| 1 | `Supply Installation Testing and Commissioning of Micro processor based Fire Alarm Control Panel (FACP) with required 2 wire fault tolerant loop Cards (each loop should support 120 detector, 120 devices or 240 in any combination). The panel shall be able to give location of all fire/fault conditions of addressable units via the address codes. Further, the panel must be able to automatically switch ON /OFF respective control module when ever any alarm is triggered. Addresses of each Fire Alarm Detector/Module/Hooter /Manual Call Point etc., shall be legibly marked near/on respective sensors. It Should have provision for triggering/integrating the Gas Suppression System, PAVA System and Fire Fighters Telephone System.Panels should have provision of CPU Redudancy, and should work in degrade mode in case of CPU failure.• Up to 3000 soft zones, logic groups with (AND, OR, NAND, NOR functions) can be created, in network configuration upto 250 Panels. • FACP should support networking. • FACP should support programming through i) Touchscreen ii) USB port iii) TCP/IP Port. • Control-by-event (CBE) equations for activations with logical operators • Historical log : 1,00,000 events • Auto-programming with automatic recognition of the model of the devices • Decision algorithms for the alarm, pre-alarm and faults • Automatic day / night sensitivity change • Indication of the need to clean the smoke sensors • Programmable alarm threshold for detectors. • Zone wise Walk-Test function. • Onboard Repeater Circuit, should be able to connect upto 64 repeaters. • 7-inch Touch Screen, 800 x480 resolution • Inbuilt Modbus / BACnet Card for BMS Integration • The Panel Shall have provision to add Zones LED display with Individual Zone Indicators expdable upto 1280 LED Indicators and provision to add 640 individual Programmable buttons. • Relay Output: 1 fault (NO/NC): 1 alarm, 1 Supervisory/FPE, and 2 optional (Form C contact user defined). • Souder Output: 1 (monitored balanced with resistor or diode) • 1 Programmable NAC Output or 24V Selectable output Max 2.5 A (NAC plus AUX) • The panel shall have a built in power supply 100 ~ 240 V AC, 50 / 60 Hz and Battery charger which should maintenance free type from 12Ah to max 65Ah of 12 V each. • The supply and installation of the entire FACP system shall conform to EN54 Part-2 / NFPA 71 and 72 norms. All equipment and systems shall be tested and approved by LPCB/UL/FM confirming to IS2189 Standard. 2 loop expandable up to 6 loop panelMake:GST/ Honeywell/ Edward` |
| 2 | `SITC of Intelligent Addressable Photoelectric smoke Detector with 3600 LED, Electronically addressable complete with Mounting Base. The detector shall share the analog datapoints to the panel. The detector should have strong environmental adaptability by drift compensation with 2 programmable sensitivity levels. Operating Voltage shall be 16 to 28 Vdc. The detector shall operate in -10°C ~ 50°C Temperature and will give alarm in case of smoke detection. The Detector shall meet RoHS standard and shall confirm to IS2189 Standards and Duly Approved by LPCB/UL/FM with relevant IS/EN/NFPA Standard. (Detectors without inbuilt isolators may be considered with an additional isolator module after 20 devices)Make:GST/ Honeywell/ Edward` |
| 3 | `SITC of Intelligent Intelligent Addressable Type Manual Call Point having Surface or flush mounting option with Electronically Addressable type. Operating voltage 16 to 28 Vdc and shall complete with Back Box for Mounting Complete as required conforming to IS2189 Standards and Duly Approved by LPCB/UL/FM/relevant NFPA/EN Standard required to complete the job in all respect up to the entire satisfaction of Engineer – in Charge of work.Make:GST/ Honeywell / Edward` |
| 4 | `SITC of approved make Addressable Loop Powered Sounders cum Strobes or Sounder Strobe with Control Module and Power Supply with all accessories. Device should be Electronically Addressable type and should support 16 type programmable alarm tones with option to switch off light/sound for special applications.Operating voltage shall be 20 to 28 Vdc. Sound output of 86 dB @ 1m with High output Light technology and superior lens design optimize light outputs conforming to IS2189 Standards and device shall be compatible with the detector base and Duly Approved by LPCB/UL/FM/relevant NFPA/EN Standard Make:GST/Honeywell /Edward` |
| 5 | `Supply Installation Testing and Commissioning of minimum 1000 Mtr. Range Siren generator provided at the roof of the building with separate power suppl, relay etc..Make: National/Kheraj/` |
| 6 | Supply Installation, Testing and Commissioning of Glow Type Exit Sign Board photo luminescent of size 300 mm x 250 mm x 1.5 mm rigid sheet signage containing Zink Sulphate as bare chemical class - I material PSPA fixed on 3 mm acrylic sheet on both side showing marking (running man, Arrow and Exit) and hanged with the ceiling with chain and fastener Managed Type including cost of labour and material required to complete the job in all respect. Make Omex/ Savmax/Fyrmax/Firesec |
| 7 | `Supply Installation Testing and Commissioning of Wall Mount/Ceiling Speaker with operation 6 Watts to complete the job in all respect up to the entire satisfaction of Engineer-in-Charge of work.Make: EON AV / Honeywell / Edward /GST` |
| 8 | Supply, installation, testing and commissioning of Addressable Control Relay Module with flexible network structures with a maximum switching current of 1A @ 30V DC. Shall be EN54/UL/VDS Certification Makes: G.S.T /Honeywell/Edwards. |
| 9 | `SITC of UL/EN54/LPCB listed and FM. Approved Line isolating for isolation the section of circuit in case of short in the addressableLoop wiring Makes: GST / Honeywell/Edwards |
| 10 | Supply, installation, testing and commissioning of Addressable Monitor Module for monitoring of a line with EOL resistor/ Potential free contact/voltage monitoring shall be EN54/UL/VDS approved. (In case of 2 monitoring features in one module (points) each point shall be considered separately for payment). Makes: G.S.T /Honeywell/EDWARDS. |
| 11 | `SITC` of addressable heat detector with fixed and rate of raise feature including mounting base with LED etc. complete as required. Each Detector should have 2 as per NFPA 72 style 7 wiring requirements (one for incoming and one for outgoing line) for maintaining operational availability of all elements in the loop in the event of a short circuit and to meet style 7 requirements. High resistance to electromagnetic effects in accordance with EFSG agreement EFSG/F/97/005. Detector should monitor Electromagnetic interference and report to the panel - current and average values. EMC safety for detector shall be 50 V/m. Shall be EN54/VDs/UL certification. (Detectors without inbuilt isolators may be considered with an additional isolator Module after 20 detector in the loop. detector) Make: GST/ Honeywell/Edwards |
| 12 | Wiring for Fire Alarm system with the following sizes 2 x 1.5 sq.mm of FRLS insulated copper conductor 1100 volts grade cables in existing surface/recessed M.S. conduit etc. as complete as required. Make Finolex/Havells/Polycab/Plaza. |
| 13 | SITC of Public Address System complete with 240 Watt Amplifire, interface unit with main Fire alarm Panel Make: EON AV / Honeywell/ Ahuja/GST Please Enable Macros to View BoQ information |