc. andmaking good to its original conditionbut excluding cost of lead joining.For 110mm o/d pipes |
| 74 | For 110mm o/d pipes |
| 75 | Elbow 90 Degree (AII side socketed) bend 110 mm |
| 76 | Door Elbow 90 Degree (AII side socketed) door bend 110mm |
| 77 | Single Tee With Door |
| 78 | Single Tee |
| 79 | P Trap/Floor Trap 110mm x 110mm |
| 80 | Construction of brick masonry inspection chambers size as given below upto 0.60 metre average depth in 1:5 cement sand mortar, C.C.1:4:8 ( 150mm thick) in foundation, cement concrete 1:2:4 benching 12.50mm thick cement plaster 1:2 with a floatingcoat of 1mm thick of neat cement, R.C.C. 1:2:4 slabs 100 mm thick cement concrete topping 50mm thick with 455mm x 455mm, 455mm x 610mm inside R.C.C. inspection chamber cover and frame (Weight as per I.S.I specifications) painted with 3 coats of black bitumastic paint conforming to I.S.I complete as per standard design. 450mm x 600 mm inside with 455 mm x 610mm cover and frame light duty double sea |
| 81 | Providing and fixing in position gully traps fixed in cement concrete 1:4:8 complete with Grating 150mm x 150mm, cover and frame clear opening 300mm x 300mm and out of side size 330mm x 330mm and chamber including cost of all bricks work in cement morter 1:5 cement concrete 1:2:4 in coping around cover and frame etc. as per standard design minimum depth of |
| 82 | Electrical Services |
| 83 | RECESSED AIR CONDITIONER SUPPLY TERMINAL POINT (USED FOR HGW, PVC CONDUIT & HDPE PIPE WIRING SYSTEM WITH MODULAR ACCESSORIES): |
| 84 | Wiring air conditioner supply terminal point recessed in wall etc., complete with powder coated/anodized concealed metal boxes required for suitable number of modules (Modular accessories) for having 25Amp. combined/ universal Socket (shuttered) and modular motor starter 25Amp. (2Module), covered with Frame Plate and other petty material etc. including the cost of above material, cutting and filling up of chases (with finishing the surface):- |
| 85 | Wiring AC supply terminal point having 1No. 25Amp. universal Socket (shuttered) erected at AC height and 1No. Motor starter 25Amp. erected at switchboard height. |
| 86 | RECESSED COMPUTER SUPPLY TERMINAL POINTS (USED FOR HGW, PVC CONDUIT & HDPE PIPE WIRING SYSTEM WITH MODULAR ACCESSORIES): |
| 87 | Wiring Computer supply terminal points recessed in wall etc., complete with powder coated/anodized concealed metal boxes required for suitable number of modules (Modular accessories) for having 6Amp. 2/3 universal socket (shuttered), 16/20Amp. combined/ universal Socket (shuttered), 6/10/16/20Amp. Switches and blanking plate etc., and covered with Frame Plate and other petty material etc. including the cost of above material, cutting and filling up of chases (with finishing the surface):- |
| 88 | Wiring Computer terminal point having 3 Nos. 6Amp. 2/3 universal socket (shuttered), 1No. 16 Amp. switch with indicator and 1No. blanking plate (Modular accessories). |
| 89 | RECESSED TV, TELEPHONE & NETWORKING SOCKETS OUTLET POINTS (USED FOR HGW, PVC CONDUIT & HDPE PIPE WIRING SYSTEM WITH MODULAR ACCESSORIES): |
| 90 | RECESSED PVC CONDUIT PIPE WIRING SYSTEM WITH MODULAR SWITCHES: |
