| 1 | Capacity (in kVA / kW)40 kVA/ 40 kW 3-Phase Input / 3-Phase OutputTechnology and Capability:a) True Online configuration with double conversion UPS b) DSP based technology with reduction in electronic components.c) Fully rated power (kVA=kW) for maximum power availability.d) Possibility of enhancing UPS capacity / redundancy by operating UPS in N+X Parallel Redundant Configuration(PRS).e) Capability of Independent or Common battery bank operation of the UPS when operated in PRS.f) UPS should be designed at Rated PF of 1 i.e. 40kVA / 40kW UPS rating.g) UPS shold have IGBT topology for both PFC (power factor correction), Rectifier and inverter.h) Should have Dual Aux power design. |
| 2 | Model Name & Number: |
| 3 | 40 kVA / 40 Kw::Make / Model / Part No to be specified by the vendor |
| 4 | Input |
| 5 | Input facility -Phases / Wires |
| 6 | Input Voltage Range:220/380V,230/400V,240/415V (3Φ4W)Range (Full Load) 173~276 / 300~477VACRange (Derating to 70% Load) 132~173 / 228~300VAC |
| 7 | Nominal Input Frequency :50/60Hz (Auto-Selectable) |
| 8 | Input Frequency Range:45 to 65 Hz |
| 9 | Input Power Factor:> 0.99 (Full Load) |
| 10 | Current Harmonic Distortion(ITHD):< 3% |
| 11 | Generator Compatibility:Compatibility to genset supply required |
| 12 | Input Protection (Thru In-built 1P MCB):Should be provided at the input of the UPS suitable for the full rated capacity of the UPS |
| 13 | Output |
| 14 | Nominal Output voltage:220/380V,230/400V,240/415V (3Φ4W) |
| 15 | Output Voltage Regulation:± 1 % |
| 16 | Nominal Output Frequency:50/60 Hz |
| 17 | Output Frequency Regulation:± 0.05Hz |
| 18 | Output Frequency Slew Rate:<1Hz/sec |
| 19 | Output Wave Form:Pure sine wave |
| 20 | Output Voltage Distortion (THDu):< 1.5 % (linear load) |
| 21 | Crest Factor:'3:1 |
| 22 | Output Short circuit Protection:Electronic Protection |
| 23 | Transient Response / Recovery |
| 24 | Transient Response: Dynamic Regulation for 10% to 90% step linear load:'±7% |
| 25 | Transient Recovery to steady state condition after 10% to 90% step linear load:< 1 cycle |
| 26 | Transfer Time |
| 27 | Transfer Time (Mode of operation):Zero ms from Mains mode to Battery ModeZero ms from Battery Mode to Mains mode |
| 28 | Transfer Time (Inverter to Bypass / Bypass to Inverter):<1ms (Synchronized Mode) |
| 29 | Automatic & Bi-directional static by-pass (In-built):Bypass To Inverter ±10 % (Rated Voltage)Inverter To Bypass ±7 % (Rated Voltage) |
| 30 | Maintenance Bypass:1.UPS should have option for manual maintenance bypass2. Maintance bypass cover removal sensing. 3.The maintenance bypass should provide for Hot-swap of the faulty UPS PWB for repairs / service. |
| 31 | Efficiency (At Nominal Voltage & Resistive Load up to kW rating of UPS): |
| 32 | Overall Efficiency (AC to AC) - Online (Double Conversion). |
| 33 | Overall Efficiency (AC to AC) - ECO Mode (Bypass feeding the load under normal conditions):96% |
| 34 | Overload |
| 35 | Inverter Overload capacity :≤105 %: continuous,106% ~ ≤125%: 10 minutes; 126% ~ ≤150%: 1 minute; >150%: 1 second |
| 36 | Display Panel (In-build LC Display & LED ) |
| 37 | Measurements (On LCD):Input: Voltage / Frequency,Bypass: Voltage / Frequency,Output: Voltage / frequency,Battery: Remaining time / Battery Level Indicator,Load: Percentage / Load Level Indicator,Battery Voltage Capacity/Status/Test Result,System Date/Time Setting,Current Time,PFC Fuse Open,Battery Temperature Too High,Battery Over Charge,Battery Out of Date,INV Short Circuit,Output Breaker Off,kVA,kW,output current,Battery current. |
