Sales : +91-777 804 8217
| Sl. No. | Item Description |
| 1 | 1. The rates for the Elect. Items are based on Specfiavtions .2. In case of any typographical error, the relevant code for specification & BSR for rates shall be final.3. The contents of RPWA 100 shall form the essential & integral part of this G-Schedule. |
| 2 | Supply, installation, testing and commissioning of UPS with isolation transformer & battery for backup, having three phases input three phase output. Online double conversion VFI-SS-111 technology, with sinusoidal wave form, architecture (standalone of distributed parallel up to 8 units), having input characteristics i.e. input voltage (380v, 400v, 415v, 3Ph+N+PE), input frequency (45 -65 Hz), input voltage range (Ph - Ph) : (half load 208v -467v/ full load 312v - 467v), total harmonic distortion of input current < 3% (at full linear load), compatibility with diesel generators configurable for synchronization between the input and output frequencies even for high frequency variations, input power factor > 0.99, having output characteristics i.e. output voltage (380v, 400v, 415v, 3Ph+N (adjustable from front panel), efficiency up to 96%, efficiency in ECO mode up to 98.5%, output frequency (nominal) 50 /60 Hz 0.01% free run (adjustable from front panel), crest factor 3 : 1, total harmonic distortion of output voltage < 2 % (at full linear load), output power factor 0.9, output voltage tolerance ± 1%, built in automatic and maintenance bypass, inbuilt isolation transformer, battery type (VRLA - AGM maintenance free). Communication & management i.e. 30 KVA (3 phase input & 3 phase output) FOR 30 MIN BACK UP MIN 24000VAH |
| 3 | Providing, Instalationand, commissioning and testing complte With all Material including Electro mechanicl with civil work required at site for opening size 1200 x 1500mm and 100kg load to be transfer from ground floor to first floor as per site conditions. Gearless Dumb Waiter,S.S 304 Honey Comb Finish Vertical Bio- Parting Manual Details are As under :-Load Capacity 200Kgs, Car diamension as per site, Door Opening 800mm, Door Height 1200mm, Car door Finish SS 304, Shaft width 1200mm depth 1500mm, Floor Height 3450mm, with No Pit.,Travel Height apprx.5000mm Max.,Car flooring ss plane sheet 1mm thick plate, Power Supply Ac 415 V 3 Phase 50 Hz & Ac 220,1 Phase 50 Hz. |
| 4 | 1. The rates for Civil & Elect. Items are based o PWD BSR 2022 (All Raj.).2. In case of any typographical error, the relevant code for specification & BSR for rates shall be final.3. The contents of RPWA 100 shall form the essential & integral part of this G-Schedule. |
| 5 | Demolishing brick work manually/ by mechanical means including stacking of serviceable material and disposal of unserviceable material within 50 metres lead as per direction of Engineer-in-charge. In cement mortar. |
| 6 | Demolishing R.C.C. work manually/ by mechanical means including stacking of steel bars and disposal of unserviceable material within 50 metres lead as per direction of Engineer-in-charge. |
| 7 | Carriage of material -Building Rubbish Stone metal (Grit and ballast etc.) For 10 Km. |
| 8 | Earth work in excavation by mechanical means (Hydraulic Excavator )/ manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan) including dressing of sides and ramming of bottoms, lift upto 1.5 m, including taking out the excavated soil and depositing and refilling of jhiri with watering & ramming and disposal of surplus excavated soil as directed with in a lead of 50 meter. All kinds of soils |
| 9 | Filling available excavated earth (excluding rock) in trenches, plinth side of foundation etc. in layers not exceeding 20 cm. in depth, consolidating each deposited layer by ramming and watering including lead up to 50 meter and with all lift. |
| 10 | Providing and laying in position cement concrete including curing, compaction etc. complete in specified grade excluding the cost of centering and shuttering - All work up to plinth level. M10 grade Nominal Mix 1: 3: 6 (1 cement : 3 coarse sand : 6 graded stone aggregate 20mm nominal size). |
| 11 | Random rubble dry stone Kharanja under floor. |
| 12 | Providing and laying in position specified grade of cement concrete for all RCC structural elements upto plinth level including curing, compaction, finishing with rendering in cement sand mortar 1:3 (1 cement: 3 coarse sand) and making good the joints and cost of plastizers( if required) excluding the cost of centering, shuttering and reinforcement. M20 grade Nominal Mix / Design Mix |
| 13 | Centering and Shuttering with plywood or steel sheets including strutting, propping bracing both ways and removal of formwork for foundation , footings, strap beam, raft , bases of columns etc. |
| 14 | Random Rubble stone masonry for with hard stone in foundation and plinth in Cement Sand mortar above 30 CM thick wall in:Cement Mortar 1:6 ( 1-Cement : 6-Sand). |
| 15 | Providing and laying in position specified grade of cement concrete for RCC structural elements upto floor five level including curing, compaction, finishing with rendering in cement sand mortar 1:3 (1 cement: 3 coarse sand) and making good the joints and cost of plastizers( if required) excluding the cost of centering, shuttering and reinforcement for Beams, suspended floors, roofs, griders having slopes up to 15º, landings, balconies, shelves, chajjas, lintels, bands, plain windows sills, staircases and spiral staircases etc. M20 grade Nominal Mix / Design Mix |
| 16 | Centering & shuttering with plywood or steel sheets including strutting, propping bracing both ways with steel props and removal of formwork for upto floor five level for : Suspended floors, roofs, landings, staircases, balconies, girders, cantilevers, bands, coping bed plates, anchor blocks, sills, chhajjas, lintel, beam, plinth beam etc. |
| 17 | Add extra for providing richer mixes respectively at all floor levels.Providing M-25 grade concrete by using cement as per codal provision instead of M-20 grade design mix. |
| 18 | Providing and fabricating reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding (including cost of binding wire) all complete up to floor five level. ('Original producers' who manufacture billet directly from iron ores and roll the bilets to produce steel conforming to IS:1786) Thermo-mechanically Treated bars (Conforming of relevent IS code) |
| 19 | Brick work with mechanised autoclaved flyash lime bricks conforming to IS: 12894 :2002 of class designation 100 in superstructure above plinth level upto floor V level in. Cement mortar 1 : 6 (1 cement : 6 coarse sand) |
| 20 | Half Brick work with mechanised autoclaved flyash lime bricks conforming to IS: 12894 :2002 of class designation 100 in superstructure above plinth level upto floor V level in. Cement mortar 1 : 4 (1 cement : 4 coarse sand) |
| 21 | Plaster on new surface on walls in cement sand mortar 1:6 including racking of joint etc. complete fine finish :20mm thick. |
| 22 | Plaster on new surface on walls in cement sand mortar 1:6 including racking of joint etc. complete fine finish :12mm thick. |
| 23 | 6 mm thick cement plaster to ceiling of mix 1:3 (1cement : 3-fine sand) |
| 24 | Providing and applying white cement based putty over plastered surface to prepare the surface even and smooth complete.New Plastered Surface (three or more coats) |
| 25 | Finishing walls with Acrylic Smooth exterior paint of required shade including all scaffolding. New work (Two or more coat applied @ 1.67 ltr/10 sqm over and including base coat of water proofing cement paint applied @ 2.20 kg/ 10 sqm ). |
| 26 | Distempering with 1st quality acrylic washable distemper (ready mixed) of approved manufacturer and of required shade and colour completeincluding all scaffolding as per manufacturer's specification. Two or more coats on new work including prepartion of base with primer, putty, lippy etc complete in all respect. |
| 27 | Making grooves as per design in plaster 10mm to 20mm wide. |
| 28 | P & F 1st quality Heavy Duty Vitrified glazed MAT tiles on floor, skirting and steps etc.in different sizes (thickness minimum 10mm) with water absortion less than or equal 0.08% and conforming to IS 15622 of approved make in all colour and shade, laid with 20 mm thick CM 1: 4 including grounting the joints with white cement and matching pigment etc complete.size 600 mm X 600 mm |
| 29 | Providing & laying Chequered terrazzo tiles of approved make 22mm thick with marble chips of size upto 6mm, in floors, jointed with neat cement slurry mixed wit pigment to match the shade of tiles including rubbing and polishing complete in all respect as per specification, on 28mm thick bed of C.M. 1:4 :Dark shade using ordinary cement. |
| 30 | Add extra for non slipping 9-12 mm ironite topping tiles |
| 31 | Kota stone slab flooring 25 mm thick over 20 mm (average) thick base laid over and jointed with grey cement slurry mixed with pigment to match the shade of the slab including rubbing and polishing complete with base of cement mortar 1 : 4 (1 cement : 4 coarse sand). For area of each slab from 2001 to 5000 Sq.Cm |
| 32 | Kota stone slabs 25 mm thick in risers of steps, skirting, dado and pillars laid on 12 mm (average) thick cement mortar 1:3 (1 cement 3 coarse sand) and jointed with grey cement slurry mixed with pigment to match the shade of the slabs, including rubbing and polishing complete. For area of each slab upto 2001 Sqcm |
| 33 | Providing and fixing Granite stone slab mirror polished and machine edge cut in walls, pillars, steps, Shelves, Sills Counters, Floors etc. laid on 12mm (Av.) thick base of cement mortar 1:3 (1 cement : 3 coarse sand) jointing with white cement mortar 1:2 (1white cement : 2 marble dust) with pigment to match the shade of the marble slab including grinding, rubbing and polishing complete. Jhunjhunu / Jalore (Red/Choclate/Black/Pink Colour) 1501 Cm2 to 3600 Cm2 Tiles |
| 34 | Extra for providing edge moulding to 15-18mm thick marble/ Granite/Kota stone counters, Vanities etc. including machine polishing to edge to give high gloss finish etc. complete as per design approved by Engineer-in-Charge. Granite/Kota Stone Work. Half Edge moulding |
| 35 | Providing and fixing 1st quality MAT finished ceremic tile size 300x300mm confirming to IS : 13755 and IS : 15622 colour such as white, grey, ivory, fume red brown, light green, light blue and other light shades in floors, steps, pillars etc. laid on a bed of neat cement slurry finished with flush pointing in the white cement mixed with pigment to match the shade of the tile complete (including the cost of cement mortar bed 1:4). |
| 36 | Providing and fixing 1st quality standard white, grey, ivory, fume red brown, light green, light blue and other light shades glazed tiles confirming to IS : 13753 & IS :15622 of size 200mm x 300mm in walls, floors, steps, pillars etc. laid on a bed of neat cement slurry finished with flush pointing in the white cement mixed with pigment to match the shade of the tile complete (excluding the cost of cement plaster on walls and pillar). |
| 37 | Grading roof for water proofing treatment with water proffing compound. Cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) |
| 38 | Crazy marble stone flooring 20mm thick marble stone with black or of specified colour topping including filling the gaps with cement marble chips mix in proportion of 4 : 7 (4cement : 7 white black or white or black marble chips) size from 1mm to 4mm by volume and under layer of 25mm thick cement concrete [1:2:4, graded stone aggregate 12.5mm nominal size] rubbing and polishing and cement slurry etc. complete :In ordinary cement. |
| 39 | Extra in marble/other flooring work for upto 50 mm wide strip of Green/White/ Jaisalmer stone in flooring work as per direction of Engineer in Charge |
| 40 | Providing gola 75x75 mm in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 stone aggregate 10mm and down gauge) including finishing with cement mortar 1:3 (1 cement : 3 fine sand) as per standard design : |
| 41 | Providing and fixing aluminum work for doors ,windows, ventilators and partition with extruded built up standard tubular / appropriate Z sections and other sections of approved make conforming to IS :733 and IS :1285, fixed with rawl plugs and screws or with fixing clips ,or with expansion hold fasteners including necessary filling up of gap. at junctions , at top ,bottom and sides with required PVC/neoprene felt etc. Aluminium section shall be smooth ,rust free, straight ,mitered and jointed mechanically wherever required including cleat angle Aluminium snap beading for glazing /paneling , C.P. brass/ stainless steel screws Al. Tower bolt & Al. handle & Al. Aldrop etc.,all complete as per architectural drawings and the directions of Engineer- in – charge .(Glazing and paneling to be paid for separately). |
| 42 | For shutters builtup standard tubular sections of openable doors ,windows & ventilators including providing & fixing hinges / rollers etc. and making provision for fixing of fittings wherever required (lockes shall be paid for separately). Powder coating aluminum ( minimum thickness of powder coating 50 micron). Extra for shutters of sliding aluminum windows |
| 43 | Extra for shutters of sliding aluminum windows |
| 44 | Providing and fixing glazing in aluminium door, window ,ventilator shutters and partitions etc. with PVS / neoprene gasket etc. complete as per the architectural drawings and the directions of engineer-in-charge.(Cost of aluminium snap beading shall be paid in basic item.) With float glass panes of 5.0 mm thickness ( weight not less than 13.50 kg/sqm) |
| 45 | Providing and fixing aluminium U shape handle of size 100mm with SS screws etc. Complete as per direction of Engineer-in-charge Polyester powder coated minimum thickness 50 micron aluminium . |
| 46 | Providing and fixing 12 mm thick prelaminated three layer medium density (exterior grade ) particle board Grade I, Type II conforming to IS : 12823 bonded formaldehyde synthetic resin ,of approved brand and manufacture in paneling fixed in aluminium doors ,windows shutters and partition frames with C.P. brass / stainless steel screws etc. complete as per architectural drawings and direction of engineer-in-charge.Pre-laminated particle board with decorative lamination on one side and balancing lamination on other side. |
| 47 | Providing and fixing expanded grill made of aluminum as per design and drawing having members section of size 7.5mm x 6.0mm and opening of size 102mm x 99mm to aluminum window/vent with required screws, Y and H aluminium section (as per drawing) at the ends and middle joints respectively complete in all respect as per direction of engineer in charge. Powder coating aluminum ( minimum thickness of powder coating 50 micron) |
