| 1 | Wiring for light point/fan point/exhaust fan with 1.5 sq. mm FR PVC insulated copper conductor single core cable in existing surface/recessed medium class PVC conduit and earthing the point with 1.5 sq. mm FR PVC insulated copper conductor single core cable etc. as required of approved brand anchor, polycab, KEI etc. |
| 2 | Wiring for circuit/sub mains wiring along with earth wire of the following size of FR PVC insulated copper conductor single core cable in surface/recessed medium class PVC conduit as required.a) 2sq.mm +1x5 sq.mm earth wire.of approved brand anchor, polycab, KEI etc. |
| 3 | b) 2X4 sq.mm + 1x4 sq.mm earth wire. |
| 4 | c) 2 X 2.25 sq.mm + 1x2.5sq.mm earth wire. (Main panel to DB) |
| 5 | c) 2 X 16 sq.mm + 1x6 sq.mm earth wire. (Main panel to DB) |
| 6 | Supply installation/testing and commissioning of surface LED bulb of 15 Wt with complete accessories |
| 7 | SITC of Pre- wired concealed type LED down light 12 watts including connection with1.5mm FRPVC insulated coppper conductor single core cable and earthimg etc as required. |
| 8 | SITC of Pre- wired Focus LED/ flood light 30 watts including connection with1 1.5 mm FRPVC insulated coppper conductor single core cable and earthimg etc as required. |
| 9 | SITC of Pre- wired surface mounted LED outdoor light 20 watts including connection with1 1.5 mm FRPVC insulated coppper conductor single core cable and earthimg etc as required. |
| 10 | Supply installation/testing and commissioning of ceilling fan fan having sweep 40mm 3 blade with complete accessories with five star grade. Of approved brand havel,hair etc |
| 11 | Supply installation/testing and commissioning of wall mounted fan having sweep 40mm 3 blade with completeaccessories.(have Anchor). |
| 12 | providng and fxing of stepped type electronic fan regulator on the existing modular plate switch box including connection but xcluding modular plate etxc. As required. |
| 13 | S/F of exhaust fan shutter type of sweep 250mm in the existing opening, including making the hole to suit the above fan, making good the damage as required.(have, Anchor). |
| 14 | S/F following size/module, GI box along with modular base and cover plate for modular switches/sockets in recess etc. as required: a) b) 4 module (125mm x 75mm) |
| 15 | c) 6 module (200mm x 75mm) |
| 16 | d) 8 module (150mm x 150mm) |
| 17 | S/F following modular switch/socket on the existing modular plate and switch box including connection but excluding modular plate etc. as required. a) 6 amp switch |
| 18 | b) 16 amp switch. |
| 19 | c) 3 pin, 6 amp socket outlet |
| 20 | d) 6 pin, 16 amp socket outlet |
| 21 | e) Indicator lamp |
| 22 | S/F Double door MCB distribution boards, 240V/415V, Sheet steel, Powder coated DB’s suitable for MCB’s fitted with Bus Bar, Neutral link, Earth Bar and Din bar of following no. of ways :a) 16 Way (16 + 64), Double door TP&N |
| 23 | S/F of 5 Amps to 63 Amps, 240/415V, “B series, ISI Mark” miniature circuit breakers suitable for lighting and other loads of following poles in the existing MCB DB complete with connections, testing and commissioning etc as required: a) Single pole 6A, SP MCB |
| 24 | b) Single pole 16A, SP MCB |
| 25 | 4 pin MCB TPN 63Amps |
| 26 | 4pin MCB TPN 40amps |
| 27 | Supplying and fixing 5 amp to 63 amp 240 V,B series, ISI marked miniature circuit breakers suitable for lighting and other loads of poles in the existing MCB DB complete with connections, testing and commissioning etc. as required (100 A Changeover switch) 200A , 4P Changeover switch includingall accessories complete. |
| 28 | providing and fixing of following sixe of medium cass pvc conduit along with accesoreis in surface recess incudincutting the wall and making good the same in case of recessed conduit as required.25mm |
| 29 | (ii) 32mm |
| 30 | (iii) 40mm |
| 31 | Earthing with Cu. earth Plate 600mm x 600mm x 3.5 mm thick along with connection from the earth plate by a copper strip of size 2R x 25mmx5mm up to the earthing terminal in panel room including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 3.2 mtr. long etc. with charcoal or coke and salt of 2.8 Cum as required. Depth of earning must be 10 feet from the ground level. |
| 32 | Supplying and laying following size and specification of XLPE insulated PVC sheathed armored cable with aluminum conductor for working voltage 1100 V grade as per IS: 7908, including thimble/lugs, double compression glands etc.of respective size.3.5C x25 sq.mm Armoured Al. cable Please Enable Macros to View BoQ information |