| 38 | Fault Indication (On LCD):Main Input Sequence Fault,Power Module General Fault,Battery Ground Fault,Bypass Static Switch Fault,Parallel Fault,System General Fault,Provide Bypass O/P Even If UPS Fault. |
| 39 | Indications (LED):Normal-Green/Battery-Orange/Bypass-Green/Fault-Red |
| 40 | Alarms |
| 41 | Audible Alarms:Battery Low beep / DC Fault beep/ UPS Overload beep/ o/p short ckt fault beep/ Shutdown beep |
| 42 | Battery Backup / Battery Bank & Charger |
| 43 | Backup Required:30 minutes 31200VAH |
| 44 | Battery Bank Voltage:Flexible 384 VDC to 600VDC |
| 45 | Battery Bank VAh :Minimum 31200 VAH |
| 46 | Batteries Type:Sealed Maintenance Free (SMF) - 12V Cells |
| 47 | Battery Makes:Amara Raja / Exide / Rocket. |
| 48 | Number of Battery Banks:Maximum Two Banks in parallel |
| 49 | Minimum Charger Rating (Including internal / external):The charger should be able to deliver charging current equivilanet to 10% of Battery Ah rating offered.(In case of external chergers, suitable monitoring of the chargers should be provided in the UPS. Also all external chargers taking AC input must have PFC - Power factor correction) |
| 50 | Charger type / Charging Method & Charging Voltages:Constant Voltage Constant Current Solid state SMPS charger Float Charge 270V±(2V)Boost Charge 280V±(2%V) |
| 51 | Battery recharge time (After complete discharge) to 90% capacity:10-12 hours |
| 52 | Battery Housing (Vendor to provide the GA drawings of the offered Battery Rack):Should be compact and space saving MS steel open racks complete with interconnectors : |
| 53 | Battery End Cell Voltage:1.75 V/cell: |
| 54 | Interfaces |
| 55 | Serial Communication RS232 Port (Option of USB Port should be available):RS2323 Port should be provided as standard in the UPS. However there should be provision for USB port also in the UPS. |
| 56 | REPO(Remote Emergency Power OFF) / ROO(Remote ON - OFF) Port:Provide both onsite & remote EPO to shutdown UPS whenemergency situation happens.REPO Port with a user-supplied switch |
| 57 | Interface to NMS (Network Management System) - To be quoted as option:SNMP (IPV6) Card for connecting the UPS to LAN thru Ethernet port & monitoring thru NMS should be available (The cost of SNMP Card / NMS software to be quoted separately) |
| 58 | Interface to BMS (Building Management System) - To be quoted as option |
| 59 | Interface to DCS (Distributed Control System) - To be quoted as option :Relay I/O Card or PFC (Potential free contacts) for connecting to UPS to DCS / PLC / SCADA system for communicating UPS operating status |
| 60 | UPS status information presented as 3 contact closures:UPS should have configurable input signal as shutdown UPS or battery test dry contact. |
| 61 | Restart / Testing Capability |
| 62 | Cold Start:UPS should start up On AC Supply (Mains) without DC Supply (Batteries)On DC Supply (Batteries) without AC Supply (Mains) |
| 63 | Automatic Restart:UPS should start up automatically on mains resumption after battery low shutdown |
| 64 | Self Diagnosis:UPS should be capable to carry out self test of Rectifier / Charger /Battery & Inverter module during start-up |
| 65 | Physical |
| 66 | Operating Temperature:0℃ ~ 40℃ |
| 67 | Storage Temperature:-20℃ ~ 40℃ |
| 68 | Operating Humidity:< 95% |
| 69 | Operating Altitude:0 to 3000m(0 To 10000ft) |
| 70 | Forced Air: |
| 71 | Noise Level:< 55dBA at 1 Meter |
