| 1 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required. Group 'B' |
| 2 | Wiring for twin control light point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, 2way modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required. |
| 3 | Wiring for light/ power plug with 2X4 sq. mm FRLS / HFFR PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit along with 1 No. 4 sq. mm FRLS/HFFR PVC insulated copper conductor single core cable for loop earthing as required. |
| 4 | Supplying and drawing following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. 3 x 4 sq. mm |
| 5 | Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required.(a) 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire |
| 6 | Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS / HFFR PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. (b) 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
| 7 | Supplying and drawing following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. 3 x 2.5 sq. mm |
| 8 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required (a) 5/6 Amp. Switch |
| 9 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. (b) 3 pin 5/6 Amp. Socket outlet |
| 10 | Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required. |
| 11 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 A & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required |
| 12 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providng and fixing 2 nos. 3 pin 5/6 A modular socket outlet and 2 nos. 5/6 A modular switch, connections etc. as required. (For light plugs to be used in non residential buildings). |
| 13 | Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, Ics=100% Icu and Operational Voltage 690V etc. as required. 125 A,36KA,FPMCCB |
| 14 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 16 way, Double door |
| 15 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Double pole |
| 16 | Supplying & Fixing 5 amps to 32 amps rating , 240 volts, C series, MCB suitable for lighting and other loads of following poles in the existing MCB DB complete with connections, testing & Commissioning etc as required.(a) Single Pole |
| 17 | Supplying and fixing following rating, double pole, 240 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. (b) 63 A |
| 18 | Earthing with G I earth pipe 4.5 m long 40 mm dia i/c assesories and providing masonary enclosure with cover plate having locking arrangement and watering pipe etc with charcoal and salt as reqd |
| 19 | Supply and fixing 6 SWG GI wire on surface or in recess for loop earthing along with existing/recessed conduit/ submain wiring/cable etc as required. |
| 20 | Supplying and fixing G.I. pipe of 40 mm dia meduim duty for protection of UG cable etc. as required of ISI marked of make Jindal/ Hindustan / Prakash. |
| 21 | Supplying, Installation, testing and commissioning of 20 watt LED batten with polycarbonate housing & integrated electronic driver, box type etc. including making connection etc. as required of make Bajaj/ Havells/ Philips/ CG/ Panasonic. |
| 22 | Supplying & laying of one number XLPE insulated and PVC sheathed, XLPE power cable of 1.1 KV Grade of size 2 X 16 Sq. mm direct in ground including excavation and refilling the trench etc as required, but excluding sand cushioning and protective covering. |
| 23 | Supplying and Laying of one number XLPE insulated and PVC sheathed aluminium conductor power cable of 1.1 KV grade of size 2 X 16 sq.mm in the RCC/HUME/METAL as required.Conf. to IS:7098 part - I of make Havells/ Polycab / KEI/Plaza/ Kalinga/ |
| 24 | Providing & fabrication of outdoor cubical panel Compartmental type feeder piller, double door made out of 16 SWG CRCA sheet of size 400mm deep having 415 Volt, 3-Phase 100 amps, 04 nos insulated aluminium bus bars and to accommodate accessories, front & back door openable, R-Y-B LED indicators and P & F of internal connection with suitable size of cu wires, accessories & angle iron frame with 600 mm long legs made out of 40 mm x 40 mm x 5 mm thick angle & grouting the same in suitable cement concrete foundation, arrangement for incoming & outgoing cables, cable termination, earthing, locking, interconnection etc. as required. Please Enable Macros to View BoQ information |