| 48 | S&f fixed wire gauge of stainless steel of 14 mesh x 24 gauge to the aluminium window by Aluminium beading 20x3mm with suitable screws not exceeding 150mm distance at all heights with all lead and lift with scafolding. |
| 49 | Supplying and fixing fixed wire gauge of 14 mesh x 24 gauge to the metal frame of rolled section by metal beading 20x3mm with suitable screw at not exceeding 150mm distance. |
| 50 | Providing and fixing 100mm brass locks (best make of approved quality) for aluminium doors including necessary cutting and making good etc. complete. |
| 51 | Providing and fixing in position collapsible steel shutters with vertical M.S. Channels 20 x 10 x 2mm and bracket with flat iron diagonals 20 x 5mm. size with top and bottom rail of T-iron 40 x 40 x 6mm. with 40mm dia steel pulleys/ball bearing complete with bolts, nuts locking arrangements inside and outside stoppers, handles etc. as per specification including applying a priming coat of approved steel primer. (To be measured and paid as per outer dimension). |
| 52 | 30mm thick factory made solid panel PVC door shutter consisting of frame made out of M.S. tubes of 19 gauge thickness and size of 19mm x 19mm for stiles and 15 mm x15mm , top & bottom rails. M.S .frame shall have a coat of steel primers of approved make and manufacture M.S. frame covered with 5mm thick heat moulded PVC ‘C channel of size 30mm thickness, 70mm width out of which 50mm shall be flat and 20mm shall be tapered in 45 degree angle on either side forming stiles; and 5mm thick, 95mm wide PVC sheet out of which 75 mm shall be flat and 20mm shall be tapered in 45 degree on the inner side to form top and bottom rail and 115mm wide PVC sheet out of which 75 mm shall be flat and 20mm shall be tapered on both sides to form lock rail. Top bottom and lock rails shall be provided either side of the panel. 10mm (5mm x 2) thick, 20mm wide cross PVC sheet shall be provided as gap insert for top rail & bottom rail. Panelling of 5mm thick PVC sheet to be fitted in the M.S. frame welded/ sealed to the stiles & rails with 7mm (5mm +2mm) thick x 15mm wide PVC sheet bending on inner side, and joined together with solvent cement adhesive. An additional 5mm thick PVC strip of 20mm width is to be stuck on the interior side of the ‘C Channel using PVC solvent adhesive etc. complete as per direction of Engineer-in-charge, manufacture’s specification & drawing.(For W.C.and bathroom door shutter). |
| 53 | Providing and fixing factory made P.V.C. door frame of size 50x47mm with a wall thickness of 5mm, made out of extruded 5mm rigid PVC foam sheet mitred at corners and joined with 2 Nos. of 150mm long brackets of 15x15mm M.S. square tube, the vertical door profiles to be reinforced with 19x19mm M.S. square tube of 19 gauge, EPDM rubber gasket weather seal to be provided through out the frame. The door frame to be fixed to the wall using M.S. screws of 65/100mm size complete as per manufacturers specification and direction of Engineer-in-Charge. |
| 54 | Providing and fixing pressed steel door frames confirming to IS 4351 manufactured from commercial mild steel sheet of 1.25 mm thickness including hinges jamb, lock jamb, bead and if required angle threshold of mild steel angle of section 50x25mm, or base ties of 1.25mm pressed mild steel welded or rigidly fixed together by mechanical means, adjustable lugs with split end tail to each jamb including steel butt hinges 2.5mm thick with mortar guards, lock strike-plate and shock absorbers as specified and applying a coat of approved steel primer after pre-treatment of the surface including filling with CC 1:2:4(M15 grade) complete as directed by Engineer-in-charge : Profile B |
| 55 | Providing and fixing M.S. sheet 1mm thick single leaf door shutter in angle iron frame 35x35x5mm suitabilly diagonally braced with 25x3mm flat iron above and below lock rail of size 50x5mm beading extra including all fittings, as per direction of Engg. incharge but excluding cost of chowkhats: including two coats of anit-corrosive red oxide primer paint. |
| 56 | Add extra for double leaf shutters. |
| 57 | Providing and fixing external grade board solid core single leaf flush door shutters ISI 2202-67 marked using Phenol formal dehyderesin in glue both sides with approved steel fittings complete as per annexure 'A' :30 mm thick . Commercial Veneer both side |
| 58 | Providing and fixing of Un perforated Antibacterial Metal Tile Ceiling System comprising of Tile of 600mm wide and 600mm long manufactured out of 0.7mm thick aluminium alloy 3105 with beveled edge of 4.15mm width height of 32mm. The Tile will be manufactured on advanced equipment that includes several leveling stages in the manufacturing process by approved manufacturers. Tile ends will be raised with pips and slops to ensure positive engagement into the spring to enable for de-mounting of individual panels. The Tile sides will be sufficiently high to ensure a minimum deflection across the length of Tile. All Tiles will be bevel edged. The Tile shall be epoxy polyester powder coating with ANTIBAC in white colour which is in compliant to ROHS directive. The Tile shall be cllpped into clip in rail of 0.5mm thick GI. in form of a grid system using a cross connector. The clip in rail shall be supported from slab by means of rigid Suspension of 4mm G .I rod, Hold on Clamp with Clip. POWDER COATING SPECIFICATION: Aluminium PANELS, cleaned through eco friendly cleaning ,process and powder applied through electrostatic charged Automatic Carona technology spray guns and cured in combination of Infrared & hot air oven in a certified plant as Akzo International approved applicator . The powder is conforming with the performance requirements of the AAMA2603.02 & Qualicoat Claa 1 specifications. The coating thickness will be minimum 60 microns with properties of Salt Spray of 1500 hrs in exposure in SST Cabinet with Minimum blister rating 8. (Tensile strength of suspension-344/413 mpa and fastner strength-110kg)All Ceiling Panels shall adhere to GreenPro Certifications.The powder is conforming with the performance requirements of the AAMA2603.02 & Qualicoat Claa 1 specifications. The coating thickness will be minimum 60 microns with properties of Salt Spray of 1500 hrs in exposure in SST Cabinet with Minimum blister rating 8. (Tensile strength of suspension-344/413 mpa and fastner strength-110kg)All Ceiling Panels shall adhere to GreenPro Certifications. |
| 59 | Providing & fixing precast cement concrete coping 1 : 2 : 4 mix 50mm thick complete as per specification : |
| 60 | Extra for using size above 200x300mm in glazed tiles and for using 400mm x 400mm MAT finished tiles in place of 300mm x 300mm size. |
| 61 | Making khurras 450 x 450mm with average minimum thickness 50mm cement concrete 1 : 2:4 over P.V.C. Sheet 1 Mtr. x 1 Mtr. x 40micron finished with 12mm cement plaster 1 : 3 and one coat of neat cement, rounding edges and making and finishing the out let complete. |
| 62 | Making of drip course (Tapka) in cement sand mortar 1:6 width upto 40 mm and 10 mm thick as per approved design |
| 63 | Supplying and fixing in walls machine cut and polished stone shelves, tands and in CM 1:3 with machine cut edges : Sand or other approved stone 50mm thick. |
| 64 | Painting with synthetic enamel paint of approved brand and manufacture to give an even shade : Two or more coats on new work |
| 65 | Providing and fixing steel gate, grating , and grills made of angles, tees, square bars, flats,or black pipe with holdfast and fittings complete as per design and drawing including cutting welding and fabrication with priming coat of red oxide |
| 66 | Supplying and fixing rolling shutters of approved make, made of 80 x 1.25mm. M.S. laths interlocked together through their entire length and jointed together at the end by end locks mounted on specially designed pipe shaft with brackets, side guides and arrangements for inside and outside locking with push and pull operation complete including cost of spring hooks, providing and fixing necessary 25.3cm. long wire springs grade No. 2 and M.S. top cover 1.25mm thick for rolling shutters as per design & IS 6248- 1979. (Clear openable area to be measured for payment). |
| 67 | Providing & fixing ball bearing for rolling shutters |
| 68 | Extra for providing grilled rolling shutters manufactured out of 8 mm dia. M.S. bar instead of laths as per design approved by Engineer-in-charge. (area of grill to be measured). |
| 69 | Providing and fixing steel glazed window frame made out of 80x40 mm hollow sheet section of 16 gauge thickness, joint mitred welded and grinded including hold fast of steel lugs 13mm x 3mm and 15 Cm long embedded in C C block 15 x 10 x 10 Cm of 1:3:6 nominal concrete and including fixing of pivoted hinges of superior quality, window shutters made out of 50 x 25.0 mm hollow steel section 15 mm paitam of 18 gauge thickness, joint mitred and grinded including 10mm x 10mm square bars welded to frame for paitam fixing float glass 4mm thick panes with glazing clips and metal sash putty and fixing of shutters frames peg stay, U shape handle 100 mm long, tower bolts 100 mm long of steel powder coated superior quality including fixing and jointing with frame hinges priming coat with steel primer complete in all respect as per direction of Engineer-in –charge Window openable. |
| 70 | Providing and fixing Square bars or other flat welded to window, ventilatiors etc. |
| 71 | Construction of embankment with approved material obtained from borrow pits with a lift upto 1.5 m, transporting to site, spreading, grading to required slope and compacting to meet requirement of Tables 300-1 and 300-2 with a lead upto 1000 m as per MoRTHSpecification Clause 305.3 |
| 72 | Construction of granular sub-base by providing well graded material, spreading in uniform layers with Tractor Mount Grader on prepared surface, mixing by mix in place method with rotavator at OMC, and compacting with smooth wheel roller to achieve the desired density, complete as per MoRTH Specification Clause 401. For Grading I Material |
| 73 | Construction of dry lean cement concrete Sub- base over a prepared sub-grade with coarse and fine aggregate conforming to IS: 383, the size of coarse aggregate not exceeding 25 mm, aggregate cement ratio not to exceed 15:1, aggregate gradation after blending to be as per table 600-1, cement content not to be less than 150 kg/ cum, optimum moisture content to be determined during trial length construction, concrete strength not to be less than 10 Mpa at 7 days, mixed in a batching plant, transported to site, laid with a paver with electronic sensor, compacting with 8-10 tonnes vibratory roller, finishing and curing. |
| 74 | Construction of un-reinforced, dowel jointed at expansion and construction joint only, plain cement concrete pavement, thickness as per design, over a prepared sub base, with 43 grade cement or any other type as per Clause 602.2.2 M30 (Grade), coarse and fine aggregates conforming to IS:383, maximum size of coarse aggregate not exceeding 25 mm, mixed in a concrete mixer of not less than 0.2 cum capacity and appropriate weigh batcher using approved mix design, laid in approved fixed side formwork (steel channel, laying and fixing of 125 micron thick polythene film, wedges, steel plates including levelling the formwork as per drawing), spreading the concrete with shovels, rakes, compacted using needle, screed and plate vibrators and finished in continuous operation including provision of contraction and expansion, construction joints, applying debonding strips, primer, sealant, dowel bars, near approaches to bridge/culvert and construction joints, admixtures as approved, curing of concrete slabs for 14- days, using water finishing to lines and grade as per drawing and MoRTH Specification Clause 602 including vaccum dewatering process with allrequired equipments |
| 75 | Marking Centre Line and stop lines etc. on road as per IRC pattern with thermoplastic paint of approved quality and make with 8% glass beads laid on the road surface at temperature 160\\" C with a special applicator machine complete with a special applicator machine complete with labour material and traffic diversion arrangements. |
| 76 | Interlocking Concrete Block PavementProviding and Laying of Interlocking M-30 grade Concrete Block Pavements as per drawings and IS 15658:2006.with all materials shall conform to MoRTH Specification Clause 602. having thickness 80 mm. |
| 77 | Providing and laying at or near ground level factory made kerb stone of M-25 grade cement in position to the required line, level and curvature jointed with cement mortar 1:3 (1 cement : 3 coarse sand ) including making joints with without grooves (thickness of joints except at sharp curve shall not to more than 5mm) including making drainage opening wherever required complete including painting etc. as per direction of Engineer-in-charge (length of finished kerb edging shall be measured for payment). (Precast C.C. kerb stone shall be approved by Engineerin- charge). |
| 78 | M-30, 60 mm thick to be used in non traffic areas like building premises, monument premises, land scapes, public gardens/ park, domestic drives, paths and patios, Embankment slopes, sand stabilization Area etc.( As per table 1 of IS 15658:2006Category ‘C’not denated on any it’s faces like Hexagon, Rectangular, square shape as per IRC SP 63:2004 |
| 79 | Structural steel work riveted, bolted or welded in built up sections, trusses and framed work, including cutting, hoisting (height upto 10 m) , fixing in position and applying a priming coat of approved steel primer all complete: |
| 80 | Extra for hoisting and fixing for every additional one metre or part thereof beyond 10 mtr height. |
| 81 | Extra if square,rectangular hollow tubelar sections are used or grill made by flats only |
| 82 | Providing and fixing cow catcher made of R.S. joist angles channels MS rounds including cutting welding and fabrication with priming coat of red oxide (as per design). |
| 83 | Add extra for Square or Rectangular Pillars in Superstructre brick work up to five storey. Upto 45 cm length and two corners are free |
| 84 | Providing and laying damp-proof course with cement concrete grade M-150 (1 : 2 : 4) mortar prepared with 1% solution of water-proof compound complete as per specification .50mm thick. |
| 85 | Providing and installation of Poly Carbonate Sheet roofing over existing steel framing as per drawing and design including fixing with non-corrodible nuts and water proof washers as per instruction of Engineer-in-charge. |