| 72 | Air Filters:UPS should have internal anticorrosion air filters for dust filtration (Optional) |
| 73 | Dimension (w x d x h) in mm:To be furnished by the vendor |
| 74 | Weight - in kg:To be furnished by the vendor |
| 75 | Reliability:MTBF greater than 100000 hours |
| 76 | Packaging Material / Vibration Withstand & Drop Test:Recyclable (No CFC) &1. Vibration testing as per ISTA -1G Non-operational with Packing |
| 77 | Standard Package of UPS to include the following minimum accessories:1.SMART Slot2.MINI Slot3.Parallel Port4.RS232 Port5.REPO Port6.Charger Detection Port7.Input Dry Contact8.Output Dry Contact 9.USB Port |
| 78 | Parallel Configuration:UPS should have capabilty for parallel 4 units. |
| 79 | DC bus Capacitor:UPS DC bus capacitor have minimum life of 5 years@40°ambient. |
| 80 | Certifications |
| 81 | Manufacturer Certifications:QMS: As per ISO 9001: 2008EMS: As per ISO 14001: 2004OSHAS: As per ISO 18001: 2007 TL 9000 |
| 82 | Product Safety Certifications (Mandatory):ESD:IEC61000-4-2: level4RS : IEC61000-4-3: level3EFT: IEC61000-4-4:level4SURGE: IEC61000-4-5:level4CS: IEC61000-4-6: level3IEC 61000-2-2EN 62040-2EN 61000-3-2 |
| 83 | ROHS compliance:UPS should be ROHS compliance |
| 84 | MAKE PREFERENCE - UPS VERTIV/ DELTA / APC-SCHNIEDER |
| 85 | MAKE PREFERENCE - SMF BATTERIES:EXIDE / AMRON -QUANTA / LEOCH |
| 86 | Supply & laying of 3 core Multistrand 2.5 sq mm annealed copper conductor speaker cable in existing pipe / channel I/C connection etc. Approved Makes :Finolex/Polycab/Havells |
| 87 | Supply Installation Testing & Commissioning of PVC pipe32mm dia ISI marked ( Medium ) recessed in wall / ceiling etc. including the cost of PVC bends , inspection boxes , iron hooks and cement concrete etc. complete in all respect upto the entire satisfaction of Engineer-in-charge of work Make: Diplast /Polyplast/polycab |
| 88 | Fabrication, Installation, Testing and Commissioning of floor mounting compartmentallised cubical panel board with locking arrangement front openable, totally enclosed, dust & vermin proof fabricated out of 2mm thick cold rolled carbon annealed, sheet steel, with 200 Amp 4 strip Al. bus bar, cable alley on one side, powder coated paint of approved shade and earthing copper strips complete with following incoming and outgoing switchgears including making connections/ inter connections with lugs/ thimble for switchgears and control wiring with 2.5 sq.mm PVC insulated FRLS copper conductor cable, including Angle baser upto 100 mm above ground level including necessary grouting / fixing on floor ,( MCCB's Ics=100 %=Icu & all MCCB's shall have spreader link & rotory handle). |
| 89 | MAIN Incomer and Outgoing to UPS: |
| 90 | 160 Amp. 25 KA breaking capacity TPMCCB with Thermal Magnetic Release - 01 Nos. |
| 91 | LED type phase indicating - (R, Y & B) Lamps with backup protection 6 A SP MCBs- 3 Nos |
| 92 | Digital Multifuctional meter (VAF+PF )-01 No. |
| 93 | Incomimg From UPS : |
| 94 | 160 Amp. 25 KA breaking capacity TPMCCB with Thermal Magnetic Release - 01 Nos. |
| 95 | Busbar: |
| 96 | Four Strip aluminium bus bars of minimum of 300 Amps capacity with heat shrinkable coloured sleeves and including DMC/SMC bus bars supports at required intervals complete for cross section,size support& their spacing etc. for with standing fault level of 31 MVA for one second - 01 Set. |
| 97 | Outgoing: |
| 98 | 100 Amp. MCB TPN - 03nos. |
| 99 | 63Amp MCB DP - 6nos. Please Enable Macros to View BoQ information |