| 1 | ESTIMATION |
| 2 | OD525870/2025-2026:Supply, Installation , Testing and Commissioning of 11KV/433V, 400KVA, 50Hz, 3phase, Vector Dyn 11 Resin Cast Indoor type Copper wound USS Type Transformer with , off load tapping +5%-5% in steps of 2.5% and with with winding temperature indicator and hooter, LV side Cable box and HV terminal connected 11KV LBS Panel.11KV Multi Panel VCBM/LBS/LBS IndoorVCB 1No Incomer- 11kV, 630A, 26.3kA for 3 sec with spring charging motor rated for 230V AC VCB, tripping coil and closing coil rated for 24V DC.LBS 2 Nos Outgoing- 11 KV, 630A, 26.3 kA/1 sec Air break manual front operated LBS, tripping coil rated for 230V ACCT 3 Nos - 11KV Resin Cast CT (--/5 A, 5P10, 15VA) Dual corePT 1 No - 11KV Resin Cast PT (11KV/110V,25VA,Class 0.5)Protection Device 1 No - Instantaneous IDMT relay with Microprocessor based 3O/C +1EFR relay1 No - Master Trip Relay1 No - Auxiliary relayMetering & Indication Devices1 No - Digital Ammeter1 No - Digital VoltmeterIndicating Lamps for VCB/LBS ON.OFF, Spring Control, Trip, Circuit healthy, DC on11KV Resin Cast CT( --/5A, 10VA, Class 0.2s)11KV Resin Cast PT(11kV/110 V,20 VA, Class 0.2)Provision for HT TOD Meter (TOD Meter not in our scope)Bus bar Connections1 Set - Aluminium Bus barPanel Accessories1 No- 6 window annunciation Panel with Alarm1 No- power pack 230V AC-24 V DC1 No - Breaker Control Switch1 No - Switch with Plug pointSpace HeaterThermostatCubicle lamp with switch3 Lot - control wiringHRC fuse |
| 3 | 8.3.2:Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade offollowing size in the existing RCC/ HUME/ METAL pipe as required.Above 120 sq. mm and upto 400 sq. mm |
| 4 | 10.4.4:Supplying and making indoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required:300 sq. mm |
| 5 | 90.14.1.2:Fabrication, supply, conveyance, installation testing and commissioning of floor or wall mounting, dust and vermin proof, cubicle type MV panel board comprising of the following components/ devices & complying to IS 8623.Fabrication of fully partitioned, dust and vermin proof enclosure for panel assembly as per form 4 of IS 8623 (with latest amendments) using CRCA sheet as per approved design and requirement, with front and rear access facility, bus bar chambers, hinged doors for all switch gear compartments, earthing the doors using 4 sq mm braided copper conductor, providing necessary cut-outs for mounting meters, relays, indication lamps, bus bar interconnection etc, detachable covers for bus bar chamber and cable alley, powder coating the assembly after subjecting to 7 tank process etc as required. CRCA sheet alone be used for the fabrication. Angles/ flats/ slotted angles etc shall not be used for the fabrication of panel assembly. The measurments will be taken the area of the complete sheets used for panel board including partitions, folding, shrouding etc.Supply and fabrication of MV panel board using 1.6mm CRCA sheet, powder coated (excluding base frame) |
| 6 | 90.14.2.5:Supply and providing 6mm SMC sheet as shrouding for bus interconnection / terminations etc. including required nut & bolt etc. |
| 7 | 90.14.3.2:Supply and providing heavy duty 'A' section neoprene gasket in the panel boardU' section rubber beeding suitable for 1.60/ 2.00 mm sheet |
| 8 | 90.14.4:Supply and fabrication conveyance and installation of base frame of panel board using 75 x 40 mm rolled steel channel (ISMC) |
| 9 | 90.14.11.15:MCCB AccessoriesSupply and fixing rotary handle, External type (including BUC handle with door interlock ) in the existing MCCB of rating up to 315-630 A |
| 10 | 2.2.18:Providing and fixing following rating and breaking capacity MCCB withthermomagnetic release and terminal spreaders in existing cubicle panel boardincluding drilling holes in cubicle panel. making connections. etc. as required.400 Amp, 50 KA, 4 pole |
| 11 | 2.2.19:Providing and fixing following rating and breaking capacity MCCB withthermomagnetic release and terminal spreaders in existing cubicle panel boardincluding drilling holes in cubicle panel. making connections. etc. as required.630 Amp, 50 KA, FPMCCB |