| 86 | Roof: Insulated sandwich panels for roof of total thickness mentioned below exclusive of crest height of top corrugation. Panel shall be made of 0.50mm (+/-0.04mm) thick pre coated metal sheet on both sides of rigid polyurethane insulation. The top external facing metal sheet shall have corrugated shape with crest. The trapezoidal shape crowns/crest height should not be less than 30mm. The pre-coated metal sheet shall be PPGL (Pre Painted Galvalume Sheet with AZ coating) sheet having SDP (Super Durable Polyester) colour coat of 18 micron (min). The bottom sheet must have tongue and groove type flange (U shape) of 8mm x 8mm on groove side and 8mm x 12mm on tongue side. Flange must be on lengthwise sides for joining adjacent panels. Panel's bottom side PPGL sheet must also be pre-strengthened by full lengthwise stiffening with semi-circular beading of 12mm width & 3 to 4mm depth at 240 (+/-5) mm pitch. The top corrugated sheet must have at-least one open crown/crest for overlapping adjacent panel widthwise. Similarly the top corrugated sheet must have suitable open extension of min 6” on bottom widthwise side of panel for overlapping further panels joined lengthwise also. The insulation core shall be self-extinguishing DIN 4102,Class B3 fire retardant class rigid PUR with thermal conductivity of 0.025 W/mK and with initial density of 40kg/m3 (+/-2kg) suitable for temperature range of -30 degree C to +80 degree C. The panel must be made using glue-free high pressure hot pressing self-bonding method. PPGL sheet on both sides of panel shall have a min15 micron protective plastic guard film to avoid scratches during transportation.Thickness 65mm (+/- 2mm) |
| 87 | Sanatry Works |
| 88 | P & F European type white glazed vitreous china 1st quality Double syphonic W.C (IS :2556 Mark) with P or S trap including cutting and making good the wall and floor |
| 89 | P & F water closet Seat Covers with brass hinges complete : |
| 90 | Solid PVC (IS 2548 marked) grade-I Black for EWC. |
| 91 | P & F C.P. lugs for toilet seat cover. |
| 92 | P & F Low level Flushing Cistern of 10 litres capacity (IS : 2556 mark) of approved make with complete fittings C.I. brackets duly painted, brass ball cock with ball (IS: 1703 mark) complete including cutting and making good the wall: |
| 93 | PVC with PVC bend as per IS : 7231. |
| 94 | P & F WVC Wash basin (Ist quality IS:2556 Mark) of approved make with C.I. brackets duly painted 1 No. 15 mm C.P. Pillar cock (IS:8934 Mark) & 32 mm C.P. brass waste coupling of approved make, P.V.C Waste pipe with PVC nut 32 mm complete including cutting & making good the wall : |
| 95 | Size 550 mm x 400 mm |
| 96 | Size 550 mm x 400 mm dia for counter top |
| 97 | P & F Kitchen & Lab. Sink of approved make with C.I. brackets duly painted, 40 mm C.P. waste coupling, C.P. Brass chain with rubber plug, 40 mm G.I. waste pipe up-to floor level complete including cutting and making good the wall & floor : |
| 98 | WVC Lab sink (IS:2556 mark) size 530 x 430 x 180 mm |
| 99 | 1.0 mm thick stainless steel AISI -304 & IS 13983-1994 kitchen sink of approved make as per Engineer-in-charge with large waste coupling. |
| 100 | Overall size Bowl size |
| 101 | (inches) (inches) |
| 102 | 37 x 18 x 7 17x15x7 (with drain board) |
| 103 | P & F Bottle Trap of approved make : |
| 104 | C.P Brass 32 mm |
| 105 | P & F Bevelled edge Mirror/mirror with teak wood lipping around of special glass of approved make as per direction of Engineer-in-charge complete with 6mm thick commercial ply base fixed to wooden screws & washers. |
| 106 | Size 600 x 450mm x 4 mm thick |
| 107 | P & F Grating of approved quality/make: |
| 108 | Stainless Steel Sheet size 125mm dia. Heavy Quality of approved make |
| 109 | P & F Toilet Paper Holder with rod of approved quality/make: |
| 110 | C.P. brass heavy & Superior quality. |
| 111 | P & F Soap Dish or Tray of approved quality/make |
| 112 | C.P. brass heavy and superior quality. |
| 113 | P & F C.P. Health Faucet with 1Mtr. Long Tube & Hook of approved make and heavy as per direction of Enginner-in-Charge |
| 114 | P & F Inlet Connection (Angle Valves) Superior quality, of approved make, for Wash basin, Gyser etc. |
| 115 | C.P. Inlet connection 15mm.Brass (IS : 8931 marked) |
| 116 | P & F 15 mm. Dia Connection Pipe of approved quality/make :PVC pipe with C.P. Brass nuts upto length, 300mm (-do-) 450mm. |
| 117 | P & F Bib Cock (IS : 8931 Mark), Superior quality of approved make: |
| 118 | C.P. Brass bib cock,15mm nominal bore. |
| 119 | (-do-) Long body, 15mm nominal bore weight not less than 690 gm |
| 120 | (-do-) Elbow-action, 15mm nominal bore. |
| 121 | C.P. Pillar cock, Swan-neck with casted spout, 15mm nominal bore. |
| 122 | Providing and fixing Superior quality CP Brass fittings of approved make as per direction of Engineer-in-charge |
| 123 | Concealed stop cock 15 mm nominal size |
| 124 | Wall mixer 3 in 1 system with provision of tetephonic bath shower with bend pipe |
| 125 | P & F Towel Rail or Ring of approved quality/make: |
| 126 | C.P. brass Towel Rail elbow type with concealed screws size 600 mm (Heavy duty). |
| 127 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes (IS 15778 : 2007 code) having thermal stability for hot & cold water supply including all CPVC plain & brass threaded fittings i/c fixing the pipe with clamps at 1 metre spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge. (Internal work Exposed on wall) |
| 128 | 25 mm nominal size |
| 129 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes (IS 15778 : 2007 code) having thermal stability for hot & cold water supply including all CPVC plain & brass threaded fittings i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer in Charge. (Concealed work including cutting chases and making good the walls etc.,) |
| 130 | 20mm nominal size |
| 131 | 25 mm nominal size |
| 132 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes (IS 15778 : 2007 code) having thermal stability for hot & cold water supply including all CPVC plain & brass threaded fittings, this included jointing of pipes & fittings with one step CPVC solvent cement , trenching refilling & testing of joints complete as per direction of Engineer in Charge. (External work). |
| 133 | 32 mm dia nominal bore. |
| 134 | Making connection of G.I. distribution branch with G.I. main including all fitting. |
| 135 | Beyond 25mm & upto 100mm dia |
| 136 | P & F Full-way Valve (IS:778 Mark) or wheel valve of approved make : |
| 137 | (-do-) 25mm nominal bore. |
| 138 | (-do-) 40mm nominal bore. |
| 139 | (-do-) 50mm nominal bore. |
| 140 | P & F Gun-metal Non-return Valve or Check Valve (IS : 778 Make) of approved make, superior quality: |
| 141 | 50mm nominal bore. |
| 142 | Horizontal |
| 143 | Providing and Fixing Unplasticized Poly Vinyl Chloride (UPVC) SWR Pipes Type B for sciland waste discharge system (IS:13592 : 1992 Marked) of approved quality /make |
| 144 | 75 mm dia |
| 145 | 110 mm dia |
| 146 | Providing and Fixing Unplasticized Poly Vinyl Chloride (UPVC) SWR Pipes fittings type B for sciland waste discharge system (IS:13592 : 1992 Marked) of approved quality /make |
| 147 | Coupler |
| 148 | 75mm dia |
| 149 | 110mm dia |
| 150 | Bend 87.5 Dg. |
| 151 | 75mm dia |
| 152 | 110mm dia |
| 153 | Bend 45 Dg. |
| 154 | 75mm dia |
| 155 | 110mm dia |
| 156 | Door Bend 87.5 Dg. |
| 157 | 75mm dia |
| 158 | 110mm dia |
| 159 | Single 'Y' |
| 160 | 75mm dia |
| 161 | 110mm dia |
| 162 | Single Tee |
| 163 | 75mm dia |
| 164 | 110mm dia |
| 165 | Socket Plug |
| 166 | 75mm dia |
| 167 | 110mm dia |
| 168 | Pipe Clip |
| 169 | 75mm dia |
| 170 | 110mm dia |
| 171 | Single Tee with Door |
| 172 | 75mm dia |
| 173 | 110mm dia |
| 174 | Nahni Trap with Jali 4” |
| 175 | 110mm dia |
| 176 | Vent Cowel |
| 177 | 110mm dia |
| 178 | P&F rigid PVC Pipe (IS:4985 mark) class II/ (4 Kg. /Cm2.) approved quality /make including joining the pipe with solvent cement rubber ring and lubricant. |
| 179 | 110 mm dia (RWP VERTICAL ) |
| 180 | Providing, Laying & Jointing R.C.C. class NP-2 Non-Pressure pipes (IS : 458mark) of approved make with collars, jointed with C.M. 1:2 or having Spigot and socket ends with flexible rubber rings joint including testing of joints etc. complete : |
| 181 | 150mm dia Internal |
| 182 | 200mm dia Internal |
| 183 | P&F rigid PVC Pipe (IS:4985 mark) class II/ (4 Kg. /Cm2.) approved quality /make including joining the pipe with solvent cement rubber ring and lubricant.160 mm dia |
| 184 | Providing & Laying C.C. 1:3:6 (Stone Agreegate 20mm nominal size) all around PVC Pipe including 7.5 cm thick bed concerte [Width & Height = Dia of Pipe in CM+15CM] excluding cost of Pipe & Excavation of trenches etc. |
| 185 | Coupler (socket) 160 mm |
| 186 | Bend 87 .5 160 mm |
| 187 | P & F Square-mouth gully trap `A` grade (IS 651-1992 :marked) of approved make complete with C.I. grating, frame & Cover masonary chamber in C.M. 1:6, 100mm thick C.C. 1:5:10 base concrete, 40mm thick C.C.M-15 grade coping, 12mm thick cement plaster in CM 1:3 complete as per approved design & type. |
| 188 | Trap size 150 X 100mm, ferrow cement cover with frame, Internal Chamber size 300 X 300mm. |
| 189 | Construction of chamber in all type of soil with 300 mm thick masonry in CM 1:6 m,10 cm thick C.C. 1:5:10 in foundation, 20mm thick insider plaster in Cm 1:6, finished with floating neat cement, 50mm thick M-15 grade C.C. flooring , earthwork etc. complete as per design including disposal of surplus earth within a lead of 50 mtr. |
| 190 | Inside size 300 X 300 mm depth upto 0.5 M Cement cover with frame. |
| 191 | Inside size size 450 x 450mm depth upto 0.5 M Cement cover with frame |
| 192 | Construction of Soakage well in all types of soil of approved drawing, top 90 Cm .Portion in 450mm thick masonry with CM 1:6, 80 mm thick stone slab covering, jointing of slab in CM 1:3 ,Ralthal, kharanja 40mm thick M-15 grade C.C flooring, earth work etc . complete including disposal of surplus earth within a lead of 50 mtr . |
| 193 | Inner dia 90 Cm & 10 to 12 Mtr deep. |
| 194 | Construction of septic Tank in all types of soil with 40 Cm .thick masonry in CM 1:6, 15 Cm thick C.C bed of 1:5:10, M-15 grade C.C floor & RCC slab covering with M15 grade c.c. floor, 50 mm thick stone slab partition walls, 20 mm thick plaster in CM 1:6 finished with neat floating cement, 4 Nos stone foot rests of approved design ,two No. 450 mm dia each Ferro cement cover with frame, earth work etc. complete as per approved drawing including disposal of surplus earth within a lead of 50 mtr:- Size 200x100x130 cm.(for 10 users) with 115 mm thick RCC (M-20) slab with Tor steel reinforcement 8mm ϕ @15 cm c/c bothways including shuttering complete in all respect. |
| 195 | Construction of open Drain with 112mm thick brick masonry in CM 1:4 Semi circular S.W. glazed channel (confirming to IS Standards) fixed with cement mortar 1:1 over a bed of 100mm thick C.C. 1:5:10, filling of edged with M-15 grade C.C. flooring, 12mm cement plaster 1:4, over all exposed faces, excavation & disposal of earth with in a lead of 50 mtr complete as per approved drawings :250 mm drain,225mm Av. depth width 25 Cm S.W. glazed channel. |
| 196 | Electrical Work |
| 197 | Wiring of light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper conductor 1.1 kV grade and 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper earth conductor 1.1 kV grade (IS:694) in recessed ISI marked MMS ( IS:9537 P - III ) virgin material PVC conduit & it's ISI marked (IS:3419-1988) accessories, round tiles, 1.2 mm thick Hot Dipped Galvanized Modular Box with earth terminal, 10A Modular switch,Modular face plate with grid plate, 3 pin ceiling rose / Holder /3 way connector, screws, making connections, testing etc. as required. For specification of copper Conductor, Phenolic Laminated sheet's & Electrical/ Wiring accessories refer Chapter E - 04, E - 05 & E - 07 |
| 198 | Short point (up to 3 mtr.) |
| 199 | Medium point (up to 6 mtr.) |
| 200 | Long point (up to 10 mtr..) |
| 201 | Wiring of twin control light point with 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper conductor 1.1 kV grade and 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper earth conductor 1.1 kV grade (IS:694) in recessed ISI marked MMS ( IS:9537 P - III ) PVC conduit & it's ISI marked (IS:3419-1988) accessories, round tiles, 2 Nos Hot Dipped Galvanized M.S Modular box of 1.2 mm thick with earth terminal,2 Nos10 A two way Modular switch, 3 pin ceiling rose / holder / 3 way connector ,Modular face plate with grid plate, screws, making connections, testing etc. as required. For specification of copper Conductor, Phenolic Laminated sheet's & Electrical/ Wiring accessories refer Chapter E - 04, E - 05 & E - 07 |
| 202 | Medium point (up to 6 mtr.) |
| 203 | Long point (up to 10 mtr..) |
| 204 | Wiring of 3/5 pin 6 amp. Light plug point with 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper conductor 1.1 kV grade and 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper earth conductor 1.1 kV grade(IS:694) in recessed ISI marked MMS ( IS:9537 P - III ) PVC conduit & it's ISI marked (IS:3419-1988)accessories, Hot Dipped Galvanized Modular box of 1.2 mm thick with earth terminal, 10 A modular switch, 3/5 pin 6 A modular socket, Modular face plate with grid plate, screws, making connections, testing etc. as required. For specification of copper Conductor, Phenolic Laminated sheet's & Electrical/ Wiring accessories refer Chapter E - 04, E - 05 & E - 07 |
| 205 | ON Board |
| 206 | Short point (up to 3 mtr.) |
| 207 | Medium point (up to 6 mtr.) |
| 208 | Long point (up to 10 mtr..) |
| 209 | S&F following sizes (dia.) of ISI marked virgin material MMS ( IS:9537 P - III ) PVC conduit along with ISI marked (IS:3419-1988) accessories as required in recess including cutting the wall, covering conduit and making good the same as required. |
| 210 | 20 mm |
| 211 | 25 mm |
| 212 | 32 mm |
| 213 | Supplying and drawing FR PVC insulated & unsheathed flexible copper conductor as per PWD specification for electrical Works with ISI marked (IS:694) and as per IS 8130 : 2013 of 1.1 kV grade . Wire should be made from 99.90 % purity copper, class 5 stranding in acc. to IS:8130/IEC 60228 for lower watt loss , oxygen free for less chances of oxidization, insulation PVC type A/C/D , flame retardant as per IS 10810-53, better amperage rating as per IS:3961 part 5, in existing surface or recessed PVC/ MS conduit/casing capping making connections with Copper Lugs of suitable size, Ferrules,testing etc. as required. OEM Must have its own in house NABL lab setup for all testing facilities for wires. |
| 214 | 3x 1.5 sq.mm (For Extra Point Wiring) |
| 215 | 2 x 2.5 sq. mm. + 1x1.5sqmm (For Light & emergency circuit) |
| 216 | 2 x 4.0 sq. mm. + 1 x 2.5 sq. mm. (For Power & AC Circuit) |
| 217 | 4 x 6.0 sq.mm (For Sub Mains) |
| 218 | 1 x 4.0 sq.mm (For Earthing) |
| 219 | 4 x 10.0 sq.mm (For Sub Mains) |
| 220 | 1 x 6.0 sq.mm (For Earthing) |
| 221 | 4 x 16.0 sq.mm (For Sub Mains) |
| 222 | Supplying and drawing PE Insulated & PVC Sheathed unarmoured telephone cable with 0.5 mm dia. Solid Annealed electrolytic grade bare Copper Conductor as per IS: 8130/84 &confirming to TEC specification GR / WIR/06-03 March 2002 in existing surface or recessed conduit/casing capping. including ferruling on each pair for Identification etc. as required. |
