Tender For Work Of Providing And Fixing Of Smoke Detection And Fire Alarm System For Prevention Of Fire Hezards At 132 Kv S/S Anand Nagar Under Etd-Ii, Gorakhpur
Name of Work:- WORK OF PROVIDING AND FIXING OF SMOKE DETECTION AND FIRE ALARM SYSTEM FOR PREVENTION OF FIRE HEZARDS AT 132 KV S/S ANAND NAGAR UNDER ETD-II, GORAKHPUR
Sl. No.
Item Description
1
Supply of 08-12 Zone Conventional fire detection and fire alarm system with power supply arrangement . (Make compatible with IS : 2189:1999 tested by ERTL (N) and System Sensor (Agni Suraksha \ Agni Devices \ Daksh OR equivalent ) .
2
Supply Manual Call Point A breakable glass cover fixed in such a way that the actuating push button is kept depressed as long as the glass is intact and released when the glass is broken . A small steel hammer shall be attached to the assembly with a steel chain to facilitate breaking of glass . The manual call points shall be suitable for surface or fully \ partly recessed mounting . 5 mm high red painting / printed word \\" IN CASE OF FIRE BREAK GLASS \\" shall be provided on the front face . The manual call point shall be compatible with all conventional control panels . (Make Agni Suraksha (ASES) \ Safeway Equivalent Agni Devices) .
3
Electronic hooter 11 dB/24V DC with strobe (ABS-V) The enclosure should be 1.5mm thickness duly painted and marked \\"FIRE ALARM \\" . All hooters shall produce a similar sound and shall maintain the same during their operation . (Make Agni Suraksha (AESE)\Safeway Equivalent \ Agni Devices) .
4
Providing and Fixing of Lonisation type smoke detectors . The detector while sensitive to all type of smokes will be insensitive to ambient lights , air drafts and changes within the operating temperature and voltage ranges . The Detector shall meet the requirements of either EN 54\FM\UL or LPC and shall be specifically approved by FM\UL\LPCB. Apollo\System Sensor\Edward\Bosch .
5
Providing and Fixing of Optical smoke detectors . The detector while sensitive to all type of smokes will be insensitive to ambient lights , air drafts and changes within the operating temperature and voltage ranges . Specially to be installed in cable gallery . The Detector shall meet the requirements of either EN 54\FM\UL or LPC and shall be specifically approved by FM\UL\LPCB. Apollo\System Sensor\Edward\Bosch .
6
Providing and Fixing of Heat detectors . (for the area like battery room , AC plant area , DG room , etc) It is a combination of rate of rise and fixed temperature principle using thermistor and with automatic compensation for changes of ambient conditions . The thermal detectors are tested and approved to EN54 part 5 (2000) Class A1R. Apollo\System Sensor\Edward\Bosch\ Agni Suraksha .
7
Providing and Fixing of response Indicator Lamp assembly consisting of Lamp holder and Lamp shall be suitable for mounting on walls , partition etc. The housing shall be suitable for surface / flush mounting of 1.5 mm thick sheet steel and the facia 3 mm acrylic mounted out side a cabin and directaly connected to the detector inside the cabin, In normal circumstances the lamp should fliker but in the event the detector inside the cabin sanses a fire , the lamp should glow.
8
Supply and laying 2x1.5 Sq. mm PVC insulated and sheathed stranded copper wire . Wiring for Fire Alarm system in General shall comply with IS: 2189 and IS: 732 amended up to date. The detector shall be wired by ISI marked 1.5 sq. mm PVC insulated stranded FRLS copper conductor wire of 110 volts grade as required and desired on site. Crimping type of lugs are also included in the rates of laying wires and its connections. PVC insulated copper conductor wires shall confirm to IS: 694 and PVC insulated copper conductor armoured cables should confirm to IS: 1554 (Part-I) make National/ Plaza/ Kalinga or any other standard make.
9
Supply and laying 4x1.5 Sq. mm PVC insulated and sheathed steanded copper wire . Wiring for Fire Alarm system in General shall comply with IS: 2189 and IS: 732 amended up to date. The detector shall be wired by ISI marked 1.5 sq. mm PVC insulated stranded FRLS copper conductor wire of 1100 volts grade as required and desired on site. Crimping type of lugs are also included in the rates of laying wires and its connections. make National/ Plaza/ Kalinga or any other standard make.
10
Supply and installation of SMF Batteries with suitable rating as required for 24 hours backup from Exide / Standard/ Amco/ Nos. Prestolite/ any other atandard make.
11
Signage with backlit facility for control building marking for various Fire/ emergency exit points.
12
Supply and laying of MS/PVC Conduit pipe 25 mm as per requirement of site. Please Enable Macros to View BoQ information