| 12 | 2.2.15:Providing and fixing following rating and breaking capacity MCCB withthermomagnetic release and terminal spreaders in existing cubicle panel boardincluding drilling holes in cubicle panel. making connections. etc. as required.200 Amp, 36 KA |
| 13 | 90.12.7.34:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 185 sq mm |
| 14 | 9.1.27:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 185 sq. mm (57mm) |
| 15 | 90.12.5.38:Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.4 core 4 sq mm |
| 16 | 90.14.5:Supply and fabrication conveyance and installation of angle iron frame work for wall mounting panel board |
| 17 | 90.16.3.5:Supply and clamping the following size of strips on surface of wall/ parapet/ existing cable tray using clamps fabricated from 20 X 3 mm GI flat duly painted or heavy duty GI spacer saddles spacing of clamps not exceeding 1 m, making good the damages, colour washing etc. as required ( for horizontal run)32 x 6 mm GI strip |
| 18 | 90.16.3.7:Supply and clamping the following size of strips on surface of wall/ parapet/ existing cable tray using clamps fabricated from 20 X 3 mm GI flat duly painted or heavy duty GI spacer saddles spacing of clamps not exceeding 1 m, making good the damages, colour washing etc. as required ( for horizontal run)50 x 6 mm GI strip |
| 19 | 90.14.10.4:Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required.16 A-100A, 25/35 kA (Ics=100%Icu), 4 pole, current limiting type MCCB having thermal setting range of 80 - 100% with thermal magnetic release having adjustable OL |
| 20 | 90.14.10.13:Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required.200A, 35/36 kA (Ics=100%Icu), 4 pole, current limiting type MCCB with microprocessor based release with overload setting of 50 - 100% having adjustable OL & SC |
| 21 | 90.14.11.3:MCCB AccessoriesSupply and fixing one number earth fault Relay up to 250A to 400A with CBCT. |
| 22 | 1.17.29:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.2 x 6 sq. mm |
| 23 | 90.6.4.51:Supply and drawing 650/1100 V grade FRLS PVC insulated stranded single core copper conductor cables conforming to IS 694 part I 1990 in the existing surface / recess conduit as required including giving necessary connections of the following sizes.10.00 sq.mm 1 Run |
| 24 | 90.12.24.1:Supply of superior quality copper tubular cable socket and making core termination of cables of the following sizes including crimping etc. as required.2.5 sq mm |
| 25 | 90.12.24.3:Supply of superior quality copper tubular cable socket and making core termination of cables of the following sizes including crimping etc. as required.6 Sq mm |
| 26 | 90.12.24.4:Supply of superior quality copper tubular cable socket and making core termination of cables of the following sizes including crimping etc. as required.10 sq mm |
| 27 | 90.14.24.31:Supply & fixing the following Power Capacitors 3 phase delta connected in positon and giving connection.5 KVAr, 3 phase, 440 V, Metalised Poly Propylene Heavy duty Cylindrical Gas filled Capacitor suitable for APFC panel without block reactor. |
| 28 | 90.14.24.34:Supply & fixing the following Power Capacitors 3 phase delta connected in positon and giving connection.10 KVAr, 3 phase, 440 V, Metalised Poly Propylene Heavy duty Cylindrical Gas filled Capacitor suitable for APFC panel without block reactor. |
| 29 | 90.14.24.36:Supply & fixing the following Power Capacitors 3 phase delta connected in positon and giving connection.15 KVAr, 3 phase, 440 V, Metalised Poly Propylene Heavy duty Cylindrical Gas filled Capacitor suitable for APFC panel without block reactor. |
| 30 | 90.14.24.37:Supply & fixing the following Power Capacitors 3 phase delta connected in positon and giving connection.20 KVAr, 3 phase, 440 V, Metalised Poly Propylene Heavy duty Cylindrical Gas filled Capacitor suitable for APFC panel without block reactor. |
| 31 | 2.10.1:Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, \\"\\"C\\"\\" curve, miniaturecircuit breaker suitable for inductive load of following poles in the existing MCBDB complete with connections, testing and commissioning etc. as required.Single pole |