| 223 | 2 pair |
| 224 | 20 pair |
| 225 | Supply and Laying of PE Insulated jelly filled Armoured Telephone Cable. with 0.6 mm thick Solid Annealed Bare Copper Conductor and confirming to TEC specifications confirming. to DOT GR/CUG-01/Aug.2003 in existing pipe / open trench / Cable tray / on surface including making necessary connection, testing etc. as required of size. |
| 226 | 20 pair |
| 227 | 50 pair |
| 228 | 100 pair |
| 229 | P & F 1.2mm thick M.S. Recessed fan box, hexagonal/ round of size 130 mm dia, depth 75mm, 12 mm dia rod fan hook with 100 mm length extended on each side . All as per pre approved by Engineer in charge. |
| 230 | Providing & Fixing of 240/415 V AC MCB with positive isolation of 10 kA breaking capacity (B/ C/D tripping characteristic as per type of load and site requirement) 4 KV impulse withstand voltage, ISI marked IS 8828(1996) / conforming to IEC 60898-1 2002, IEC 60947-2, low watt losses, trip free mechanisum , energy limiting of class 3 as per IEC, minimum phase termination capacity of 35sq.mm. , conductor line load reversibility , IP 20 contact protection and fitted in existing distribution board/sheets, minimum electrical operation 20,000 upto 20 A rating and 10,000 upto 63 A, 5000 for 80 A & above rating including making connections, testing etc. as required. OEM shall have submit NABL / CPRI / ERDA accrediated lab type test reports & All as per pre approved by Engineer in charge. |
| 231 | Single pole MCB (With B/C curve tripping Characteristics) |
| 232 | 6 A to 32 A rating |
| 233 | Four pole MCB (With B/C curve tripping Characteristics) |
| 234 | 40 A rating |
| 235 | 50/63 A rating |
| 236 | Providing & Fixing of 240/415 V Residual current circuit breaker (RCCB) conforming to (IS:12640-1)/ IEC 61008 -1 , rated 4 KV impulse withstand voltage truly current operated and shall operate on CBCT mechanisum, provision for pad lock, min. operation 10,000 upto 63 A rating and 5000 for 100 A rating and minimum phase termination capacity of 35 sq.mm. rigid wire , IP 20 contact protection with existing distribution board / sheet including making connections, testing etc. as required. OEM shall have submit NABL / CPRI / ERDA accrediated lab type test reports & All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR |
| 237 | Two pole 100/300mA sensitivity |
| 238 | 40 A rating |
| 239 | 63 A rating |
| 240 | Providing & Fixing of Recessed/surface mounting heavy duty horizontal type Double Door ( Metal / Glazed )Distribution board with Metal end box made out from Galvanized steel / CRCA sheet not less then 1.2 mm thick conforming to IS-8623-1 & 3 / IEC 61439- 1 & 3, powder painted complete with reversible door (for double door DB only )100 amp. insulated copper bus bar/shorting link , copper neutral link, copper earth link , color coded interconnecting wire set of suitable rating and din bar,masking sheet, making internal DB terminations with copper lugs, Ferrules, detachable gland plate, including making connections, testing etc. as required. OEM shall have submit NABL / CPRI / ERDA accrediated lab type test reports & All as per pre approved by Engineer in charge. |
| 241 | Metal door (single phase) IK-09 and IP-43 with Metal end box |
| 242 | 12 Way (12+2) |
| 243 | Metal door (Three phase) Per phase isolation, Horizontal IK-09 and IP-43 with Metal end box |
| 244 | 8Way(Incomer 8,Sub Incomer2+2+2) |
| 245 | 12 Way(Incomer 8,Sub Incomer2+2+2) |
| 246 | P&F metal clad / Plastic industrial plug top & socket unit with pin and sleeve type contact on porcelain/ bakelite base in Recessed/surface mounting heavy duty Enclosure made out from Galvanized steel / CRCA sheet not less then 1.2 mm thick conforming to IS-8623-1 & 3 / IEC 61439- 1 & 3. powder painted (without MCB) including making connections, testing etc.as required. |
| 247 | 20 amp, 3 pin + scrapping Earth, 4 Module |
| 248 | 32 amp, 5 pin + scrapping Earth, 8 Module |
| 249 | Providing & Fixing of modular type 120 W Step Fan regulator duly ISI marked (IS 11037:1984 ) with CM/L no. printed made out of unbreakable and fire retardant vergin poly carbonate with brass terminals and captive screws & silver alloy contact tip with IP-20 rating , including all as per pre approved by Engineer in charge,making connections, testing etc. as required. |
| 250 | 5 step fan regulator 2 Module 360 dgree rotating |
| 251 | Providing & Fixing of modular type switch/ bell push duly ISI marked (IS :3854) with CM/L no. printed and made out of unbreakable and fire retardant vergin UV Stabilized Polycarbonate with brass terminals and captive screws & silver alloy contact tip with IP-20 rating ,minimum width of switch toggle( PUSH PART ) should not less then 20mm, including all as per pre approved by Engineer in charge,making connections, testing etc. as required. NOTE- ONLY COMPUTER POINTS SET. |
| 252 | 10 A one way switch (TV) |
| 253 | 16 A one way switch With Led Indicator |
| 254 | Providing & Fixing of modular type lockable feature socket duly made out of unbreakable and fire retardant vergin poly carbonate with brass terminals and captive screws & silver alloy contact tip with IP-20 rating , including all as per pre approved by Engineer in charge,making connections, testing etc. as required. NOTE- ONLY COMPUTER POINTS SET. |
| 255 | 6 A 3/5 pin shuttered socket |
| 256 | 6/16 A shuttered socket |
| 257 | Providing & Fixing of following modular accessories as per PWD specification for electrical Works, made out of unbreakable and fire retardant vergin poly carbonate with brass terminals and captive screws & silver alloy contact tip with IP-20 rating , including all as per pre approved by Engineer in charge,making connections, testing etc. as required. |
| 258 | RJ-11 telephone jack single line |
| 259 | T.V. coaxial socket |
| 260 | 25 Amp. 2 Module Motor Starter with on / off Push button |
| 261 | RJ-45, Cat 6 computer jack with shutter |
| 262 | Blanking plate |
| 263 | Providing & Fixing of following size mounting grid plates with cover plates made from fire retardent UV established high performance engineering plastic suitable for all universal metal boxes for front installation & removal direct fit type complete in all respect.All as per pre approved by Engineer in charge. NOTE- ONLY COMPUTER POINTS SET. |
| 264 | 1/2 Module |
| 265 | 8 Module |
| 266 | Providing & Fixing of Wiring Accessories OEM fabricated following size GI box of 1.2 mm thick with earthing terminal and adjustable floating clamp in recess/ surface suitable for modular accessories as required.All as per pre approved by Engineer in charge. NOTE- ONLY COMPUTER POINTS SET. |
| 267 | 1-2 Module |
| 268 | 6 / 8 module |
| 269 | Supplying and fixing of power plug point with Modular accessories as per PWD specification for electrical Works, on hot dipped galvanized modular box of 1.2 mm thick with earthing terminal/connector on surface or in recessed with suitable size of modular face place with grid plate and cover plate including cost of ISI marked modular 16 amp. Switch (IS :3854) and 6/16 amp. socket outlet (IS:1293) making connection , testing , etc. as required. For specification of Wiring accessories refer Chapter E - 07 related item. |
| 270 | Providing & Fixing of modular type switch/ bell push duly ISI marked (IS :3854) with CM/L no. printed and made out of unbreakable and fire retardant vergin UV Stabilized Polycarbonate with brass terminals and captive screws & silver alloy contact tip with IP-20 rating ,minimum width of switch toggle( PUSH PART ) should not less then 20mm, including all as per pre approved by Engineer in charge,making connections, testing etc. as required. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR |
| 271 | 25 Amp. 2 Module switch With Led Indicator |
| 272 | Providing & Fixing of modular type lockable feature socket duly made out of unbreakable and fire retardant vergin poly carbonate with brass terminals and captive screws & silver alloy contact tip with IP-20 rating , including all as per pre approved by Engineer in charge,making connections, testing etc. as required. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR |
| 273 | 25 Amp. 2 Module Socket |
| 274 | Providing & Laying P.V.C. / XLPE insulated & P.V.C. sheathed Arrmoured Aluminium cable confirming to IS:1554 P-I / IS :7098 P - I of 1.1 KV with H4- Grade electrolytic aluminium conductor confirming to IS 8130 of purity >99.6 %, round / flat strip armouring of cables, Inner / outer sheath confirming to IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray(with cable tie) including testing etc. as required of following size. OEM must have it's own in house NABL accrediated Laboratory for testing procedure as per IS:10810. |
| 275 | 4 x 10.0 sq.mm |
| 276 | 4 x 16.0 sq.mm |
| 277 | 3.5C X25.0 Sq.mm |
| 278 | Supplying and making one end termination with Nickel plated heavy duty brass single compression gland (as per IS 12943-1990)) SIBG type consisting of Check Nut, Gland Body, Metal Washer(3 Nos.), Outer Seal Rubber Ring, Compression Nut, heavy duty aluminium lugs (as per IS 8309 -1993) duly crimped with crimping tool, PVC tape as per IS 8337-1976 of following size of PVC insulated & PVC sheathed/ XLPE aluminium conductor cable of 1100 volt grade as required.All as per pre approved by Engineer in charge. |
| 279 | 4 x 10.0 sq.mm |
| 280 | 4 x 16.0 sq.mm |
| 281 | 3.5 x 25.0 sq.mm |
| 282 | Supplying and making end termination with heavy duty Copper lugs ( ANY type ) confirming to IS 8337 -1976 duly crimped with crimping tool, PVC tape etc of following size.All as per pre approved by Engineer in charge. |
| 283 | 6.0 Sq.mm |
| 284 | 10.0 Sq.mm |
| 285 | 16.0 Sq.mm |
| 286 | Supply, Fabricating & installing following sizes of perforated Powder coated MS cable tray with perforation not more then 17.5% in convenient section including horizontal and vertical bends, reducers tees,cross members and other accessories as required and duly suspended from the ceiling with GI suspenders including GI bolts & nuts , fastners, supports etc. as required.All as per pre approved by Engineer in charge. |
| 287 | 150mm x 50mm x 1.6mm |
| 288 | Providing & Fixing of 400 mm Sweep BLDC technology Oscillating type Wall mounting / Pedestal type fans with Three speed, ON and OFF position, Double Wall bearing with front and back 120 or more ribs guard; Three no. blades, noise level should be <= 75 dB, including fixing with anchor bolts, making connection testing etc. as required. ( With Remote ) All as per pre approved by Engineer in charge. |
| 289 | Wall mounting type with Service value 2.0 CMM /W, Min. Air Delivery 71 CMM |
| 290 | Providing & Fixing of BEE Star rated copper wounded double ball bearing capacitor start, aluminium body & Metallic blade ceiling fan Conforming to all the performance requirements laid down in IS 374:2019 including all amendments, as applicable ; & Carry BIS licensing (i.e. ISI marking) with down rod up to 80 cm with secondary support safety cable ( steel rope) , cotter pin with 3 x 1.5 sq.mm pvc insulated flexible copper conductor making connection testing etc. as required. All as per pre approved by Engineer in charge. |
| 291 | 1200 mm Sweep BEE 3 Star rated (service value >=5.0 to< 5.5 ) |
| 292 | Providing & Fixing of Heavy duty capacitor start, copper wound Double ball bearing 900/1400 RPM single phase Exhaust fan conforming to IS:2312 ISI marked in existing opening including making connections testing etc. as required. All as per pre approved by Engineer in charge. |
| 293 | 300 mm sweep(900/1400 RPM) |
| 294 | Providing & Fixing of IP20 SMD Mid Power LED batten type integrated light fixture made from Powder coated Extruded aluminium housing with in built driver , System lumen efficacy ≥ 110 lm/Watt output, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, CRI >80 , life time of minimum 50000 Burning Hours with , 70% of intial Lumen maintaned till life ends , CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin) , Maximum power consumption should not more than the specified rating and Fixture shall be of BIS standard and trade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. OEM must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79 & LM80) certificate / Report from OEM shall be submitted. All as per pre approved by Engineer in charge. |
| 295 | 1170mm(+/-10%) LED batten with min. lumen output 2200 lm |
| 296 | Providing & Fixing of IP-20 LED Recessed / Surface Mounted, Round / Sqaure SMD Mid Power LED Downlight with power coated die-cast aluminum housing with UV Stabilized non yellowish Diffuser with BIS complience 2.5 KV surge protected Isolated driver, with Short & Open circuit protection, having efficiency > 85% . System Lumen efficacy of ≥ 110 lm / watt, THD < 10 % , Pf.≥0.95, CRI >80, life time of minimum 50000 Burning Hours with , 70% of intial Lumen maintaned till life ends , CCT 3000°K / 4000°K/ 5700°K /6000°K/6500°K (As per ANSI Bin) , maximum power consumption should not more than the specified rating and Fixture shall be of BIS standard and trade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. |
| 297 | Recessed Mounting |
| 298 | Minimum lumen output 1950 lm |
| 299 | Surface Mounting |
| 300 | Minimum lumen output 1950 lm |
| 301 | Providing & Fixing of IP20, 2'x2' LED Surface/ Recessed mounting Mid power SMD type LED Light fixture not less than 50mm housing depth made from CRCA sheet steel housing, high purity / transmisivity UV stabilized Non -yellowish diffuser for uniform light distribution. High efficiency with 4 KV internal/ external surge protection BIS certified isolated driver having efficiency > 85% , with Short & Open circuit protection (Integral with light fixture). System lumen efficacy of ≥ 120 lm/Watt ,THD < 10 % , p.f.≥0.95,CRI >80 , life time of minimum 50000 Burning Hours with , 70% of intial Lumen maintaned till life ends , CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin) , maximum power consumption should not more than the specified rating and Fixture shall be of BIS standard and trade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. |
| 302 | OEM must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79 & LM80) certificate / Report from OEM shall be submitted. All as per pre approved by Engineer in charge. All as per pre approved by Engineer in charge. |
| 303 | Minimum lumen output 4200 lm |
| 304 | P & F Krone module with base frame in the recess / surface made out of 1.2 mm thick sheet steel box, front openable, having locking arrangements duly powder painted,including dressing, ferruling and punching of telephone cable with krone tool etc. as required. |
| 305 | 20 Pairs |
| 306 | 50 Pairs |
