| 1 | Supply, laying , testing and commissioning HT cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) with stranded aluminium conductor, 11000 volts grade, of size 3 core 95 sq mm confirming to IS 7098 Part- II, connecting by providing suitable size of aluminium lugs and laid in trenches/ducts/walls/passing through pipes ets all as specified and directed by Engr-in-charge. |
| 2 | Excavating in trenches not exc 1.5m wide and not exc 1.5m deep and getting out in soft / loose soil complete all as specified and directed |
| 3 | Returning, filling in soft/loose soil, including, spreading, levelling, watering and well ramming in layers not exc. 25 cm complete all as specified and directed. |
| 4 | Removing excavated materials (soils) to a distance not exc 50.00 mtr and depositing where directed at a level not exc 1.50 mtr above the starting point , complete all as specified and as directed. |
| 5 | M&L for sand cushioning for protection of HT under ground cable with screen wash sand in trenches 8 cm before laying and 15 cm after laying the cable (15 cm should be punned to 10 cm) and punning properly all as specified and directed by Engr-in-charge. |
| 6 | Supply and laying factory made un-reinforced precast concrete cable cover, class HVP, type 1 with peak, size 300mm x 180mm x 40mm complete all as specified and directed. |
| 7 | M & L for Cable jointing kit for 11 KV (Earthed) grade cable for outdoor end termination cold shrink end type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50sqmm to 95 sqmm complete all as specified and directed. |
| 8 | Supply and fix cable jointing kit for 11 KV grade cable for straight through cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE, armoured, Al conductor cable of size 50 Sqmm to 95sqmm, Outdoor type complete all as specified and directed. |
| 9 | M&L for earthing complete with Galvanised Iron electrode 600x600x6 mm thick buried directly in ground (earth pit not less than 2.25 m depth below ground level) with top edge of the plate not less than 1.5 m below normal ground level connected to GI strip 20x3mm mm dia by means of brass nut, bolt, washer & protection pipe for earth lead from the earthing plate to the DB/main switch/Panel, (25 mm bore, Light grade), watering pipe from plate to earthing pit (20 mm bore, medium grade), funnel with wiremesh. The earthing pit made up of PCC 1:3:6 type CI and pit cover made up of 40 mm thick pre cast RCC 1:2:4 type BI reinforced with 6 mm dia TMT rod and suitable handle of 8 mm dia TMT rod incl necessary earth work as shown in SSR Part 1 plate no.5 as specified & directed. Please Enable Macros to View BoQ information |
| 10 | M&L for earthing complete with Galvanised Iron electrode 600x600x6 mm thick buried directly in ground (earth pit not less than 2.25 m depth below ground level) with top edge of the plate not less than 1.5 m below normal ground level connected to GI strip 20x3mm mm dia by means of brass nut, bolt, washer & protection pipe for earth lead from the earthing plate to the DB/main switch/Panel, (25 mm bore, Light grade), watering pipe from plate to earthing pit (20 mm bore, medium grade), funnel with wiremesh. The earthing pit made up of PCC 1:3:6 type CI and pit cover made up of 40 mm thick pre cast RCC 1:2:4 type BI reinforced with 6 mm dia TMT rod and suitable handle of 8 mm dia TMT rod incl necessary earth work as shown in SSR Part 1 plate no.5 as specified & directed. Please Enable Macros to View BoQ information |