| 32 | 2.10.4:Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, \\"\\"C\\"\\" curve, miniaturecircuit breaker suitable for inductive load of following poles in the existing MCBDB complete with connections, testing and commissioning etc. as required.Triple pole |
| 33 | 90.16.1.4:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required4.00 mm copper conductor ( 8 SWG) |
| 34 | 5.4:Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 35 | 90.12.5.34:Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.3.5 core 185 sq mm |
| 36 | 90.12.7.36:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 300 sq mm |
| 37 | 90.6.4.1:Supply and drawing 650/1100 V grade FRLS PVC insulated stranded single core copper conductor cables conforming to IS 694 part I 1990 in the existing surface / recess conduit as required including giving necessary connections of the following sizes.1.00 sq.mm 1 Run |
| 38 | 90.6.5.19:Supply and drawing the following sizes of multi-core PVC insulated & FRLS PVC sheathed 650/1100 V grade copper conductor round flexible cables conforming to IS 694 part I 1960 in the existing surface / recess conduit as required including giving necessary connections of the following sizes.4 core 2.50 sq mm |
| 39 | 90.12.10.2:Supply & laying of DWC pipe in ordinary soil 0.75m below ground level including excavation50/38 mm or nearest size |
| 40 | 9.1.1:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.2 X 6 sq. mm (19mm) |
| 41 | 9.1.30:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 300 sq. mm (70mm) |
| 42 | OD525884/2025-2026:Supply, installation , testing and commissioning of 12 stage 440/110 V 5A/1A, Intelligent Power Factor Controllers (IPFC) on existing panel board. |
| 43 | OD525885/2025-2026:Supply and providing plate earthing as per IS 3043 with 1200x1200x12.0 mm GI/CI earth plate 50 mm GI watering pipe fixed to earth plate with 25 x 3 mm GI clamps.GI funnel with weld mesh, filling required quantity of charcoal including construction of inspection chamber with a bed concrete of 1:4:8 PCC using 40 mm broken stone (10 cm thick),brick work in cement mortar 1:6 plastering the surface of brick masonry and the exposed surface of PCC bed with cement mortar 1:4,12mm thick(the finished inside dimension shall be 450x450x450 mm) including test joint, earth continuity conductor to the plate, and covering at the top. ( in ordinary soil ) |
| 44 | OD525886/2025-2026:Supply and fixing Aluminium Busbar of required size including all accessories as required. |
| 45 | OD525887/2025-2026:Supply and fixing Three Phase Over Current & Earth fault Relay with IDMT & Definite time characteristic, 51N suitable for 240 V AC |
| 46 | OD525888/2025-2026:LED indicators for all Voltage Ranges -Red, Yellow,green, or Orange colour |
| 47 | OD525889/2025-2026:Supply, conveyance, installation, testing and commissioning of Multi function Meter to read V, A, F, PF, kW, kVA and site selectable kWh/ kVAh |
| 48 | OD525890/2025-2026:Supply and providing 2.5 mm thick Elastomeric fire retardant insulating mat as per IS15652/2006 to withstand 11KV dielectric strength |
| 49 | OD525891/2025-2026:Supply 3 core 300 sqm stranded compact circular aluminium conductor, conductors screened with extruded semi conducting compound XLPE insulated, insulation screened with extruded semi conducting compound in combination with copper tape (0.3KA for I sec.) cores laid up. inner sheath of PVC tape, galvanized steel flat strip armoured, and overall PVC sheathed cable conforming to IS: 7098 part II 1985 with latest amendments |
| 50 | OD525937/2025-2026:Supply, installation , testing and commissioning of 12 stage 440/110 V 5A/1A, Intelligent Power Factor Controllers (IPFC) on existing panel board. |
| 51 | 90.12.7.37:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 400 sq mm |
| 52 | 9.1.31:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 400 sq. mm (82mm) Please Enable Macros to View BoQ information |