| 307 | Supply, Drawing and Testing of 4 pair, 23 AWG Solid Bare Copper wire insulated with PVC, UTP (Unshielded Twisted Pair), Category 6, Class E, 100 Ohm Impedance, Indoor Cable as per latest ammendments of ANSI/TIA/EIA-568 , The copper conductors should be balanced twisted in pairs, seperated by a cross-member fluted pair divider & protected by PVC Jacket. Certified performance in a 4-connector configuration upto 100 Mtrs channel requirements & transmission frequencies up to 250 Mhz. in existing MS/PVC Conduits/casing capping including making connections to Information outlets and Patch Panels with jack & ferruling at both ends for identification with necessary tools for punching, stripping, crimping and testing etc as required complete in all respect. All as per pre approved by Engineer in charge. |
| 308 | Supply and Installation of unsheilded/360 degree sheilded Information outlets made of high impact plastic body with ABS, FR Grade halogen free material with provision for protection against dust in jack, suitable for Cat 6/6A application complying to latest ammendments, According. to Cat. 6/6A channel, It should support channel as well as components requirements of Cat.6/6A standards at frequencies of up to 250 to 500 Mhz. Cat 6/6A unshielded/shielded Jack should be suitable to terminate 4 pair, 23/24 AWG solid/stranded wire diameters, using 100 Ohm unshielded/shielded balance twisted pair cable, the jack should have tooless/impact termination on reliable copper tin plated Insulation displacement contact, with easy lock mechanism, It supports IEC 60603-7-4 and complied with ANSI/TIA/EIA 568 C.2 standard. jack should be RJ11,RJ12 & RJ45 compatible. Should support Ethernet 1.2 Gb/s ATM,Digital video and broadband/baseband analog video, Voice over internet protocal (VOIP) Specifications in existing modular/MS Boxes along with necessory connections as required.All as per pre approved by Engineer in charge. |
| 309 | Cat 6, Un-sheilded Information Outlet |
| 310 | Supply & fixing of square Faceplate for Flush / Surface Mount Information Outlets Single/Dual or Quad Aperture , material should be PC+ABS body, Suitable for RJ45 unshielded/shielded connection modules. Should match with I. O. OEM. Dimensions should be 86mm X 86mm as required complete in all respect. All as per pre approved by Engineer in charge. |
| 311 | Single Aperture |
| 312 | Supply , Installation and Testing of 4 pair, 100 Ohm impedance, Cat 6/6A /Class E/Ea patch cords should be constructed of minimum 23/24 AWG, stranded bare Copper cable with FRPVC/LSZH Jacket, with an enhanced performance by factory moulded RJ45 connectors with strain relief boots as per ANSI/TIA/EIA 568-C.2 suitable for Cat 6/6A application complying to latest ammendments Category 6/6A Standards, According. to TIA568C.2, ISO/IEC 11801, EN 50173, IEC 60603-7-51, EN 60603-7, IEEE 802.3an minimum requirement for 1G BASE-T to 10G BASE-T performance. Patch cords shall be straight thru cable compatible with both T568-A and T568-B wiring schemes, should support IEEE 802.3af / IEEE 802.3at for POE applications, Minimum 750 to 1000 mating cycles in plug contacts for long durability, Should support Ethernet 10GBASE-T, 1.2 Gb/s ATM, Token ring 4/16, Digital video and broadband/baseband analog video, Voice over internet protocal (VOIP).All as per pre approved by Engineer in charge. |
| 313 | 1 Mtr |
| 314 | Supply, Installation, & Testing of 19\\" 1U Rack Mounted/ surface mounted aluminum/ CRCA 1.2mm powder coated, Singlemode glass Fiber Optic Cable Patch panel/LIU loaded with flangless/screwable duplex adapters for ST/E-2000/SC/LC/MT-RJ/PC type, It should have easy removable Top plate with push buttons, there should be a splice tray installed in the Patch panel/LIU which can handle the fiber cores, splice tray should be PC+ABS material, it should include accessories like mounting hardware, gormetts, heat shrink tubes/sleevs, screws, nuts to install the panel for rack/wallmount applications as per requirment complete in all respect. All as per pre approved by Engineer in charge. |
| 315 | 24 Ports |
| 316 | Supply & Installation of IP-20 & IK-08 , UL Listed Wall mounted Double Section Communication enclosure (Rack) made from powder coated (60 to 80 Micron) CRCA sheet, front sturdy sheet steel frame folded from one piece and welded with minimum 5mm toughened glass door,Vertical Mounting Rail 1.6 MM with 'U' Marking , with All round protective channel on the door aperture, lock integrated on front door, top and bottom cover with cable entry provision with gland plates, integrated side walls, 2 pair of 19\\" angles with wall mounting provision on wall. Accessories like: 1 No of 19\\" 1U Horizontal Cable manager, 1 No of 90 cfm 230V AC Fan with 1 mts long cable, mounting hardware , 1 No of 19\\" 1U, mountable socket strips with 5 nos of 5A universal sockets with 2 mts long power chord for supplying power to switches, fans etc along with earth continuity kit, indicator, moulded power supply cable. fixing on wall with Suitable Anchor fastner etc as required.All as per pre approved by Engineer in charge. |
| 317 | 9 U Rack with Width 600 mm & Depth 400 mm + 100 mm |
| 318 | Supply , Installation, Testing and Comissioning of Managed Layer-2 Intelligent 10/100 Ethernet Switch providing 24 x 10/100/1000 MBPS Giga Ethernet ports / with min 2 SFP Giga Ports (provision for Fiber Giga connectivity) with related LAN Base Software including making connections etc as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 319 | Supply , Installation, Testing and Comissioning of Inverter type Air Cooled Hi Wall split type Air conditioners with latest star rating system as per BEE amended upto date complete with Indoor unit(IDU), Out door unit (ODU), surface / concealed copper Refrigerant piping with insulation (closed cell elastomeric nitrile rubber tubular pipe section) upto 3 Mtr (IDU to ODU), copper power cable upto 3.5 Mtr (IDU to ODU), R-32/R-410 Green Refrigerant, wireless Remote control, suitable for working between 230V +/- 10% with low & high voltage cutoff and 50 hz , single phase AC supply capable of performing cooling, dehumidification, air circulation of following capacity with Scroll / rotary compressor. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 320 | 1.0 TR ISEER not less then 4.6 |
| 321 | 1.5 TR ISEER not less then 4.6 |
| 322 | 2.0 TR ISEER not less then 3.8 |
| 323 | Supplying and drawing flexible / stranded bare copper conductor, PVC / XLPE insulated, overall aluminium mylar tape shielded ATC drain wire and outer PVC sheathed industrial Instrumentation (shielded)cables voltage grade 300/500 V as per BS /EN 50288-7 in existing surface or recessed PVC/ MS conduit/casing capping / Cable tray / Open Duct making connections, testing etc. as required. OEM Must have its own in house NABL lab setup for all testing facilities for cables. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 324 | 4 core x 2.5 Sq.mm |
| 325 | Supply, installation, testing and comissioning of interconnecting copper refrigerant piping of DHE Grade C12200- ASTM B68, B75, chemical composition of copper %- 99.0 Min and Phosphorus %- 0.015 to 0.040 . For Annealed copper tube :- Tensile strength = 210 Mpa wih elongation % = 40 Min . Ink Mark Brand Printing on Hard Tubes should be present. duly insulated with tubular elastomeric nitrile rubber FM/UL approved with high water vapor diffusion resistance and low thermal conductivity should be certified 'Class O' in Fire Propagation as per BS 476 Part 6 including chase cutting andfilling with mortar, Slotted channel supports mounted on 10 mm threaded rod at suitable spacing the exposed piping shall be wrapped with glass woven cloth and lag coating for vapour barrier and weather protection. Joints shall be covered with nitrile rubber tape of 3 mm thick complete as required of following sizes. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 326 | 15.9 mm O.D., wall thinkness ≥ 0.8mm (insulation – 13 mm thick) |
| 327 | 12.7 mm O.D., wall thinkness ≥ 0.8mm (insulation – 13 mm thick) |
| 328 | 9.5 mm O.D., wall thinkness ≥ 0.8mm (insulation – 13 mm thick) |
| 329 | 6.4 mm O.D., wall thinkness ≥ 0.8mm (insulation – 13 mm thick) |
| 330 | Supply & fixing MS powder coated stand suitable for 1.0/1.5/ 2.0 Tr outdoor type of Split AC. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 331 | Providing & Fixing of IS : 4985 - 2000 Class -4 (10 Kgf / Sqcm) UPVC drain water piping with fittings (IS:7834 & 10Kgf/sqcm) like elbow, socket, Tee, solvent cement jointing, support with MS hanger on ceiling or recessed in wall with chasing & plastering with 6 mm thick closed cell elastomeric nitrile rubber insulation including leakage testing etc. as required of following Nominal sizes. All as per pre approved by Engineer in charge. |
| 332 | 20 mm |
| 333 | Electrical Work |
| 334 | Providing & Laying P.V.C. / XLPE insulated & P.V.C. sheathed Arrmoured Aluminium cable confirming to IS:1554 P-I / IS :7098 P - I of 1.1 KV with H4- Grade electrolytic aluminium conductor confirming to IS 8130 of purity >99.6 %, round / flat strip armouring of cables, Inner / outer sheath confirming to IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray(with cable tie) including testing etc. as required of following size. OEM must have it's own in house NABL accrediated Laboratory for testing procedure as per IS:10810. |
| 335 | 4C X4.0 Sq. mm (EXT.LIGHTING) |
| 336 | 3C X6.0 Sq. mm |
| 337 | 3.5C X25.0 Sq.mm |
| 338 | 3.5C X70.0 Sq.mm |
| 339 | 3.5C X150.0 Sq.mm |
| 340 | 3.5C X300.0 Sq.mm |
| 341 | 400.0 Sq. mm |
| 342 | 3.5 core |
| 343 | 630.0 Sq. mm |
| 344 | 1 core |
| 345 | 300.0 Sq. mm |
| 346 | 1 core |
| 347 | Supplying and making one end termination with Nickel plated heavy duty brass single compression gland (as per IS 12943-1990)) SIBG type consisting of Check Nut, Gland Body, Metal Washer(3 Nos.), Outer Seal Rubber Ring, Compression Nut, heavy duty aluminium lugs (as per IS 8309 -1993) duly crimped with crimping tool, PVC tape as per IS 8337-1976 of following size of PVC insulated & PVC sheathed/ XLPE aluminium conductor cable of 1100 volt grade as required.All as per pre approved by Engineer in charge. |
| 348 | 3 x 6.0 sq.mm |
| 349 | 3.5 x 25.0 sq.mm |
| 350 | 3.5 x 70.0 sq.mm |
| 351 | 3.5 x 150.0 sq.mm |
| 352 | 3.5 x 300.0 sq.mm |
| 353 | 1 x 300.0 sq.mm |
| 354 | 1 x 630.0 sq.mm |
| 355 | 3.5 x 400.0 sq.mm |
| 356 | Supplying and making end termination with heavy aluminium lugs ( Pin / ring type ) confirming to IS 8309 -1993 & IS 8337-1976 duly crimped with crimping tool, PVC tape etc of following size.All as per pre approved by Engineer in charge. |
| 357 | 6.0 Sq.mm |
| 358 | P/Laying ISI marked P.V.C. insulated submersible cable confirming to(IS:694) and as per IS 8130 : 2013 of 1.1 kV grade . Wire should be made from 99.90 % purity copper, stranding in acc. to IS:8130/IEC 60228 for lower watt loss , oxygen free for less chances of oxidization, insulation PVC type A/C/D , flame retardant as per IS 10810-53, better amperage rating as per IS:3961 part 5, existing pipe / open trench / Cable tray / on surface including making connection etc. as required. |
| 359 | 6.0 Sq.mm 3 core flat / Round |
| 360 | P / L of Double wall corrugated HDPE pipe confirming to IS : 16205 P-24, Stiffness Class 750 N, Externally corrugated and having smooth surface inside with HDPE Coupler, Elbow, Tee at required Depth below the ground for laying cable of following Nominal Outer dia. MFR Test report from NABL accrediated is to be submitted.(Excavation of Earth & Back filling with compaction is to be Paid Extra)All as per pre approved by Engineer in charge. |
| 361 | 110 mm |
| 362 | 160 mm |
| 363 | S/F cable route marker with 10cm x 10cm x 5mm thick or 10 cm dia. G.I.plate with inscription thereon, bolted/welded to 35mm x 35mm x 5mm angle iron, 60cm long and fixing the same in ground in C C ( 1:3:6 ) as required. All as per pre approved by Engineer in charge. |
| 364 | Providing & Laying XLPE insulated three core Armoured Aluminium cable for working voltage 11 K.V.(E) confirming IS :7098 P - 2 with H4- Grade electrolytic aluminium conductor confirming to IS: 8130 class-2 of purity >99.6 %, Insulation Screening: Extruded Semiconducting Compound followed by helically wrapped Copper Tape, round / flat strip armouring of cables , Inner / outer sheath PVC type ST-2 confirming to IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray including testing etc. as required of following size. OEM must have it's own in house NABL accrediated Laboratory for testing procedure as per IS:10810 All as per pre approved by Engineer in charge. |
| 365 | 3 core 185.0 Sq.mm |
| 366 | Providing & making heat shrinkable type indoor/outdoor/straight through terminations/ joint kit suitable for 11 KV / 33 KV (Earthed) cable with required components, prepration of cable ends. Type test report should be as per IS13573:2011 which covered all sequence for table 2 for termination kit and table 3 for streight through joint inclusive thermal & dynamic short circuit test, humidity test, soil fog test. Cross linking shall be done out side factory with E- beam/ peroxide technology. Extrusion process shall be in house OEM within same vicinity. including testing etc. as required of following sizes. All as per pre approved by Engineer in charge. |
| 367 | 11 KV End Termination Kit Indoor type |
| 368 | 3 core 120/150/185 Sq.mm |
| 369 | 11 KV End Termination Kit Outdoor type |
| 370 | 3 core 120/150/185 Sq.mm |
| 371 | EARTHING |
| 372 | Plate Earthing as per IS:3043 with copper Earth plate of purity >95% of size 600mm x 600mm x 3.0mm by embodying 3 mtr. below the ground level with 20 mm dia. G.I. 'B' class watering Pipe ,including all accessories like nut, bolts, reducer, nipple, wire meshed funnel, and Heavy duty weather proof poly-propylene earth pit chamber with lockable Jam free lid suitable for safe working load 5000 Kg or more of size Top Dia. 225 to 260 mm, Bottom Dia 300 to 350 mm. and Height 250 to 300 mm. and embodying the pipe complete with alternate layers salt and coke/ charcoal, testing of earth resistance for value of 5 ohms or less as required & must record by engineer in charge during site visit and ensure to enter in measurment book. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 373 | Plate Earthing as per IS:3043 with Hot dipped G.I. Earth plate of size 600mm x 600mm x 6.0mm by embodying 3 to 4 mtr. below the ground level with 20 mm dia. G.I. 'B' class watering Pipe ,including all accessories like nut, bolts, reducer, nipple, wire meshed funnel, and Heavy duty weather proof poly-propylene earth pit chamber with lockable Jam free lid suitable for safe working load 5000 Kg or more of size Top Dia. 225 to 260 mm, Bottom Dia 300 to 350 mm. and Height 250 to 300 mm. and embodying the pipe complete with alternate layers salt and coke/ charcoal, testing of earth resistance for value of 5 ohms or less as required & must record by engineer in charge during site visit and ensure to enter in measurment book.All as per pre approved by Engineer in charge. |
