| 1 | Taking down of existing false ceiling with fittings carefully for executing the control wiring and fixing of smoke/heat detector and after the completion refixing the same false ceiling with fittings complete all as specified and directed.Note : Any damages in existing false ceiling during the execution/refixing the disturbed surface shall make good by the contractor at his own cost. |
| 2 | Taking down of old U/S outdated fire alarm system including fire alarm panel,smoke detectors,RI,Hooter,wiring complete all as specified and directed. Note : (1) taking down of One control panel with connected detectors ,MCP,RI,Hooter, shall be measured as one job |
| 3 | Supply, install testing and commissioning of Analogue Addressable Microprocessor based Modular Expandable fire alarm control panel ,2 Loop with 99 detectors and 99 modules up to 200 detectors and modules with standard 80 character LCD display, three Access levels, minimum 2000 event historic logging, flash EPROM sufficient numbers of programmable relay controls for controlling the existing UPS/HVAC controller 440V AC power supply, automatic battery charger, 24 volts sealed lead acid batteries sufficient for 4 hours normal working and capable of operating the system for 1 hours during an emergency condition complete. The panel should be of web server based ,Ethernet port and surge protectection device should be inbuilt. The panel should have one nos of NAC external with sufficient power. The panel should be with CRCA enclosure of proper 16 gauge and hinged front door with lock & key. The panel should be EN-54 / No Hardware / software Dongle / Lincese required for operating the panel .Programming & modification if required the cost should be included on the same for Life time. Installation shall be done only by the OEM and a complete demonstration shall be given to the user/JE at the site after the successfull installation. A signed copy from the user after demonstration shall be obtained by the contractor. |
| 4 | Supply and fix the control relay module for UPS power/HVAC system and programming for automatic tripping of existing UPS/HVAC system any capacity during fire incidents complete all as specified and as directed.Note : (1) A complete demonstration shall be given to the user /JE at the site after the successful installation. |
| 5 | Supply and fix addressable type Manual Call point enclosed in the Press Type compatible with main fire alarm control board microprocessor based resettable as per IS-2189 and LED blinking alrm facility. complete all as specified and directed.Note:1. The call points shall be installed 1.4m above the floor level.2. The MCP shall be interlinked with the Fire Control panel.3. The MCP shall be fixed in the path of escape and essentially near the exit point.4. The MCP shall be capable to transmit signals to the control panel to effect the movement of fire crew.to tackle the situation. |
| 6 | Supply, install, test and commissioning intelligent type analog addressable sensor with micro processor based single unit smoke cum heat /Multi Detector complying with and type certified to EN 54 addressable type, microprocessor based, programable inteligent type, multisensor detector with heat and smoke combination with base working on ionisation priciple and photo electric type fixing on false ceilling or above false ceiling complete including necessary connection all as specified and directed. |
| 7 | Supply install testing and commissioning of wall mounted Addressable electronic sounder cum strobe/Siren electronic type with sound level 65 DB to 120 DB measured 1.5 mtr with sound output variation of +5 DB and 1000 mtr range ,EN 54 on 24V DC made of FR ABS Plastic all as specified and as directed. |
| 8 | Supply install test and commissioning of addressable response indicator metallic type with dual red colour LED indicator, Flus/ ceiling mounted, operating on 12 V DC complete all as specified and as directed. Please Enable Macros to View BoQ information |
| 9 | Supply install test and commissioning of addressable response indicator metallic type with dual red colour LED indicator, Flus/ ceiling mounted, operating on 12 V DC complete all as specified and as directed. Please Enable Macros to View BoQ information |