| 91 | Wiring in PVC insulated copper conductor single core FR cable (ISI marked) overall 1.5sq. mm, 1100volts grade to be laid in heavy gauge PVC conduit pipe 20mm/ 25mm dia. (ISI Marked) recessed in wall etc., complete with powder coated/anodized concealed metal boxes (1.6mm thick with Brass lugs) required for suitable number of modules (Modular accessories) for having Step type electronic fan regulators (two module) 100watts, bell push, 6Amp. 2/3 universal socket (shuttered), 16/20Amp. combined/ universal Socket (shuttered), 6/10Amp. Switches, 16/20Amp. switches with indicator etc. and covered with Frame Plate etc., PVC connector (For Fan Box and Call Bell), Steel Hooks, Sheet metal fan box (1.6mm thick shape hexagonal), Circular junction Boxes (Four way PVC 1½\\" deep for walls and CI 3\\" deep for ceiling), bonding to earth with PVC insulated copper conductor single core FR cable (ISI marked) 1sq. mm, 1100volts grade (For 6Amp. wall socket & plug control point) and other petty material etc., including the cost of above material, cutting and filling up of chases (with finishing the surface):- |
| 92 | Wiring fan point (With fan box) |
| 93 | Wiring light point |
| 94 | Wiring 6Amp. wall socket point |
| 95 | Wiring 6Amp. Plug control comprising wall socket point |
| 96 | Wiring 16/20Amp. power plug control point |
| 97 | PVC INSULATED FR COPPER CONDUCTOR CABLES: |
| 98 | Supply and erection of PVC insulated FR single core Unsheathed copper conductor cable (ISI marked) suitable upto 1100 volts grade confirm to IS:694/1990 left bare in pipe or casing of suitable size complete in all respect as desired by the Engineer-in-charge:- |
| 99 | Overall size 1 sq.mm (Un-sheathed) |
| 100 | Overall size 1.5sq.mm (Un-sheathed) |
| 101 | Overall size 2.5sq.mm (Un-sheathed) |
| 102 | Overall size 4sq.mm (Un-sheathed) |
| 103 | PVC, HDPE PIPES & PVC FLEXIBLE PIPES: |
| 104 | Supply & erection of PVC Conduit Pipes (ISI marked) as per IS9537:Part-III & HDPE pipes (ISI marked) as per IS:4984:1995 for wiring purposes including bends, junction boxes, Steel hooks, M.S. saddle clamps and other petty materials etc., as per PWD General Specifications:- |
| 105 | Heavy Gauge PVC Conduit Pipe 25mm dia. (On Surface) |
| 106 | Heavy Gauge PVC Conduit Pipe 25mm dia. (Flushed) |
| 107 | MINIATURE CIRCUIT BREAKERS/ RCBO's/ RCCB's: |
| 108 | MINIATURE CIRCUIT BREAKERS: |
| 109 | Supply and erection of Miniature Circuit Breaker MCB's for circuit protection against overload and short circuit current fault suitable for 240/ 415 volts 50cycles AC supply with breaking capacity of 10kA, Curve-C and low watt losses as per IS/IEC 60898-1, energy limitation class-3, true contact indication, label holder facility in the existing MCB distribution board as per PWD General Specifications including connections with suitable size of thimbles/lugs:- |
| 110 | MCB Single Pole 6-32amp. (10kA, Curve-C) |
| 111 | MCB Double Pole 6-32amp. (10kA, Curve-C) |
| 112 | SHEET METAL DOUBLE DOOR DISTRIBUTION BOARD FOR MCB's/ RCBO's/ RCCB's: |
| 113 | Supply and erection of sheet metal Double Door Distribution Boards IP 43-IK09 metal door (dust protected) as per IS 8623-1&3, IEC 61439-1&3 suitable for flush mounting with fully insulated copper busbars, shrouded neutral bars, earth bars, cement spill protector, color-coded interconnecting wire set, cable ties, blanking plates and circuit identifications label and of required no. of ways for mounting miniature circuit breakers/ RCBO's/ RCCB's in the distribution board (For SP&N distribution board with provision DP MCB's/ RCCB's/ RCBO's as incomer and SP MCB's as outgoings and for TP&N horizontal distribution board with provision TPN/ FP MCB's/ RCCB's/ RCBO's as incomer and SP MCB's as outgoings) as per PWD General specifications including connections with suitable size of thimbles and bonding to existing earth etc:- |
| 114 | SP&N Double Door Distribution Board 12 way each Please Enable Macros to View BoQ information |