| 374 | Supply and installation of high tensile low carbon steel rod molecularly bonded with 99.9 % Copper thickness (250 microns) and confirming to UL 467, IS/IEC 62561-2 of following size and length and as per point mentioned (a), (b), [c), (d), (e) below :- |
| 375 | (a) Bore a hole of dia. 100 mm of required length, Place the rod in the centre of Hole |
| 376 | (b) filled with anti corrosive conductive compounds with the permanent sealings at both the ends, CPRI/ ERDA tested with RMS capacity of minimum 30 KA for withstanding 1 second .To ensure the moisture content and electrical conductivity, 25 kg for 2000 mm & 50 Kgs for 3000mm of resistance lowering earth enhancement material shall be used as a backfill compound. The compound shall be tested form NABL acredeated lab for low resistivity ( less than 0.12 Ohm - meter ) & high conductivity in nature with carbon as a major content as per referance of IS 3043-1987,IEEE 80-2013 (clause 14.5d) , IEEE 837 & IER 1956 with latest amendemnts |
| 377 | © Connect the rod with copper Strip/Conductor/Wire with suitable clamp made from tinned copper and SS 304 Bolt |
| 378 | (d) Place Heavy duty weather proof poly-propylene earth pit chamber with lockable Jam free lid suitable for safe working load 5000 Kg or more of size Top Dia. 225 to 260 mm, Bottom Dia 300 to 350 mm. and Height 250 to 300 mm. |
| 379 | (d) Testing of earth resistance for value of 5 ohms or less as required & must record by engineer in charge during site visit and ensure to enter in measurment book. |
| 380 | (e) Test certificates for confirming above standards from OEM is mandatory. All as per pre approved by Engineer in charge. |
| 381 | 25 mm thick and 3 Mtr. Long |
| 382 | Supply & Laying following size earth strip in horizontal or vertical run in surface by means of Earth strip DMC Insulator including riveting/ soldering/ welding, Jointing shall be done by overlapping and with 2 set of Brass (for Cu strip) / GI (for GI Strip) nut bolt & spring washer spaced at 50cm making connection etc. as required.All as per pre approved by Engineer in charge. |
| 383 | 40mm x 6mm copper strip |
| 384 | 25mm x 3mm G.I. ( Hot Dipped ) Strip |
| 385 | Supply & Laying following size earth wire in horizontal or vertical run in ground/surface/recess including riveting, soldering, saddles, making connection with GI/Cu purity purity >95% thimble etc. as required. All as per pre approved by Engineer in charge. |
| 386 | 8 SWG G.I. ( Hot Dipped ) Wire |
| 387 | P & F of Heavy duty weather proof poly-propylene earth pit chamber with lockable Jam free lid suitable for safe working load 5000 Kg or more of size Top Dia. 225 to 260 mm, Bottom Dia 300 to 350 mm. and Height 250 to 300 mm. All as per pre approved by Engineer in charge. |
| 388 | Supply installation testing & Commissioning of Copper wound distribution Transformer of following rating and % Impedance, 11/0.433KV Delta-Star Connected, Vector Group Dyn 11, ONAN Cooled losses as per IS 1180 part I 2014 (Fourth Revision) Level-1, with boltless core design including standard accessories like conservator with prismatic oil level gauge , silica gel breather, Bucholz relay, pressed steel radiator fins, Radiator Valve(above 800 Kva) Suitable size HT cable box, LT cable box with Busbar connection for outgoing cables, Off -LTC (+/- 2.5%, +/- 5% to - 7.5% ), temperature rise of 40 degree C in oil / 45 degree C in winding , drain valve, Air release device, Dial type Oil & Winding Temperature gauge with alarm & trip contacts, first filling of transformer oil as per IS :335-1953 , Epoxy primer and PU based paint as Top coat, Unidirectional rollers for rating upto 800 kva & bi- directionalabove 800 Kva rollers with locking arrangement etc. as required. The Transformer shall be subjected to routine factory tests (as per IS:2026 and IS:1180) including Temperature rise test in OEM's own lab shall be witnessed by Department engineer Physically. |
| 389 | Transformer shall be tested from CTL of discom before charging of transformer & complete installaion must be certified from Electrical Inspectorate office as per Indian Electricity rule, (CTL testing charges and Electrical Inspection charges shall be reimbursed by the department to the contractor)Following tests shall be carried out on each transformer at site by OEM enginer in presence of department authorised representative:- a) Ratio test on each tapping.b) Resistance of windings at principal and all tapings.c) Insulation resistance of the winding between HV to earth / HV to LV / LV to earth.d) Vector group test.e) Magnetic Balance test. All as per pre approved by Engineer in charge. |
| 390 | 800 KVA with % Impedance 4.5 |
| 391 | Supply & Installation of D.P. Structure With AIR BREAK SWITCH having following specifications A, B, C, D, E. All as per pre approved by Engineer in charge. |
| 392 | A) Double pole structure on 2 no ISMB ( I beam ) of size 150 x 75 mm, 10 mtr length using 7 no MS channel each of size 100 mm x 50 mm x 2500 mm complete in all respect with nuts, springs washers, clamps as required. |
| 393 | D) 3 piece non linear resistor type. lighting arrestor of approved make suitable for 3 wire, 11kv Overhead line with rated voltage of 9kv rms & nominal discharge current rating of 5 ka & complete with galvanized clamping arrangement GI bolts, nuts, washer etc as required. |
| 394 | E) 3 no 11kv ACSR conductors mounted on pin type insularors as required. 6.GENERAL:The go shall be operated by hand operated liver properly earthed with provision for locking mounted at 3’ |
| 395 | B) Off load type gang operated 3-pole vertical flute type switch suitable for 11KV ; 400A ,3-ø, central post rotating double break isolator complete with MS hardware , copper moving & fixed contact ,assembly of 9 nos pin insulator ,GI pipe of suitable length for operation. |
| 396 | C) 3nos Vertical / Horizontal mounted 11kv horn gap fuse set /drop out 11kv barrel fuses mounted on 6no pin insulators |
| 397 | SITC of 11kV 630 Amps 21KA for 3 Sec. SF6 insulated, outdoor duty (IP54) , Extensible / Non extensible type Ring main unit (RMU) manually operated in combination of VCB modules and Load Break switch consisting of Copper busbar in SF6 insulated 304 (Non-Ferrite Non-Magnetic Grade) stainless steel enclosure of thickness 2.5mm with manometer. The HV switchgear and control gear should be confirming to IEC-62271-100, IEC-62271-200-2003 & IEC-60694-1996. The RMU should be internal arc tested for 21KA for 1Second with IAC-AFL classification for gas tank. Vacum Interrupter of VCB should be RMU Manufacturer’s own make. Each feeder of RMU should have voltage presence indicator. . and compring of followings:- 1 no. microprocessor based Self powered numerical relay with over Current/ earth fault & short circuit protection with each VCB feeder. - 3 Nos. Protection CT shall be of Burden 2.5VA, ratio 50/1A, Class of Accuracy class 5P10 for O/C and E/F protection for each VCB.- 1 No. Manometer for each tank,- 1 nos. Fault Passage indicator,-Right angle boots for all the feeder Modules All the type test certificates as per IEC from Third party NABL / CPRI / ERDA accrediated lab to be submitted. (Cost of RCC Foundation / Steel Structure to be paid Extra) All as per pre approved by Engineer in charge. |
| 398 | Extensible 3 way RMU with 1 no. VCB & 2 No. Load Break Switch |
| 399 | Extensible 2 way RMU with 1 no. VCB & 1 No. Load Break Switch |
| 400 | SITC of following capacity IK10 Sandwich Type Rising Mains / Bus Duct Confirming to IEC 61439 part 1 & part 6 standard & IS 8623 P-II and Manufactured in India for use on 3 phase 4 wire , 50% internal earth , 415 volts, 50Hz A.C. supply , class F insulation, rated insulation voltage 1000V, impulse withstand voltage 12 KV, min. seismic zone 4 as per IS1892, with IP-54 / IP-66 (With Canopy) enclosure made of 1.6mm thick sheet steel duly powder coated in convenient sections complete with 4 Nos aluminium (with 6101 or 63401 grade) bus bars, necessary joints & expansion joints, fire barrier at each floor, provision of tapping at every metre, continuous earthing with 2 Nos aluminium strip of suitable size (one on each side) including, G.I. clamping brackets, angle iron bracket, steel fasteners, connecting to earthing system including making opening in RCC / Brick Masonary and repairing the same etc. as required. Type Tests reports like (i) Short Circuit Test (ii) Degree of Protection (iii) Temperature rise test of Rising main in CPRI/UL/ASTA accrediated lab will be submitted by OEM. |
| 401 | Routine test as per OEM's QAP in It's own Manufacturing facility in India shall be witnessed by department Engineer virtually / Physically. Complete Installation of Rising Mains shall be Vetted by Manufacturer before Comissioning. All as per pre approved by Engineer in charge. |
| 402 | Out Door Bus Duct IP66 with Canopy |
| 403 | 1250 Amps 65kA SC for 1 sec |
| 404 | SITC of HT metering cubical panel as approved By DISCOMs fabricated out of 18 SWG CRCA sheet steel in two compartment & MS angle of size 60mmX 6mm having provision for Following: (i)Provision for fixing Trivector / Import - Export Meter (To be supplied by DISCOMs) (ii)Provision for fixing of combined CT PT Set with Copper strip for Connection (To be supplied by DISCOMs), (iii)Test terminal Block, (iv) 6mm thick Bakelite sheet on all sides, (V) 3/6 corex 1.5 / 2.5 Sq.mm copper cable for interconnections, etc. as required. All as per pre approved by Engineer in charge. |
| 405 | Earth work in excavation/ by mechanical means (Hydraulic Excavator) / Manual means over areas (exceeding 30 cm in depth, 1.5m in width as well as 10 sum on plan) including disposal of excavated earth, lead upto 50 m and lift upto 1.5 m, disposed earth to be levelled and neatly dressed: |
| 406 | Random rubble masonry with hard stone in foundation and plinth including levelling up with cement concrete 1:6:12 (1 cement : 6 coarse sand : 12 graded stone aggregate 20 mm nominal size) upto plinth level with Cement Mortar 1:6 ( 1-Cement : 6-Sand). |
| 407 | Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete upto plinth level. |
| 408 | Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level |
| 409 | M10 1:3:6 (1 Cement : 3 coarse sand (zone-III) derived from natural sources : 6 graded stone aggregate 20 mm nominal size derived from natural sources) |
| 410 | M15 grade Nominal Mix 1:2:4 (1 cement : 2 coarse sand (zone-III) derived from natural sources : 4 graded stone aggregate 20 mm nominal size derived from natural sources) |
| 411 | Plaster on new surface on wall in cement sand mortar 1:4 including racking of joints etc. complete fine finish : |
| 412 | 20mm thick |
| 413 | 12mm thick |
| 414 | Finishing wall with water proofing cement paint of approved brand and manufacture and or required shade to give an even shade including all scaffolding: |
| 415 | New work (Two or more coats applied @ 3.84 kg/10 sqm). |
| 416 | Providing and fixing welded mesh/expanded metal mesh 25 mmx 25 mm x 3mm in frame work, flat iron beading 20x3mm including top cross laps inside and out sides welding, iron bolts, crews, clips etc. including two coat of red oxide and two coat of enamel paint or more required complete with frame work with 50 X 50 X 6mm angle iron post 30 cm in ground embeded in cement concrete 1:3:6 (30X30X45cm) at corner and every three mtr including painting with one coat of primer and two coat of enamel paint work will be done as per direction of engineer incharge of size complete in all respect. All as per pre approved by Engineer in charge. |
| 417 | Gravelling of Transformer / RMU Yard with 100 mm Height Gravels of Size 20 to 25 mm including leveling, Dressing etc. as Required. |
| 418 | SITC of Radiator Cooled and Turbo charged Silent DG Set (As per latest CPCB emission norms) having specifications as per A, B, C, D, E, F,G,H & I |
| 419 | A) 1500 RPM Diesel Engine conforming to BS:649/5514 of suitable BHP (up to 82.5 kVA 6 cylinder or Below required, 125 kVA & Above ratings 6 cylinder or above required ) capable of taking 10% over loading for one hour after 12 hours of continuous operation., Dry exhaust mainfold with Hospital grade silencer and catalytic convertor(isolated from main DG chamber), up to 3 M exhaust piping (with LRB insulation & Alum. cladding ) as required . |
| 420 | B) AC Brush less SPDP Alternator conform to BS 5000 (part 99) or IS/IEC 60034-1. . Alternator shall be self regulated with standard Alternator Protection( Over voltage , over speed & under voltage, under speed warning & shutdown).Engine & Alternator mounted on a common base Frame & coupled through a flexible coupling or close coupled |
| 421 | C) CPCB / ARAI approved Standard canopy with Weatherproof, powdercoated Accoustic enclosure for DG set for sound attenuation fabricated from 1.6 mm CRCA sheet steel (structure) with sidewall fabricated from 1.6 mm CRCA sheet & filled with glasswool (96Kg/m3) / Foam. as per IS8183 the doors of 28/40/50/85mm thick as perrating and fabricated from 1.6mm CRCA sheet packed with accoustic material, All doors/opening are sealed with neoprene /EPDNgaskets. The DG Set has Inbuilt / External in fuel tank to run 6 to 8 Hrs as per OEM standard, with protection and tripping of DG set against temperature of more than 50 degree centigrade. |
| 422 | D) Electronic / Mechanical governor, Manual & electric Start ,Batteries with battry charger, Engine instruments panel,AVM pads All controls for operation of DG set are from outside the enclosure with DG control panel having Microprocessor based Genset monitoring like Running Hour, RPM, Low Lube Oil tripping & control system, Panel mounted MCCB/ACB of suitable rating, Ammeter, Voltmeter, PF meter, frequency meter, KWH meter,digital fuel display meter, Ind.lamps etc. mounted inside enclosure , visible and accessible from outside. The enclosure should be suitable for following capacity DG sets and alternator. Noise level shall be less than 75 dB at a distance of 1 Mtrs. duly certified by authorised agency etc. complete in all respect of following capacity : |
| 423 | E) (i) Accoustic glass wool wall thickness should not be less then 40mm and not less then 20mm PU foam upto rating 100 KVA. (ii).Accoustic glass wool wall thickness should not be less then 65mm and not less then 50mm PU foam upto rating 250 KVA. (iii)Accoustic glass wool wall thickness should not be less then 100mm for rating above 250 KVA. |
| 424 | F) First filling of the fuel tank shall be done by contractor and the prevailing fuel cost at that time shall be reimbursed to the contactor by department. |
| 425 | G) Servicing Contract of DG Set from OEM's Authorised Service Dealer as per OEM guidelines during the DLP period shall be done by contractor including all consumables, actual charges shall be reimbursed to the contractor by End User Department. |
| 426 | H) Manufacturer / OEM must have its authorized service dealer in Rajasthan. Which can provide service within 6 Hours of compalint registration. |
| 427 | I) DG set will be offered for Inspection and Testing at Manufacturer's Works in presence of Departmental Engineers. All as per pre approved by Engineer in charge. |
| 428 | 500 KVA at 0.8 pf 415V 50Hz 3-ǿ |
| 429 | SITC of PLC Based Auto main failure (AMF) Panel fabricated from CRCA sheet steel 2 mmThick , Powder coated finish , Engine Start & Stop commands, control Relays , Ammeter & Voltmeter with selector switches, Control & 2 nos 4 pole Power Contactors with 2 no. of required size 4 pole MCCB, Timers, Electronic Hooter ,Visual & Alarm indication for faults, UPS, operator interface panel complete in all respect suitable for following capacity DG sets: Appropriate Test Certificate/ report of product/accessories from OEM/Panel Manufecturer shall be submitted. All as per pre approved by Engineer in charge. |
| 430 | 500 KVA |
| 431 | Providing, Fixing, Jointing, Testing & Commissioning of Medium duty MS B class pipes conforming to IS 3589 / 1239 part-I for DG Exhaust applications (beyond 1.5 Mtr. length) including cutting, welding etc & fittings like elbows,flanges, tapers, reducer, gaskets etc. fixing the pipe on the wall/ceiling with suitable clamps, hanger and nuts bolts . including the cost of thermal insulation with 50 mm thick layers of LRB rock wool as per IS : 8183-1993 (64 kg/m3 density) & 26 SWG aluminium sheet claddings etc complete as required complete in all respect. (Cost of Steel Structure for Exhaust pipe will be paid Extra). All as per pre approved by Engineer in charge. |
| 432 | 200 mm dia |
| 433 | MOTOR PUMP SET |
| 434 | SITC of Radial / mixed flow ISI marked water and anti-corrosive liquid filled submersible motor pump sets suitable for 100/150mm dia borewell. The size of adopter fixed on top of the motor should exceed the top of coupler , for safegaurd the coupler. The construction material of motor and pump should match IS: 8034 : 2018 and IS: 9283 guideline. The radial flow pumpset should operate at 5 star energy efficiency level of BEE and mixed flow pump set should operate at 3 star energy level of BEE, accompained by valid BEE certificate. Motor should be IE2 class as per IEC 60034-2-1: 2007, IEC 60034-30: 2008, & IS12615:2011 with required accessories including making connection suitable for Bore well. The job includes labour part of lowering of riser pipe G.I./ H.D.P.E. with rope, cables & pump, installation of complete fitting and accessories, jointing of electrical cables up to Starter. All labour for testing of submersible pumps set and supply of water to water mains, complete in all respect. OEM shall have submit NABL / CPRI / ERDA accrediated lab type test certificate before execution. All as per pre approved by Engineer in charge. |
| 435 | 150 mm diameter Submersible pump shall have following HP Rating, phase, Head range, Discharge range respectively. |
| 436 | 7.5 HP, 3-Ø, (76 - 96)Mtr, (285-180) LPM |
| 437 | Providing & Fixing of CI foot valve complete in all respect. All as per pre approved by Engineer in charge. |
| 438 | Handi type (for open well) 80/ 100 mm |
| 439 | Supply & fixing of GI pipes confirming to IS : 1239 P - 1 ( 2004 ) with flanges duly screwed & welded including rubber washer, nuts & bolts of 8mm dia complete in all respect.All as per pre approved by Engineer in charge. |
| 440 | B class 50mm dia |
| 441 | Providing & Laying of Polypropylene rope Confirming to IS:5175 for submersible pump of following sizes. complete in all respect. All as per pre approved by Engineer in charge. |
| 442 | 16mm (suitable above 50mm & up to 75mm OD pipe) |
| 443 | SITC of Monoblock motor pump set ISI marked (IS:9079-2002) with TEFC motor, motor should be IE2 class as per IEC 60034-2-1: 2007, IEC 60034-30: 2008, & IS12615:2011. with Stainless steel Impellor, Stainless steel shaft, Mechanical seal, Single/Three phase ( 240 - 440 V ) permanent split capacitor type (PSC), fitted with thermal overload protection, Including cost of hardware etc on existing platform complete. Pump shall have following HP Rating, phase, Head, minimum Discharge respectively complete in all respect. OEM shall have submit NABL / CPRI / ERDA accrediated lab type test certificate before execution. All as per pre approved by Engineer in charge. |
| 444 | 5.0 HP, 3-Ø, (24-44)Mtr, (680-370) LPM |
| 445 | MAIN DISTRIBUTION PANELS |
| 446 | SITC of IP-42 and general construction confirming to IS:8623 : 1993, wall/ free standing floor mounted dust and vermin proof compartmentalised cubical panel as specifications and Other parameters required as per point (a) ,(b), (c),(d), (e), (f), (g), (h) as below:- |
| 447 | (a)Thickness of CRCA sheet shall be 2.0 mm, cable alley compartments having concealed hinged type doors with key type lock with / without detachable extension type structure. Removable 3 mm. thick sheet steel gland plates with appropriate size of knockouts for cables shall be provided |
| 448 | (b)complete panel shall undergo a process of degreasing, Water rinsing, Activation, derusting, pickling in acid bath, phosphatising & shall be subjected to nine tank process and then Powder coated with approved shade of minimum 70 microns on both side of panel. The panel having PE foam/ Neoprene rubber gasket of not less than 3mm thickness ,required hardware , concealed hinged door with key type locking arrangement for equipment/switchgear earthed with 2.5 sq.mm braided copper wire. |
| 449 | [c) Interconnection between bus bar and switchgears /cable shall be rigidly supported and made out by flexible copper wires (up to 63 amp ) and by solid bus bar (>63 amp ) . control wiring will be carried out with 1.5 Sq.mm, Earth wire with 2.5 Sq.mm and CT with 2.5 sq.mm flexible copper wire only. All joints / interconnections of copper bus bar shall be dully tinned . Clearance between main bus bar and risers / metal parts shall be at least 10 mm additional to width of bus bar Bus bar is insulated by Heat Shrinkable sleeves . Earth and Neutral bus bar shall be half of the size of phase bus bar. ( Cost of Bus bar / Flexible wire for Interconnection between Main busbar and Switchgear is to be Paid Extra ) |
| 450 | (d)Wiring between components within switchgear and Incoming / outgoing cable shall be done through the terminal block only. Direct connection shall not be permitted. Each terminal block shall be one piece moulded, barrier type, 650 volt grade, complete with washers, heads, studs with two nuts and identification strips and shall have adequate continuous current rating. For tap-offs, adjacent terminals with shorting strips shall be used. 10% Spare terminal blocks shall be provided. Wire identification on marking strip shall correspond to the designation of the wiring diagrams. All wire terminals on the equipment shall also be marked with designation corresponding to those of the wiring diagram. |
| 451 | (e)All wiring shall be enclosed in plastic channels and neatly bunched and closed in metering chamber, Wiring between terminals of various devices shall be ‘point to point’ (no wire splitting or tee connections) with wires neatly trucked along the back of the panels, adequately supported to prevent sagging. |
| 452 | (f)Floor mounted panel shall be mounted on Base frame of ISMC channel size 100 x 50 x 5 mm ( to be paid Extra ) |
| 453 | (g) Tests: The insulation resistance (with 1000 V Megger) and High voltage Power frequency test (by applying a voltage of 2.5KV for one minute) shall be measured between phases, between phase and neutral and between phase and earth. both before and after high voltage power frequency test. The insulation resistance shall not be less than three megaohm. CT Secondary current injection test shall also be carried out. |
| 454 | (h) only outer surface area on all sides shall be measured & panel to be fabricated only from CPRI approved fabricator only (CPRI Test certificates to be submitted)All as per pre approved by Engineer in charge. |
| 455 | Supplying and fixing of Aluminium (IEC 60105 ISO 209-1,2) / Copper (IEC 60028) bus bar by means of SMC / DMC type insulator with standard short circuit withstand capacity , high tensile nuts and bolts spring washers in existing panel including bending , cutting in required shape and size and colour coding with heat shrinkable PVC sleeves. All as per pre approved by Engineer in charge. |
| 456 | Electrolytic grade Aluminium bus bar 6010 grade |
| 457 | Providing & Fixing of IS: 13875 & IEC :61326 confirming LED Digital type (up to 500) V range Volt meter / Direct- Ammeter / CT oertated ammeter/ Frequency meter / KWH meter / Multi Function Meter / Power analyzer of class 1 accuracy as per IS : 1248 of size 96mm x 96 mm including making connection by PVC insulated copper conductor with PVC sleeves / channel etc. as required. All as per pre approved by Engineer in charge. |
| 458 | Three phase with universal Auxiliary supply + AMP + HZ + PF + KW + KVA + KVAR + KVARH + KWH + DUAL ENERGY+ ENERGY+THD-I, THD-V & RUN HRS + MD with RS485 |
| 459 | Providing & Fixing of BIS approved Current Transformer as per PWD specification for electrical Works ,ISI marked as per IS 2705-1992/ conforming to IEC 60044-1, with secondary terminal of CT shall be brought out suitable to a terminal block which shall be easier accessible for testing and terminal connection , with all necessary support in existing panel including connection etc. as required Current transformer Ring Type Tape Wound/Resin Cast Wound as per IS 16227 with, Accuracy Cl, CT ratio and burden as specified. ISF<=5, Cu cross section of secondary wire 1.5sqmm (minimum), including all necessary support in existing panel including connection etc. as required . All as per pre approved by Engineer in charge.All as per pre approved by Engineer in charge. |
| 460 | Ring type tape wound CT |
| 461 | C T Class 1, Ratio upto 150/5, Burden 5 VA |
| 462 | C T Class 1, Ratio 400/5 to 1200/5, Burden 15 VA |
| 463 | Providing & Fixing of 110/220 V, unibody LED Indicating lamp IEC 60947 with integral circuit, IP 65 above panel & IP 20 terminal block, Approx. body dia for panel not less then 20 mm, length min. 50mm, front LED cover dia min. 29 mm, contact material phospher bronze for Led, PCB contacts shall be of brass (tin plated), impulse dielectric tested for 2.5 KV, Rated insulation resistance shall be 100 M ohm at 500VDC including connection etc. as required. All as per pre approved by Engineer in charge. |
| 464 | Red/yellow/Green colour |
| 465 | Blue / white Colour |
| 466 | Providing & Fixing of flush head push button actuators IEC 60947 with integral circuit, IP 65 above panel & IP 20 terminal block, Approx. body dia for panel not less then 20 mm, length min. 50mm, front LED cover dia min. 29 mm, contact material phospher bronze for Led, PCB contacts shall be of brass (tin plated), impulse dielectric tested for 2.5 KV, including connection etc. as required. All as per pre approved by Engineer in charge. |
| 467 | Luminous type Red , Yellow, Green, Amber |
| 468 | Providing & Fixing of 240/415 V AC MCB with positive isolation of 10 kA breaking capacity (B/ C/D tripping characteristic as per type of load and site requirement) 4 KV impulse withstand voltage, ISI marked IS 8828(1996) / conforming to IEC 60898-1 2002, IEC 60947-2, low watt losses, trip free mechanisum , energy limiting of class 3 as per IEC, minimum phase termination capacity of 35sq.mm. , conductor line load reversibility , IP 20 contact protection and fitted in existing distribution board/sheets, minimum electrical operation 20,000 upto 20 A rating and 10,000 upto 63 A, 5000 for 80 A & above rating including making connections, testing etc. as required. OEM shall have submit NABL / CPRI / ERDA accrediated lab type test reports & All as per pre approved by Engineer in charge. |
| 469 | Triple pole MCB (With B/C curve trippingCharacteristics) |
| 470 | 6 A to 32 A rating |
| 471 | 50/63 A rating |
| 472 | Providing & Fixing of self healing IP20 MPP type shunt capacitor (banks) conforming to IS:13340-41 / IEC :831-1&2 OR IEC : 60831-1& 2 in existing panel or parallel with load terminals , the capacitor shall be fitted with discharge resistors, pressure sensitive disconnector ( PSD ) and shall have dissipation factor less than 0.0025 at 50 Hz, Operating loss less than 0.30 Watt per KVAR. Min over current capacity 1.8 times rated current & peak inrush current min. 300 times of rated current, llife expectancy greater than 100000hrs (temp class - 25 D) in 440 V/480 V Capacitor and for 525 V should life expectancy minimum 1,65,000 hrs (temp class - 25 D) including making connections, testing etc. as required.All as per pre approved by Engineer in charge. |
| 473 | Heavy duty Three phase 480 V, 50 Hz cylindrical type capacitor (Bank) |
| 474 | Providing & Fixing of 3-Phase 415/440 V , 7 % / 14 % Detuned Reactors conforming to IEC 61558-2-20 & IEC 60076-6 Aluminium wound for harmonics filter with 180% to 200 % Linearity, H - Class Insulation ( 180 degree C), high temp. Disconnection above 155 deg C., ambient temperature: +60 deg C. with thermal cut off switch in existing panel with following Capacitor ratings. including making connections, testing etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 475 | 7 % (189 Hz) Aluminium wound Reactors |
| 476 | 10 KVAR |
| 477 | 12.5 KVAR |
| 478 | 20 KVAR |
| 479 | 25 KVAR |
| 480 | 50.0 kVar |
| 481 | Providing & Fixing of IP54 microprocessor based 3 CT’s for all 3 phase sensing compensation power factor correction relay Size 139mm x 139 mm, Operating Voltage 415/440 V , IEC / EN 61000-6-(2&4) having 3 CT sensing, sensitivity up to 50 milli amp secondary current , self analysing auto c/k setting according to targeted power factor setting, the relay shall have digit display unit for display of real power factor, targeted power factor, lag/lead capacitor switching status, alarm output for under current, over current, insufficient compensation, communication interface with RS 485, indication of switching on units, auto/manual status, and shall have over load protection, no volt release , having multi parameter like KW, KVA, KVAR, RMS Value, step switching time 2 sec to 1800 sec. Lead & Lag parameters, metering facility and 3 no. Class- 0.5 Cast Resin CT ( refer CT specs in this chapter )for sensing the relay including making coonection with 1.5 Sq.mm copper wire etc. as required. All as per pre approved by Engineer in charge. |
| 482 | 12 to 14 stage |
| 483 | Providing & Fixing of AC operated heavy duty 230 /440 Volt power contactor as per PWD specification for electrical Works, ISI marked IS/IEC 60947-4-1 : 2000 having provision of mechanical interlocking, auxilary contacts, Din rail mounting type including making connections, testing etc. as required. All as per pre approved by Engineer in charge. |
| 484 | 3 pole Power contactors with following AC 3 Rating |
| 485 | 13 to 25 Amp |
| 486 | 32 Amp. |
| 487 | Providing & Fixing of 440 Volt 3 pole capacitor (AC 6 B ) duty contactor with 3 no. early make and post break auxiliary contacts in series with quick discharge damping resistors/ reactors to limit the inrush current as per PWD specification for electrical Works, IS/IEC 60947-4-1 : 2000, insulation voltage 1000V, impulse withstand voltage 8 KV,Din rail mounting type including making connections, testing etc. as required. suitable for following capacity capacitor bank. All as per pre approved by Engineer in charge. |
| 488 | 8.5 KVAR |
| 489 | 12.5 KVAR |
| 490 | 20.0 KVAR |
| 491 | 25.0 KVAR |
| 492 | 50.0 KVAR |
| 493 | P & F of Front / Side mounting Add on Auxiliary Contact Block with required NO & NC combination including making connections, testing etc. as required. All as per pre approved by Engineer in charge. |
| 494 | Providing & Fixing of thermal over load relay with built in single phase protection and having at least 1NO & 1NC contacts, manual /auto reset facility including making connection testing etc. as required. All as per pre approved by Engineer in charge. |
| 495 | Up to 14 Amp |
| 496 | 14 to 23 Amp |
| 497 | 20 to 33 Amp |
| 498 | P & F of 240 / 415 V Electronic ON - OFF Timer 3 -30 Sec / 12 - 120 Sec including making Connection etc. as required. All as per pre approved by Engineer in charge. |
| 499 | P & F Earth leakage relay for continuous surveillance of the earth leakage current of Rating 240 VAC at 50/60 Hz, Overload : x2 continuously, x10 for 3 secs as per BS6253, Voltage Tolerance : : - 25% to +10% Operating temp.: : -10 C to +70 C, Setting of trip point : : 0.030, 0.10, 0.30, 0.50, 1.0 ,3.0 ,5.0, 10.0,20.0 & 30.0 ( User Selectable) with Alarm Relay Output, Trip Relay Output etc. as required. All as per pre approved by Engineer in charge. |
| 500 | ELR with 70mm CBCT |
| 501 | P & F of Direct on line (DOL) / Star - Delta Starter as per IEC type-2 Co-ordination chart of OEM in Existing Panel with circuit breaker having inbuilt overload protection or separate thermal Overload relay , Short circuit, phase loss protection, suitable Contactors, including wiring between switchgears, Indicating lamps for R,Y,B,ON,OFF, Push button for ON, OFF, Volt meter, Ammeter, selector switch for local/remote, auto/manual/OFF operation. Cast resin CT's, provision for potential free contacts making connection, testing etc. as required. All as per pre approved by Engineer in charge. |
| 502 | Direct on line (DOL) Starter with following Motor rating |
| 503 | Motor rating 4.0 KW |
| 504 | Motor rating 5.5 KW |
| 505 | SITC of Draw out type 3/4 pole door interlock Air Circuit Breaker (ACB) as conforming to IS/IEC 60947 P - 2 :2003 in existing LT panel suitable for LT installation 440 V, 50 Hz and having adjustable over load short-circuit, Instantaneous , earth fault (LSIG) with separate LED indication for each type of fault shall confirm to EMI/ EMC test , LCD/LED display, last 10 trip history, provision of ZSI, Communication, Power metering module, Thermal memory , trip free mechanisum , suitable for ambient 50 degree and utilization catagary B. In built electrical & mechanical anti pumping feature , 100% rated neutral . ACB shall have separate indication for service, test, isolation & maintenance position, Breaking capacity Icu = Ics = Icw ( 1 sec ) , U imp - 12 KV, break time not more then 25 ms. Provision for electrical & mechanical interlock between ACBs, Min.electrical operation 10000 upto 2000 A rating and 5,000 for 2500 A to 4000 A. including making connections, testing etc. as required. OEM shall have submit NABL / CPRI / ERDA accrediated lab type test certificate before execution. All as per pre approved by Engineer in charge. |
| 506 | Microprocessor based release Draw out type ( Motorised charging type) 4P |
| 507 | 630/800 A Rating ,50 Ka |
| 508 | 1250 A Rating ,50 Ka |
| 509 | Supply and fixing of following accessories for Air circuit breaker (ACB) compatible with MAin ACB OEM as per PWD specification for electrical Works, conforming to IS/IEC 60947 P - 2 :2003 including making connection etc complete in all respect. OEM shall have submit NABL / CPRI / ERDA accrediated lab type test certificate before execution. All as per pre approved by Engineer in charge. |
| 510 | Mechanical Interlocking Kit using key & Lock |
| 511 | Shunt Trip Release |
| 512 | Under voltage Release |
| 513 | SITC of 3 /4 pole current limiting Moulded case circuit breaker (MCCB) made of flame retardent & heat resistant material having following current rating, short circuit breaking capacity at 440/415 V, 50 Hz; O/L & S/C settings , conforming to IS/IEC 60947 P -2 :2003 with front face and centralised adjustable, trip free mechanisum, true contact position indicator, line load interchangeability, designed for both horizontal & vertical mounting without any adverse effect on electrical performance, suitable for operation upto 55 degree and without derating upto 40 degree, pollution degree 3, having positive isolation capability, push (test) to trip, trip time less then 10 ms under s/c condition, Breaking capacity Ics = 100% Icu. U imp =8 KV, rated insulation voltage 690 V. provision for UVR , shunt trip , earth fault trip, door interlock, pad lock & rotary handle , including making connections etc. as required.OEM shall have submit NABL / CPRI / ERDA accrediated lab type test certificate before execution All as per pre approved by Engineer in charge. |
| 514 | 3 pole MCCB With Thermal Magnetic release |
| 515 | 125 Amp , 25 kA, adjustable O/L & adjustable S/C setting, |
| 516 | 3 pole MCCB With Microprocessor based release with adjustable O/L & S/C setting with Inbuilt Instantaneous and Ground fault Protection. |
| 517 | 630 Amp , 50 kA |
| 518 | 4 pole MCCB With Thermal Magnetic release |
| 519 | up to 100 Amp , 25 kA, adjustable O/L & adjustable S/C setting, |
| 520 | 160 Amp , 25 kA, adjustable O/L & adjustable S/C setting, |
| 521 | 200 Amp , 25 kA, adjustable O/L & adjustable S/C setting, |
| 522 | 250 Amp , 35 kA, adjustable O/L & adjustable S/C setting, |
| 523 | 4 pole MCCB With Microprocessor based release with adjustable O/L & S/C setting with Inbuilt Instantaneous and Ground fault Protection. |
| 524 | 400 Amp , 50 kA |
| 525 | Supply and fixing of following accessories for Moulded case circuit breaker (MCCB) compatible to main MCCB OEM as per PWD specification for electrical Works, conforming to IS/IEC 60947 P - 2 :2003 including making connection etc complete in all respect. OEM shall have submit NABL / CPRI / ERDA accrediated lab type test certificate before execution. All as per pre approved by Engineer in charge. |
| 526 | Shunt Trip Release |
| 527 | Under Voltage Release |
| 528 | Extended Rotary Handle |
| 529 | Spreaders upto 125A, 3 Pole MCCB |
| 530 | Spreaders for 160A, 4 Pole MCCB |
| 531 | Spreaders for 250A, 4 Pole MCCB |
| 532 | Spreaders for 400A, 4Pole MCCB |
| 533 | Spreaders for 630A, 3Pole MCCB |
| 534 | Spreaders for 630A, 4Pole MCCB |
| 535 | Phase Barriers up to 630A, 3/4Pole MCCB |
| 536 | STREET LIGHT |
| 537 | Providing & Fixing of IK08, IP 66 protected LED Street Light Luminaire on existing bracket/pole. Fixture made of powder coated single piece pressure die cast aluminum material with heat dissipation fins on housing with UV stabilized PC (UV stablization report submitted for UV cover ) /Toughened Glass cover and secondary lens on each LED & should be SMD type of 3 to 5 watt each . The System efficacy >=125 lm/ wt and potted driver & has a unique BIS R number with Input Voltage AC 120 to 270 V AC with High voltage Cutoff @>=300 V AC and Auto resetting Safety , Power Factor >0.95 driver Efficiency >85% ,THD(I) <10% Humidity 10% to 90% RH Working Temp -5C to 45C . driver current <750mA. The luminaire shall be BIS certified and Trade mark certified. Life Expectancy Equal or more than 50000 burning hrs with Minimum 70% lumen maintened , CRI >70 and CCT 5700K +355K. Surge protection shall be min ≥ 4 KV internal and min 10 KV external inside driver compartment. driver should be Phase to phase protection of 440 V for 4 Hrs. Manufactures Word Mark/Name Engraved/Embossing on die cast housing to allow traceability/authenticity. Fixture shall be AS PER IS 10322 Complianced.OEM Must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79/LM80) Certificate/ report with liable warranty of product/accessories from OEM shall be submitted. All as per pre approved by Engineer in charge. |
| 538 | LED Street Light fixture with Minimum lumen output 11225 lm |
| 539 | Providing & Fixing of IK08 IP-66 protected high power LED flood light system with single piece Pressure diecast aluminium housing, toughened glass diffuser with suitable lenses on LED to achieve various beam angles, of high power LED of 3 to 5 watt each . Integrated potted driver as a unique BIS R number having efficiency more than 85 % and in compliance to BIS certified and Trade mark certificate. The System level Luminaire efficacy >=125 lm/ wt. LED driver Input Voltage AC 120 to 270 V AC with High voltage Cutoff @>=300 V AC and Auto resetting Safety .Power Factor >0.95 , THD(I) <10% , driver current <=750mA. driver should be Phase to phase protection of 440 V for 4 Hrs. Electrical Connector , Surge Protection Min >=4KV internal and 10KV external but inside driver compartment, System life of 50000 Burning hours with 70% of Initial Lumens maintained, CRI>70 and CCT 5700K ±355K. Manufactures Word Mark/Name Engraved/Embossing/Screen printing on die cast housing to allow traceability/authenticity. Fixture shall be IS 10322 Complianced.OEM Must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79/LM80) Certificate/ report with liable warranty of product/accessories from OEM shall be submitted. All as per pre approved by Engineer in charge. |
| 540 | High Power LED Flood Light Minimum lumen output 14800 lm |
| 541 | Supply and erection of Mild steel Swaged tubular pole conforming to IS: 2713-1980 (part I to II) with base plate, The pole shall be made from steel tube & Pipe (IS:1141, Fe 410) including excavation of the pit and filling the same with C.C. of M-20 grade (1:1.5:3) from base plate to 50 cm above ground level, with the help of steel frame not less than 40 cm dia up to 114.3mm outer dia and 50 cm beyond 114.3mm outer dia around the pole. Duly finished with cement plaster, earthing terminals, cable entry with 32 mm dia. 'B' class GI cable sleeves. After eraction pole shall be painted with two coat of red oxide primer and two quote of enamel paint of silver colour as per the direction of Engineer incharge complete as required of following height & designation. ( See Table P - 02 for specs. ) All as per pre approved by Engineer in charge. |
| 542 | 8.5 Mtr. ( 410 SP - 17 ) |
| 543 | Add for supply and fixing of Pole OEM fabricated Mild steel Overhang of following size over the existing poles, Overhang shall be painted with two coat of red oxide primer and two quote of enamel paint of silver colour as per the direction of Engineer incharge. All as per pre approved by Engineer in charge. |
| 544 | 76.1 mm OD x 3.25 mm thickness |
| 545 | Providing and fixing of fuse box size 250(H) x 200(W) x 150(D) mm fabricated of 1.6mm MS sheet with hinged cover, dust and vermin proof, rubber gasket, locking arrangement, duly holded with 2 nos pole clamps of 20 mm x 3 mm flat with nut and bolts, complete with anticorrosive treatment, finished with two coat of approved enamel paint. The box shall be provided with 2 / 4 nos copper bus bar 125 x 20 x 3 mm with brass screws suitable supports,earth terminal, inter connection, knock outs for 20 / 25 mm cable gland, 1 no. 6 Amp MCB complete in all respect. All as per pre approved by Engineer in charge. |
| 546 | Providing & Fixing of Electrical insulating rubber matts as per PWD specification for electrical Works, ISI marked confirming to IS: 15652 / 2006 with one side anti skid abberation marks and pasting the mat with synthetic rubber adhesive as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 547 | 3.3 KV, class A 2 mm thick with proof voltage 10 KV AC (rms) and Break Down Voltage 30 KV AC (rms) |
| 548 | 11 KV, Class B 2.5 mm thick with proof voltage 22 KV AC (rms) and Break Down Voltage 45 KV AC (rms) |
| 549 | STIC of Finger Print Access Control System having Operation System Linux, Size 4.3 inch. Resolution 800x480, Operation Method Capacitive Touch Screen, Pixel 2MP, Network Interface, RS-485, Exit Button, Door Contact input, USB 2.0,Card Capacity, 1500 or better, Fingerprint Capacity 1500 or better. Event Capacity 150000, Card Type Mifare I card, Card reading distance 0 to 3 cm, Power Supply 12VDC/2A, including metalic push button complete in all respect. Make:- Hikvision,Panasonic,EESL. |
| 550 | Supply of Mifare RF card Non Contacting IC Card having working distance no more than 100mm (Depends on the antenna dimension). Working Frequency: 13.56 MHz. High Data Transmission speed: 106 kbit/s, Anti-Conflict. 1 kbyte (16 zones. 4 sections per zone, 16 bytes per section). Long time data storage: 10 years, Only one serial No. for one card complete with all respect. |
| 551 | SITC of Electro magnetic single leaf lock having power supply and Maximum thrust 280 Kg (617 Lbs) liner thrust, Input Voltage 12VDC/24VDC, Working Current 12V/500mA, 24V/250 mA, LED indicator Red: Door is unlocked and Green: Door is locked, Suitable for wooden, Glass, Metal door complete with mounting bracket as required. Make:- Hikvision, Panasonic, ERD. |
| 552 | Supply, Drawing and Testing of 4 pair, 23 AWG Solid Bare Copper wire insulated with PVC, UTP (Unshielded Twisted Pair), Category 6, Class E, 100 Ohm Impedance, Indoor Cable as per latest ammendments of ANSI/TIA/EIA-568 , The copper conductors should be balanced twisted in pairs, seperated by a cross-member fluted pair divider & protected by PVC Jacket. Certified performance in a 4-connector configuration upto 100 Mtrs channel requirements & transmission frequencies up to 250 Mhz. in existing MS/PVC Conduits/casing capping including making connections to Information outlets and Patch Panels with jack & ferruling at both ends for identification with necessary tools for punching, stripping, crimping and testing etc as required complete in all respect. All as per pre approved by Engineer in charge. |
| 553 | S&F following sizes (dia.) of ISI marked virgin material MMS ( IS:9537 P - III ) 25MM PVC conduit along with ISI marked (IS:3419-1988) accessories as required in recess including cutting the wall, covering conduit and making good the same as required. |
| 554 | 25 mm Please Enable Macros to View BoQ information |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |
| 5 | Click here to download tender document | Tender Documents |
| 6 | Click here to download tender document | Tender Documents |
| 7 | Click here to download tender document | Tender Documents |
Copyright © 2026 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail