Sales : +91-777 804 8217
| Sl. No. | Item Description |
| 1 | CIVIL WORKS |
| 2 | Construction of Main Building |
| 3 | Excavation in Soil (any type) using Hydraulic Excavator CK 90 with hydraulic excavator of 0.9 cum bucket capacity including cutting, trimming bottom and side slopes, in accordance with requirements of lines, grades and cross sections, including all lifts and combined lead upto 30m. Earth filling under floors with surplus ordinary soil or soil containing gravel or kankar upto 40% excavated from outside the building plinth in 15 cm layers including ramming, watering and consolidating leadupto 30 metres |
| 4 | Cement Concrete 1:4:8 with stone ballast of size. 40 mm guage. using concrete mixing volumetric type |
| 5 | Reinforced cement concrete M-25 mechanicaly batch mixed using batch type concrete mixer as per IS:1791 and vibrated by needle vibrator but excluding steel reinforcement centring and shuttering in foundation and plinth. |
| 6 | Shuttering for faces of concrete foundations and foundation beam & plinth beam (vertical or battering) |
| 7 | First class burnt brick work laid in cement sand mortar 1:6 in foundation and plinth. |
| 8 | Reinforced cement concrete M-25 mechanicaly batch mixed using batch type concrete mixer as per IS:1791 and vibrated by needle vibrator but excluding steel reinforcement centring and shuttering in supersturcture. |
| 9 | Extra for using computerised concrete batch mixing plant including carriage by transit mixer within 1 km lead (note: where concrete mixer is already included in the rate the same shall be deducted ) |
| 10 | Extra for pumping charges of Batch Mix Concrete / Ready mix conrete work (RMC) |
| 11 | Extra rate for enhancement in pumping power, addition of pipe length, scaffolding for handling the pipe arrangement for pumping of concrete in subsequent storey above the below storey up to height of 4 meters or part there of up to the roof top level of that storey |
| 12 | First Floor |
| 13 | Second Floor |
| 14 | Third Floor |
| 15 | Centering and shuttering for columns (Square or rectangular or poly gonal in plain) |
| 16 | Extra Rate For First Floor |
| 17 | Extra Rate For Second Floor |
| 18 | Extra Rate For Third Floor |
| 19 | Centering and shuttering for sides and soffits of beam, beams, launching girders, bressumers, lintels. |
| 20 | Extra Rate For First Floor |
| 21 | Extra Rate For Second Floor |
| 22 | Extra Rate For Third Floor |
| 23 | Centring and shuttering for stair cases with sloping with soffits including risers and stringers. |
| 24 | Extra Rate For First Floor |
| 25 | Extra Rate For Second Floor |
| 26 | Centering and shuttering for faces of walls, partitions, retaining walls and the like (vertical or battering including attached pilasters buttresses etc. |
| 27 | Extra Rate For First Floor |
| 28 | Extra Rate For Second Floor |
| 29 | Centering and shuttering for flat surfaces such as suspended floors, roofs, landings, chajjas, shelves etc. |
| 30 | Extra Rate For First Floor |
| 31 | Extra Rate For Second Floor |
| 32 | Extra Rate For Third Floor |
| 33 | Centering and shuttering for arches of varandah, door and windows openings. |
| 34 | Extra Rate for Second Floor |
| 35 | Extra for burnt brick work in arches excluding cost of shuttering.More than 3 metres but less than 6 metres span |
| 36 | Cold twisted deformed (Ribbed/ Tor Steel Bar/TMT) Bars Fe 500 grade as per IS 1786-2008, for R.C.C works, where not including in the complete rate of RCC including bending and placing in position complete |
| 37 | Extra Rate For First Floor |
| 38 | Extra Rate For Second Floor |
| 39 | Extra Rate For Third Floor |
| 40 | First class burnt brick work laid in cement sand mortar 1:6 in first storey upto 4 metres above plinth level. |
| 41 | Extra Rate For First Floor |
| 42 | Extra Rate For Second Floor |
| 43 | Extra Rate For Third Floor |
| 44 | 115 mm thick brick wall with every fourth course reinforced with hoop iron laid in 1:4 cement mortar in superstructure |
| 45 | Extra Rate For First Floor |
| 46 | Extra Rate For Second Floor |
| 47 | 12.5 mm thick cement plaster 1:5 |
| 48 | Extra Rate For First Floor |
| 49 | Extra Rate For Second Floor |
| 50 | Extra Rate For Third Floor |
| 51 | 20mm thick cement plaster 1:5 in two coat work |
| 52 | Extra Rate For First Floor |
| 53 | Extra Rate For Second Floor |
| 54 | Extra Rate For Third Floor |
| 55 | 12.5 mm thick cement plaster 1:4 |
| 56 | Extra Rate For First Floor |
| 57 | Extra Rate For Second Floor |
| 58 | Extra Rate For Third Floor |
| 59 | 20mm thick cement plaster 1:4 in two coat work |
| 60 | Extra Rate For First Floor |
| 61 | Extra Rate For Second Floor |
| 62 | Extra Rate For Third Floor |
| 63 | Providing and fixing on wall face unplasticised Rigid PVC rain water pipes (working pressure 4 kgf / cm²) conforming to IS : 4985, including fixing with MS ClampU-PVC pipes (working pressure 4kgf. / sqcm) pipe 110 mm dia. |
| 64 | Providing and fixing 110 mm dia. U.P.V.C bend for Rain water pipe as per IS:14735 including jointing complete as per specifications and to the entire satisfaction of Engineer- in- charge.UPVC 110 mm bend |
| 65 | Providing and fixing 110 mm dia SWR U.P.V.C Coupling/Sockete for Rain water pipe as per IS:14735 including jointing complete as per specifications and to the entire satisfaction of Engineer- in- charge.UPVC 110 mm Coupling /Sockets |
| 66 | Top khurra 0.6m x 0.6m for rain water pipe in 25mm thick cement concrete 1:2:4 over 50mm thick cement concrete1:8:16. |
| 67 | Providing and fixing in position gratings 150mm x 150mm for gully trap.PVC grating |
| 68 | Bottom Khurra on ground 1.2m. x 0.6m. consisting of brick on- edge laid in cement mortar 1:3 over 75mm cement concrete 1:8:16 including 12.5m.m. thick cement plaster 1:3. |
| 69 | Terracing consiting of tiles 22.86x11.43x3.83cm laid over 25 mm mud plaster 7.5 cm mud filling on another layer of 25mm mud plaster including two coats of bitumen laid hot at 1.65 Kg. /Sqm top of R.C.C. slab including grouting with cement sand mortar 1:4 and top surface to be left clean after wire brushing |
| 70 | Cement concrete 1:2:4 gola 10cm x 10cm concave quadrant along junction of roofs with parapet wall finished smooth, where specially specified. |
| 71 | Earth filling under floors with surplus ordinary soil or soil containing gravel or kankar upto 40% taking outside the premises in 15 cm layers incluidng ramming, watering and consolidated all lead . CSR 6.8 C(i) |
| 72 | Earth filling :--Earth filling under floors with surplus ordinary soil or soil containing gravel or kankar upto 40% excavated from foundation and taken only from outside the building plinth in 15 cm layers including ramming, watering and consolidating lead upto 30 metres |
| 73 | Base course of floor consisting of 100mm thick cement concrete 1:8:16 with stone aggregate 40mm gauge and 100mm fine sand filling using mechanical mixer for mixing of material. |
| 74 | Screed of 50mm thick cement concrete 1:8:16 with stone aggregate 40mm gaugeto be laid below the topping using mechanical mixer for mixing of material |
| 75 | Extra Rate For First Floor |
| 76 | Extra Rate For Second Floor |
| 77 | Extra Rate For Third Floor |
| 78 | Providing and laying vitrified floor tiles in different sizes in light colour shades made using Full Body Technology (thickness to be specified by the manufacturer) with water absorption’s less than 0.08% and conforming to IS : 15622 of approved make in all colours and shades, laid on 20mm thick cement mortar 1:4 (1 cement: 4 fine sand), complete. ( Full body vitrified tiles have pigment in entire body / thickness of tile which makes chips and scratches less noticeable and make na ideal choice for high traffic zones.)Size 600x600 mm |
| 79 | Extra Rate For First Floor |
| 80 | Extra Rate For Second Floor |
| 81 | Grouting the joints of flooring tiles having joints of 3 mm width, using epoxy grout mix of 0.70 kg of organic coated filler of desired shade (0.10 kg of hardener and 0.20 kg of resin per kg), including filling / grouting and finishing complete as per direction of Engineer-in-charge. Size 600x600 mm. |
| 82 | Kota stone slab 20-25 mm thick flooring over 20 mm (average) thick base laid over and jointed with grey cement slurry mixed with pigment to match the shade of the slab including rubbing and polishing complete with base of cement mortar 1 : 4 (1 cement : 4 coarse sand) : |
| 83 | Extra Rate For First Floor |
| 84 | Extra Rate For Second Floor |
| 85 | Providing and fixing Morwad Marble Strip 12mm to 15mm thick and 100 mm wide in kotah stone flooring over 12.50mm thickness base of cement mortar 1:3 jointed with cement slurry including cost of additional mortar equivalent to the kota stone thickness andcolouring pigment to match the colour rubbed and polished to granolithic finish complete in all respects.respects. |
| 86 | Kotah stone tile 20mm thick in skirting, riser of steps, dado walls and pillars laid in 12.5mm thick cement mortar 1:3 (1 Cement and 3 Sand) and jointed with neat cement slurry mixed with pigment to match the shade of stone including rubbing and polishing |
| 87 | Extra Rate For First Floor |
| 88 | Extra Rate For Second Floor |
| 89 | Marble stone flooring with 18-20 mm thick marble stone, as per sample of marble approved by Engineer-in-charge, over 20 mm (average) thick base of cement mortar 1:4 (1 cement : 4 coarse sand) laid and jointed with grey cement slurry, including rubbing and polishing complete with :Udaipur Green Marble Tiles of thickness 18mm to 20mmSlabs sizes above 0.50 sqm |
| 90 | Extra Rate For First Floor |
| 91 | Extra Rate For Second Floor |
| 92 | Coloured Granite stone tiles 15mm to 20mm thick in skirting, risers of steps, dado walls and pillars laid in 12.5mm thick cement mortar 1:3 (1 cement 3 coarse sand) and jointed with neat cement slurry mixed with pigment to match the shade of stone, including rubbing and polishing including labour for fixing dowel pins and cramps. |
| 93 | Extra Rate For First Floor |
| 94 | Extra Rate For Second Floor |
| 95 | Extra labour for projected nosing of stair case of any shape and design |
| 96 | Providing and Laying Out Door Precast Designer chequered tiles of any size & any shape 25mm thickness having top layer of white cement mixed with pigment, laid on 20mm thick bed of ordinary cement mortar 1:3(1 ordinary cement :3 fine sand), joints grouted with white cement slurry containing pigment to match the shade complete in all respect as per specifications and to the entire satisfaction of engineer- in- charge. |
| 97 | Extra Rate For First Floor |
| 98 | Extra Rate For Second Floor |
| 99 | Providing and Laying Tactile Flooring full body vitrified , low water absorption below 5%, having excellent slip resistance , very dense, durable and abrasion resistant, solid through colour, fade proof, highly chemical and stain resistance unglazed finish porcelain tile of size 300mm x 300mm x 10mm + 5mm thick, approved profile design, Tec-button/Tec-liner laid in ordinary grey cement and on 20mm thick bed of cement mortar 1:3 filling neat cement slurry between joints with White Cement containing pigment to match the shade complete in all respect. (Tile design and pattern will be as per guidelines issued for persons with disability) |
| 100 | Extra Rate For First Floor |
| 101 | Extra Rate For Second Floor |
| 102 | Providing and applying plaster of paris (ISI marked such as JK, Kohinoor, Maharaja etc.) punning 6mm thickness over plastered surface to prepare the surface even and smooth complete in all respect as per the directions of Engineer-in-charge. |
| 103 | Extra Rate for First Floor |
| 104 | Extra Rate for Second Floor |
| 105 | Extra Rate for Third Floor |
| 106 | Providing and fixing mineral fibre false ceiling tiles at height upto 4 Mtr. of size 595X595mm of approved texture, design and pattern. The tiles should have Humidity Resistance (RH) of 99%, Light Reflection > 85%, Thermal Conductivity k = 0.052 - 0.057 w/m K, Fire Performance as per (BS 476 pt - 6 &7)in true horizontal level suspended on interlocking T-Grid of hot dipped all round galvanized iron section of 0.33 mm thick (galvanized @120 gsm) comprising of main T runners of 15x32 mm of length 3000 mm, cross T of size 15x32mm of length 1200 mm and secondary intermediate cross T of size 15x32 mm of length 600 mm to form grid module of size 600x600 mm suspended from ceiling using galvanized mild steel item (galvanised@80gsm) 50 mm long 8mm outer diameter M-6 dash fasteners, 6 mm diameter fully threaded hanger rod up to 1000 mm length and L-shape level adjuster of size 85x25x2 mm, spaced at 1200 mm centre to centre along main T. The system should rest on periphery walls /partitions with the help of GI perimeter wall angle of size24x24X3000 mm made of0.40 mm thick sheet, to be fixed to the wall with help ofplastic rawl plug at 450 mm centre to centre & 40 mm long dry wall S.S. screws. The exposed bottom portion of all T-sections used in false ceiling support system shall be pre-painted with polyester baked paint, for all heights. The work shall be carried out as per specifications, drawings and as per directions of the engineer-in-charge. With 16 mm thick beveled tegular mineral fibre false ceiling tile (NRC 0.55 to 0.6) size 595x595 mm |
| 107 | Providing and fixing tiled false ceiling at height upto 4 Mtr. of specified materials of size 595x595 mm ( GI Metal Ceiling Lay in plain Tegular edge Global white color tiles of size 595x595 mm, and 0.5 mm thick with 8 mm drop; made of G I sheet having galvanizing of 100 gms/sqm (both sides inclusive) and electro statically polyester powder coated of thickness 60 microns(minimum), including factory painted after bending.) in true horizontal level, suspended on inter locking metal grid of hot dipped galvanized steel sections ( galvanized @ 120 grams/ sqm, both side inclusive) consisting of main \\"T\\" runner with suitably spaced joints to get required length and of size 24x38 mm made from 0.30 mm thick (minimum) sheet, spaced at 1200 mm center to center and cross \\"T\\" of size 24x25 mm made of 0.30 mm thick (minimum) sheet, 1200 mm long spaced between main \\"T\\" at 600 mm center to center to form a grid of 1200x600 mm and secondary cross \\"T\\" of length 600 mm and size 24x25 mm made of 0.30 mm thick (minimum) sheet to be interlocked at middle of the 1200x600 mm panel to form grids of 600x600 mm and wall angle of size 24x24x0.3 mm and laying false ceiling tiles of approved texture in the grid including, required cutting/making, opening for services like diffusers, grills, light fittings, fixtures, smoke detectors etc. Main \\"T\\" runners to be suspended from ceiling using GI slotted cleats of size 27 x 37 x 25 x1.6 mm fixed to ceiling with 12.5 mm dia and 50 mm long dash fasteners, 4 mm GI adjustable rods with galvanised butterfly level clips of size 85 x 30 x 0.8 mm spaced at 1200 mm center to center along main T, bottom exposed width of 24 mm of all T sections shall be pre-painted with polyester paint, all complete for all heights as per specifications, drawings and as directed by Engineer-in-charge. |
| 108 | Providing and fixing 15 mm thick false ceiling tiles at all heights with integral densified calcium silicate reinforced with fibre and natural filler false ceiling tiles of Size 595x595 mm of approved texture, design and patterns having NRC (Noise Reduction coefficient) of 0.50 (minimum) as per IS 8225:1987, Light reflectance of 85% (minimum). Non combustible as per BS:476 (part- 4), fire performance as per BS:476 (part 6 &7), humidity resistance of 100%, thermal conductivity< 0.043 W/m K as per ASTM 518:1991,in true horizontal level on the existing frame work consisting of T-sections and Lsections suitably fixed according to tile size as per direction of Engineer-in-charge. |
| 109 | Supplying and fixing of Japani sheet frames (Chowkat) consisting of 18 gauge (1.25mm) thick steel sheet of the specified section (standard design latest), including iron lugs (hold fasts) iron hinges conforming to PWD specifications including bolts for fixing steps, lock notch provision for receiving tower bolts and finished, fixed in position including the cost of cement concrete 1:3:6 for filling in the frame and cement concrete 1:2:4 for lugs complete to the satisfaction of Engineer-in-charge.Doors and windows frame of size 118mm x 60mm with 40 mm wide single rebate weighing 3.43 kg per meter. |
| 110 | Doors and windows frame of size 151mm x 60mm with 35 mm wide double rebate weighing 3.95 kg per meter. |
| 111 | Providing & fixing of Box type steel windows, made of various ERW section outer 60mm x 25mm, central mullion 60mm x 25mm, for shutter 50mm x 20mm having thickness of 1.25mm (18 gauge), shash bar MS Tee 25mm x 3mm where required joints mitered and electrically flash-welded, with iron fittings including necessary iron handles, hinged cleat, tower bolts, iron hold fast and pintle hinges complete (excluding glazing and wire gauge) and finished with ready mixed paint red lead non setting primer complete as per specification, Drawings and to the entire satisfaction of engineer-in-charge. (Note:- Glazing, wire gauge and grill will be paid as per respective items) |
| 112 | Providing & Fixing glass panes with nails and putty or wooden strip complete in all respect. 5.0mm thick Plate glass (INDIAN) |
| 113 | Wire gauge fixed in steel windows, of standard rolled steel section with 3mm thick flat iron cover moulding of 12.5 mm width, fixed with machine screws, complete in all respects. |
| 114 | Providing and fixing aluminum work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/appropriate z sections and other sections conforming to Is: 733 and IS : 1285 of Jindal, Hindalco, Mahavir or equivalent make approved by Engineer in Charge , fixed with rawl plugs and screws or with fixing clips, or with expansion hold fasteners including necessary filling up of gaps at junctions, at top, bottom and sides with required PVC Plug/neoprene felt etc. aluminum sections shall be smooth, rust free, straight, mitered and jointed mechanically wherever required including cleat angle, aluminum snap beading for glazing/paneling, C.P.brass/stainless steel screws, all complete as per architectural drawings and the directions of Engineer-In-Charge. (Glazing and paneling to be paid for separately) : |
| 115 | For shutters of doors, windows & ventilators including providing and fixing hinges/pivots and labour for fixing of fittings wherever required including the cost of PVC Plug / neoprene gasket required |
| 116 | Providing and fixing glazing in aluminum door, window, ventilator shutters and partitions etc. with PVC Plug/ neoprene gasket etc. complete as per the architectural drawings and the directions of engineer-in-charge . (Cost of aluminum snap beading shall be paid in basic item) |
| 117 | Providing Polyester Powder coating 50 micron any coloured specified to alumnum section of various sizes including carriage of material from market to workshop & workshop to site of work. |
| 118 | Providing & fixing ACP Sheets of various thickness High Class ISI marked complete in all respect as per the directions of Engineer-in-charge. 4mm thick ACP Sheet |
| 119 | Factory manufactured solid flush door fixed in position iron hinges, etc (excluding the cost of any fittings other than specified above but including labour for fixing the same in position (Code : IS 2202-1 (1999).Decorative with elm or gurjan facing on one side and teak facing on the other side edges lipped with teak with laminated core 35mm thick |
| 120 | Preparation of plywood surface for painting including sand papering the surface and applying filling with approved quality fillers consisting of white lead, linseed oil, Varnish, and Chalk Mitti including finishing the surface to required finish complete. |
| 121 | Applying pink primer or aluminum priming coat on wood work including preparation of surface knotting and stopping etc. |
| 122 | Wrought iron & Mild steel ladders, framed grills, gratings etc. with ends of bars riveted or molded forged framed window guards, barred iron doors stair case iron railing etc. including cost of bolts and nuts, screws, welding rod complete fixing in position |
| 123 | Applying priming coat with metal primer on new steel or iron work including preparation of surface. |
| 124 | Painting two or more coats excluding priming coat with synthetic enamel paint in all shades on wood work, metallic or plastered, concrete surface to give an even shade. |
| 125 | Cost of Aluminium fittings complete for doors, windows such as tower bolts, handless and screw etc. for these fittings (Excluding sliding bolt)For shutter area above 0.50 sqm |
| 126 | Providing and fixing aluminium sliding door bolts ISI marked anodized (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade with nuts and screws etc. complete :300mm x 16mm |
| 127 | Providing & fixing 16 gauge stainless steel pipe railing of grade 304 duly fixed on steps with the help of bolts grouted on steps with hand rail and newel post of 50mm dia Stainless steel pipe, Balusters of 40mm dia Stainless steel pipe and guard 3 Nos of 15mm dia Stainless Steel pipe complete in all respect |
| 128 | Providing & fixing teak wood top size 150mmx75mmonstair railing including polishing complete in all respect. |
| 129 | Providing and fixing facing extruded clay Tile (Glas sReinforced Clay Tiles(GRC)) any size any shade & design on wall with under layer of 12 mm thick cement plaster 1:3 and jointed with neat cement matched with pigment complete as per drawings,specifications and to the entire satisfaction of engineer- in- charge. |
| 130 | Preparation of plastered or concrete surface for painting (including sand papering the surface) using ready mixed cement based wall putty by applying two or more coats to get required finish |
| 131 | Extra Rate for First Floor |
| 132 | Extra Rate for Second Floor |
| 133 | Extra Rate for Third Floor |
| 134 | Distempering with Acrylic washable oil bound distemper (of approved manufacture) two or more coats over one priming coat to give an even shade |
| 135 | Extra Rate for First Floor |
| 136 | Extra Rate for Second Floor |
| 137 | Extra Rate for Third Floor |
| 138 | Finishing walls with acrylic smooth exterior paint of required shade with two or more coats applied @ 1.67 litre/10Sqm over and including base coat of water proofing Cement Paint applied @ 2.20 Kg/10 Sqm |
| 139 | Extra Rate for First Floor |
| 140 | Extra Rate for Second Floor |
| 141 | Extra Rate for Third Floor |
| 142 | Providing and fixing ( PPGL) precoated painted galvalume sheet roofing (size, shape and pitch of corrugation as approved by Engineer-in-charge) The end rib shall have anti appillary groove and return leg. The steel sheet must be having yield strength of 550 MPa ( Fy= 550 MPa) metallic coated with Zinc- Aluminium alloy ( i.e. 55% Al, 43.4%Zinc, .6% Si-Zincalume) AZ150 ( Min. 150 bm/mm2 total on both sides), pre painted with super Durable Polyster XRW quality paint includes inorganic infrared reflective pigment. The sheet confirms to general requirement of AS/NZS 2728 type 4/ IS 15965 class 3 durability and gloss value of 25% -40%. should be supplied in single length upto 12 metre or as desired by Engineer-incharge. The sheet shall be fixed using self drilling /self tapping screws of size (5.5x 55 mm) with EPDM seal, complete upto any pitch in horizontal/ vertical or curved surfaces, excluding the cost of purlins, rafters and trusses and including cutting to size and shape wherever required.0.50 mm (+ 0.05 %) thick |
| 143 | Steel work in built up tubular pipes (round, square or rectangular hollow tubes etc. ISI Marked) for flat shed (ie.Where no truss work is involved) including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer, including welding and bolted with special shaped washers etc. complete. |
| 144 | Construction of Plinth protection complete as per drawing. |
| 145 | Earth work in exavation in foundations, trenches, etc. in all kinds of soil where pick jumper work is not involved and not exeeding2.0 Mtr. depth and subsequent filling around masonary in 15 cm layers with compaction including disposal of all surplus soil as directed within a lead of 30 Mtr. complete in all respect as per specifcation, drawing and to the entire satisfication of Engineer In-Charge. |
| 146 | Cement Concrete 1:8:16 with 40mm guage stone aggregateusing mechanical mixer. |
| 147 | First class burnt brick work laid in cement sand mortar 1:6 in foundation and plinth. |
| 148 | Base course of floor consisting of 100mm thick cement concrete 1:8:16 with stone aggregate 40mm guage and 100mm fine sand filling using mechanical mixer for mixing of material |
| 149 | Conglomerate floor 40mm thick cement concrete topping 1:2:4 (Using mechanical mixer for mixing of material). |
| 150 | 12.5 mm thick cement plaster 1:5 complete in all respect as per specifcation, drawing and to the entire satisfication ofEngineer-In-Charge. |
| 151 | DISMANTLING ( RIGHT BLOCK) |
| 152 | Stripping and stacking slate or tiles of a roof. |
| 153 | Earth work excavation in ordinary soil, exclusive of compensation of earth:-Earth work undressed with a combined lead upto 15 metres including breaking of clods. |
| 154 | Cement concrete plain 1:2:4 mix |
| 155 | Dismantling concrete Reinforced cement concrete |
| 156 | Removing doors and windows Doors |
| 157 | Dismantling brick work tile, masonry or tile lining In cement |
| 158 | Add for roof trusses of iron or wood, (rafters, purling etc.) in case of item Nos. 8.10 and 8.11. |
| 159 | Disposal of Malba ouitside the premises including loading and unloading as desired by Engineer in charge. |
| 160 | Dismantling steel work in built up sections in angles,tees, flats and channels including all gusset plates,bolts, nuts, cutting rivets, welding etc. includingdismembering and stacking within 50 metres lead. |
| 161 | Credit of Material to be received from dismentling |
| 162 | Tile from dismenling of tile terracing |
| 163 | Bricks from dismenling of Brick works |
| 164 | Brick/Tile bats |
| 165 | PPGL Sheet |
| 166 | Credit of Steel & Iron |
| 167 | Outer Development |
| 168 | Construction of embankment with good quality earth obtained from borrow pits including compensation of earth, loading, unloading, carriage to site of work, spreading, grading to required slope and compacting to meet requirement of table 300-2 as per technical clause 305 of MORT&H specifications |
| 169 | Dismantling concrete Cement concrete plain1:2:4 mix |
| 170 | Dismantling concrete Cement concrete plain 1:4:8 or 1:5:10 |
| 171 | Disposal of Malba ouitside the premises including loading and unloading as desired by Engineer in charge. |
| 172 | Cement Concrete 1:4:8 with stone ballast of size. 40 mm guage. using concrete mixing volumetric type |
| 173 | Providing and laying 60 mm thick factory made cement concrete interlocking paver block of M-35 grade machine made rubber moulded smooth finish with strong vibratory process or with vibro- hydraulic compaction machine and of approved size and design / shape laid in Ordinary Grey and pattern over and including 40 mm thick compacted bed of coarse sand, filling the joints with fine sand etc, all complete as per directions of Engineer-in-Charge |
| 174 | Extra Cost for using darker fast shade for interlocking pavers Tiles of any shape & thickness instead of grey colours. |
| 175 | Precast Cement Concrete Kerb Providing and laying factory made rubber moulded smooth finish cement concrete Kerb M-20 grade 250mm high with bottom width 165mm and top width 115mm made over strong vibratory table and fixing with cement mortar 1:2 as per MORT&H specifications |
| 176 | Applying priming coat with cement primer in all shade on newly plastered or concrete exterior surface |
| 177 | Painting two or more coats excluding priming coat with synthetic enamel paint in all shades on wood work, metallic or plastered, concrete surface to give an even shade. |
| 178 | Providing Internal Electrical Installations: |
| 179 | POINT WIRING: |
| 180 | RECESSED PVC CONDUIT PIPE WIRING SYSTEM WITH MODULAR SWITCHES: Wiring in PVC insulated copper conductor single core FR cable (ISI marked) overall 1.5sq. mm, 1100volts grade to be laid in heavy gauge PVC conduit pipe 20mm/ 25mm dia. (ISI Marked) recessed in wall etc., complete with powder coated/anodized concealed metal boxes (1.6mm thick with Brass lugs) required for suitable number of modules (Modular accessories) for having Step type electronic fan regulators (two module) 100watts, bell push, 6Amp. 2/3 universal socket (shuttered), 16/20Amp. combined/ universal Socket (shuttered), 6/10Amp. Switches, 16/20Amp. switches with indicator etc. and covered with Frame Plate etc., PVC connector (For Fan Box and Call Bell), Steel Hooks, Sheet metal fan box (1.6mm thick shape hexagonal), Circular junction Boxes (Four way PVC 1½\\" deep for walls and CI 3\\" deep for ceiling), bonding to earth with PVC insulated copper conductor single core FR cable (ISI marked) 1sq. mm, 1100volts grade (For 6Amp. wall socket & plug control point) and other petty material etc., including the cost of above material, cutting and filling up of chases (with finishing the surface):- |
| 181 | Wiring fan point with sheet metal fan box |
| 182 | Wiring light point |
| 183 | Wiring call-bell point |
| 184 | Wiring 3 pin 6 Amp. wall socket point |
| 185 | Wiring 3 Pin 6 Amp. Plug control comprising wall socket point |
| 186 | Wiring 3 pin 16/20 amp. power plug control point |
| 187 | Wiring light point without control switch. |
| 188 | Wiring light point with double control switches. |
| 189 | RECESSED AIR CONDITIONER SUPPLY TERMINAL POINT (USED FOR HGW, PVC CONDUIT & HDPE PIPE WIRING SYSTEM WITH MODULAR ACCESSORIES):Wiring air conditioner supply terminal point recessed in wall etc., complete with powder coated/anodized concealed metal boxes required for suitable number of modules (Modular accessories) for having 25Amp. combined/ universal Socket (shuttered) and modular motor starter 25Amp. (2Module), covered with Frame Plate and other petty material etc. including the cost of above material, cutting and filling up of chases (with finishing the surface):- |
| 190 | Wiring AC supply terminal point having 1No. 25Amp. universal Socket (shuttered) erected at AC height and 1No. Motor starter 25Amp. erected at switchboard height. |
| 191 | RECESSED COMPUTER SUPPLY TERMINAL POINTS (USED FOR HGW, PVC CONDUIT & HDPE PIPE WIRING SYSTEM WITH MODULAR ACCESSORIES):Wiring Computer supply terminal points recessed in wall etc., complete with powder coated/anodized concealed metal boxes required for suitable number of modules (Modular accessories) for having 6Amp. 2/3 universal socket (shuttered), 16/20Amp. combined/ universal Socket (shuttered), 6/10/16/20Amp. Switches and blanking plate etc., and covered with Frame Plate and other petty material etc. including the cost of above material, cutting and filling up of chases (with finishing the surface):- |
| 192 | Wiring Computer terminal point having 3 Nos. 6Amp. 2/3 universal socket (shuttered), 1No. 16 Amp. switch with indicator and 1No. blanking plate (Modular accessories). |
| 193 | SUPPLY AND ERECTION OF WIRING ACCESSORIES:Supply and erection of switches, sockets and other accessories (flush piano type/ modular accessories) in the existing bakelite/ modular cover frame including fixing & connections and petty material etc.:- |
| 194 | Ceiling Rose (Flush Piano type) |
| 195 | Call Bell 220/230 volts AC Ding Dong |
| 196 | LED'S FIXTURES & FANS: |
| 197 | Supply and erection of Slim Recessed mounted, Round downlighter 18 watt with Pressure die cast aluminium housing & polycarbonate diffuser with surge protection 10KV and efficacy of LED fixture minimum 100 lumens per watt and operating voltage between 140 to 270 volt, input AC frequency 50 Hz ± 3 %, housing & driver shall be of same brand, supported with LM 79 reports not more than 2 years old from NABL /UL accredited laboratory complete along with erection of the same with connections, testing etc. complete in all respects as approved and desired by the Engineer-in-charge at site. The certification and specifications of the LED Fitting's should be as approved by O/o Advisor (Technical), Govt of Punjab vide Letter no.AT/2021/GL/1410-1422 Dated 06/05/2021. Besides this the lighting fixtures manufactures should have in house NABL accredited laboratory. |
| 198 | Supply and erection of LED batten 20 Watt LED (including constant LED driver) with High quality extruded aluminium with efficacy of LED fixture minimunm 100 lumens per watt and operating voltage between 140 to 270 volt, THD <10% ingress protection IP20 (as per latest BIS standards) surge protection - 2.5 KV and above (as per IS/IEC standards) wattage of each low power LED less than 1 watt input AC frequency 50 Hz ± 3 % with 5 year warranty including there drivers complete along with erection of the same with connections, testing etc. complete in all respects as approved and desired by the Engineer-in-charge at site. LED Fitting as per Specifications approved by Hon. Tech. Advisor to CM Punjab vide Letter ION No: AT/2021/GL/1410-1422, Dated: 06.05.2021. Besides this the lighting fixtures manufactures should have in house NABL accredited laboratory. |
| 199 | Supply and erection of LED batten 40 Watt LED (including constant LED driver) with High quality extruded aluminium with efficacy of LED fixture minimunm 100 lumens per watt and operating voltage between 140 to 270 volt, THD <10% ingress protection IP20 (as per latest BIS standards) surge protection - 2.5 KV and above (as per IS/IEC standards) wattage of each low power LED less than 1 watt input AC frequency 50 Hz ± 3 % with 5 year warranty including there drivers complete along with erection of the same with connections, testing etc. complete in all respects as approved and desired by the Engineer-in-charge at site. LED Fitting as per Specifications approved by Hon. Tech. Advisor to CM Punjab vide Letter ION No: AT/2021/GL/1410-1422, Dated: 06.05.2021. Besides this the lighting fixtures manufactures should have in house NABL accredited laboratory. |
| 200 | Supply and erection of Recessed mounted 36watt LED panel (including LED driver) with CRCA sheet having efficacy of LED fixture minimunm 100 lumens per watt and operating voltage between 140 to 270 volt, THD <10% ingress protection IP20 (as per latest BIS standards) surge protection - 2.5 KV and above (as per IS/IEC standards) wattage of each low power LED less than 1 watt input AC frequency 50 Hz ± 3 % with 5 year warranty including there drivers complete along with erection of the same with connections, testing etc. complete in all respects as approved and desired by the Engineer-in-charge at site. LED Fitting as per Specifications approved by Hon. Tech. Advisor to CM Punjab vide Letter ION No: AT/2021/GL/1410-1422, Dated: 06.05.2021. Besides this the lighting fixtures manufactures should have in house NABL accredited laboratory. |
| 201 | Supply and erection of BEE 3-Star rating AC Ceiling Fan 1200mm (48\\") suitable for 230 V single phase with double ball bearing, copper wound, full aluminium body, 3Nos. of blades, white in colour. The mounting type is down rod mount. The product should possess a minimum air deleivery of 210 CMM (approx.). The rated speed of the the product must be minimum of 300 revolutions per minute and 5Nos. of speeds. The product should have a manufcaturer's guarantee /warranty of minimum 2 years. The product should be complete in all aspects with fan motor, bladeset, down rod, conopy set, shackle kit, twisted wire etc., including erection & testing of ceiling fan having connection with PVC insulated PVC sheathed two single core copper conductor (FR) cable 0.75 sq. mm complete in all respects as per satisfcation of the Engineer in-charge at site. |
| 202 | Supply and erection of Wall Fan Plastic Body 400MM, 16\\" including flexible wire & petty material etc. for connections and testing complete in all respect as approved and desired by the Engineer in-charges at site. |
| 203 | Supply and erection of Heavy duty Exhaust Fan 300mm, 900RPM with aluminium louver shutter, double ball bearing longer life including flexible wire & petty material etc. for connections and testing complete in all respect as approved and desired by the Engineer in-charges at site. |
| 204 | OCCUPANCY SENSORS: |
| 205 | Supply and erection of Ceiling mounted Occupancy based PIR sensor (360° detection angle motion detector) with installation height 3mts, 8.5 Amps resistive load, Detection dia 8M, time delay - 5s to 59 mins , Light level threshold - 5 to 1275 Lux, IP - 20, Sensitivity Adjustment, Walk LED test, with additional options like walkthrough, daylight set point, vacancy complete in all respect as approved and desired by the Engineer in-charges at site. |
| 206 | SUSPENSION RODS FOR CEILING FANS: |
| 207 | HEAVY GUAGE WELDED CONDUIT PIPES:Supply & erection of Heavy guage welded conduit pipe (ISI marked) as per IS:9537:Part-II for wiring purposes including bends, junction boxes, Steel hooks, GI saddle clamps and other petty materials etc., where necessary including painting as per PWD General Specifications:- |
| 208 | Supply & erection of 19/20mm dia. M.S. conduit pipe (1.6mm thick), white painted suspension rod for ceiling fan. |
| 209 | CONDUIT PIPE & COPPER WIRES: |
| 210 | PVC, HDPE PIPES & PVC FLEXIBLE PIPES:Supply & erection of PVC Conduit Pipes (ISI marked) as per IS9537:Part-III & HDPE pipes (ISI marked) as per IS:4984:1995 for wiring purposes including bends, junction boxes, Steel hooks, M.S. saddle clamps and other petty materials etc., as per PWD General Specifications:- |
| 211 | Heavy gauge PVC conduit pipe 20mm dia. (ISI marked) Flushed |
| 212 | Heavy gauge PVC conduit pipe 25mm dia. (ISI marked) Flushed |
| 213 | Heavy gauge PVC conduit pipe 32mm dia. (ISI marked) Flushed |
| 214 | Heavy gauge PVC conduit pipe 40mm dia. (ISI marked) Flushed |
| 215 | PVC INSULATED SINGLE CORE FR COPPER CONDUCTOR CABLE:Supply and erection of PVC insulated FR single core Unsheathed copper conductor cable (ISI marked) suitable upto 1100 volts grade confirm to IS:694/1990 left bare in pipe or casing of suitable size complete in all respect as desired by the Engineer-in-charge:- |
| 216 | Overall size 1sq.mm (Un-sheathed) |
| 217 | Overall size 1.5sq.mm (Un-sheathed) |
| 218 | Overall size 2.5sq.mm (Un-sheathed) |
| 219 | Overall size 4sq.mm (Un-sheathed) |
| 220 | Overall size 6sq.mm (Un-sheathed) |
| 221 | Overall size 10sq.mm (Un-sheathed) |
| 222 | Overall size 16sq.mm (Un-sheathed) |
| 223 | Overall size 25sq.mm (Un-sheathed) |
| 224 | SUB DISTRIBUTION SYSTEM: |
| 225 | SHEET METAL DOUBLE DOOR DISTRIBUTION BOARD FOR MCB/ RCBO/ RCCB's:Supply and erection of sheet metal Double Door Distribution Boards IP 43- IK09 metal door (dust protected) as per IS 8623-1&3, IEC 61439-1&3 suitable for flush mounting with fully insulated copper busbars, shrouded neutral bars, earth bars, cement spill protector, colorcoded interconnecting wire set, cable ties, blanking plates and circuit identifications label and of required no. of ways for mounting miniature circuit breakers/ RCBO's/ RCCB's in the distribution board (For SP&N distribution board with provision DP MCB's/ RCCB's/ RCBO's as incomer and SP MCB's as outgoings and for TP&N horizontal distribution board with provision TPN/ FP MCB's/ RCCB's/ RCBO's as incomer and SP MCB's as outgoings) as per PWD General specifications including connections with suitable size of thimbles and bonding to existing earth etc:- |
| 226 | TP&N Vertical Double Door Distribution Board 4 way each. |
| 227 | TP&N Vertical Double Door Distribution Board 8 way each. |
| 228 | Supply and erection of sheet metal Cable End Box (Make is same as MCB Distribution Board) mounting on the top or bottom of the MCB Distribution Board (Either Horizontal or Vertical) to keep loose wires & cables as per PWD General specifications including petty materials etc as required:- |
| 229 | Cable End Box for TPN Vertical 4/8/12Way |
| 230 | MINIATURE CIRCUIT BREAKERS:Supply and erection of Miniature Circuit Breaker MCB's for circuit protection against overload and short circuit current fault suitable for 240/ 415 volts 50cycles AC supply with breaking capacity of 10kA, Curve-C and low watt losses as per IS/IEC 60898-1, energy limitation class-3, true contact indication, label holder facility in the existing MCB distribution board as per PWD General Specifications including connections with suitable size of thimbles/lugs:- |
| 231 | MCB Single Pole 6-32amp. (10kA, Curve-C) |
| 232 | MCB Four Pole 40amp. (10kA, Curve-C) |
| 233 | MCB Four Pole 50, 63amp. (10kA, Curve-C) |
| 234 | MAIN DISTRIBUTION SYSTEM: |
| 235 | MAIN VERTICAL DISTRIBUTION BOARD (EMERGENCY): TPN 4Way to feed MCB DB's (EMERGENCY LOAD) ON GROUND FLOOR |
| 236 | Supply and erection of sheet metal double door vertical distribution boards IP 43-IK09 metal door (dust protected) as per IS:8623-1&3, IEC 61439-1&3 suitable for flush mounting with fully insulated copper busbars for each phase, 2 Nos. shrouded neutral bars, 2Nos. earth bars, cement spill protector, color-coded interconnecting wire set, cable ties, blanking plates and circuit identifications label and of required no. of ways for mounting MCCB's as incomer and outgoings SP/TP miniature circuit breakers in the distribution board as per PWD General specifications including connections with suitable size of thimbles and bonding to existing earth etc.:- |
| 237 | TP&N Double Door Vertical DB's 4 way each (With provision of FP MCCB upto 125amp) |
| 238 | MCCB's (MOULDED CASE CIRCUIT BREAKER):Supply and erection of Moulded Case Circuit Breaker (Panel mounting Cubical type) in the existing Cubical Panel (confirm to IEC:60947-2) having Ics=100% Icu, 100% neutral with spreader links and relevant PWD general specifications complete with G.I. Bolts, Nuts & Connection on both sides of MCCB with suitable size of thimbles etc:- |
| 239 | MCCB Four Pole 100amp., 415volts, ≥25kA Fixed Magnetic and Adjustable Thermal Setting |
| 240 | MCCB Four Pole 125amp., 415volts, ≥25kA Fixed Magnetic and Adjustable Thermal Setting |
| 241 | Supply and erection of PVC flexible pipe complete without compression glands, locking arrangement, check-nuts as required:- |
| 242 | PVC flexible pipe 40mm dia. |
| 243 | Supply and erection of Compression glands, Locking arrangement, Checknuts for PVC flexible pipe complete with as required:- |
| 244 | PVC compression Socket gland 40mm dia. |
| 245 | INDOOR LT PANELS: FOR MAIN BUILDIING |
| 246 | LT PANELS & MCCB's (MOULDED CASE CIRCUIT BREAKERS):Designing, Supply, Erection, Testing & commissioning of indoor Type LT cubical panel enclosure (dust, vermin and interchangeable modules with facilites for extensions or reduction as per the space or requirments). The Panel shall be suitable for operation at 415+6% Volts, 50HZ, 3 phase 4 wire & earth system. The assembly manufacturer should be ISO approved and CPRI tested for short circuit of (minimum 50kA) as well as IP degree of protection (IP 54/55).Fabrication: Panel shall be made from 14/16 SWG CRCA sheet, conforming to IS 8623/1977-82. The sheet metal used for the fabrication of control panel will be 2mm for load bearing member’s door and fittings plates etc. the partitions and other non load bearing members will be fabricated out of 1.6mm sheet, the sheet will be of mild steel CRCA type. The base channel will be made out of 75 x 40 x 5mm rolled channel. The door should be double folded without edge and the gasket should be ‘S’ type puffed neutral rubber gasket for long life. The hinges of the door should be bolted type with double hole arrangement. The panel door lock should be quick openable type spring loaded. There should not be any special tool or key to open the lock. Minimum depth 400mm / wide 300 mm for busbar/ Cable ally at the front of the panel. The panel will be free standing floor mounting type having provision for cable entry from bottom/top with cable glands etc. The fabrication should be such that all the member i.e. vertical/horizontal should be detachable type i.e. total bolted. In case of any changes required at site. it should be possible then and their self without any cutting or welding. The fabrication of the panel in 3B construction fully compartmentalized type i.e. bus bar chamber as well as the cable chamber should be totally isolated from the feeder chamber. Where there crossing of the wire or bus links. It should have proper rubber gourmets or non-hygroscopic material. No live part should be in visible condition.Painting: The sheet metal is sprayed with corrosion resistant etch Primer. The finishing treatment shall be applicable with air drying paint (7/9 tank Powder coated process should present in company pemises) after necessary putty work . |
| 247 | Busbars: The panel shall be provided with TPN aluminium busbar of suitable size according to the size of MCCB's. Busbar shall be of high conductivity (53% to 58%) E91-E Grade aluminium (1A/Sq.mm). All Busbar will be air insulated with codified in Red, Yellow, Blue & Black as per standard for cable termination with the help of extended busbar only with proper adjustable cable supports. The main busbar would be supported upon non-hygroscopic SMC/DMC supports. Metering: The panel shall be completed with digital metering unit (with selector switches, voltmeter & ammeter) epoxy insulator, gasket, PVC sleeves, CT's & L.E.D. type indicator etc. Manufacturer of Panel should be CPRI Approved (Approval not older then 5 years) & ISO certified (Manufacturer workshop as per ISO 9001: 2015 standard) The Concerned contractor shall be approved the detailed drawing of panel with complete specification from the Engineer in charge at site.Detail of capacities of MCCB's to be installed in the cubical panel Enclosure (Excluding the cost of MCCB's) as per following:- |
| 248 | MAIN LT PANEL: |
| 249 | LT Panel enclosure having space for 1No. Incomer MCCB 630Amp. and 6Nos. outgoing MCCB's 40amp. to 250amp. (Option: MCCB 200-250amp.= 2Nos. and MCCB's 40-100amp.= 4Nos.) according to the requirement at site (Approx. size 1475 x 1800 x 400mm) (DETAIL SEE IN PANEL INVENTORY) |
| 250 | SUB LT PANEL (NORMAL): |
| 251 | LT Panel enclosure having space for 1No. Incomer MCCB 400Amp. and 8Nos. outgoing MCCB's 40amp. to 160amp. according to the requirement at site (Approx. size 1750 x 1750 x 400mm) (DETAIL SEE IN PANEL INVENTORY) |
| 252 | SUB LT PANEL (EMERGENCY): |
| 253 | LT Panel enclosure having space for 1No. Incomer MCCB 250Amp. and 8Nos. outgoing MCCB's 40amp. to 100amp. according to the requirement at site (Approx. size 1575 x 1700 x 400mm) (DETAIL SEE IN PANEL INVENTORY) |
| 254 | MCCB's (MOULDED CASE CIRCUIT BREAKER):Supply and erection of Moulded Case Circuit Breaker (Panel mounting Cubical type) in the existing Cubical Panel (confirm to IEC:60947-2) having Ics=100% Icu, 100% neutral with spreader terminal links, Extended rotary handle and relevant PWD general specifications complete with G.I. Bolts, Nuts & Connection on both sides of MCCB with suitable size of thimbles etc |
| 255 | MCCB Four Pole 40/63/80/100amp., 415volts, ≥25kA Fixed Magnetic and Adjustable Thermal Setting |
| 256 | MCCB Four Pole 125amp., 415volts, ≥25kA Fixed Magnetic and Adjustable Thermal Setting |
| 257 | MCCB Four Pole 250amp., 415volts, ≥36kA Microprocessor Based Adjustable Thermal and Magnetic Setting |
| 258 | MCCB Four Pole 400amp., 415volts, ≥36kA Microprocessor Based Adjustable Thermal and Magnetic Setting |
| 259 | MCCB Four Pole 630amp., 415volts, ≥36kA Microprocessor Based Adjustable Thermal and Magnetic Setting |
| 260 | MINIATURE CIRCUIT BREAKERS:Supply and erection of Miniature Circuit Breaker MCB's for circuit protection against overload and short circuit current fault suitable for 240/ 415 volts 50cycles AC supply with breaking capacity of 10kA, Curve-C and low watt losses as per IS/IEC 60898-1, energy limitation class-3, true contact indication, label holder facility in the existing MCB distribution board as per PWD General Specifications including connections with suitable size of thimbles/lugs:- |
| 261 | MCB Four Pole 40amp. (10kA, Curve-C) |
| 262 | MCB Four Pole 50, 63amp. (10kA, Curve-C) |
| 263 | ON LOAD CHANGEOVER SWITCH (Without Sheet Enclosure): |
| 264 | Supply and erection of On Load Change over Switch with advance neutral UNIT (Panel mounting Cubical type) in the existing Cubical Panel Confirms to IS 13947 (Part-3) complete with G.I. Bolts, Nuts & Connections on both sides of switch with suitable size of thimbles as per PWD General Specifications:- |
| 265 | On Load Change Over Switch Four Pole 250amp., 415volts |
| 266 | On Load Change Over Switch Four Pole 400amp., 415volts |
| 267 | EARTHING SYSTEM (INDOOR): |
| 268 | COPPER EARTHING 8SWG :- Earthing with 8 SWG (4mm dia.) electrolytic copper wire thimbled (1No. copper thimble with suitable size steel bolt, washers & double nut) with 30cm x 60cm x 2mm thick copper plate (made cylindrical) burried below ground level in the hole of excavation having bore dia. 125mm and surrounded by salt & charcoal dust mixture (20 kg.) including fixing the copper wire run through 20mm dia. G.I. pipe (A-Class) recessed in wall and in floor etc., up to suitable Length in metre (including bore Length). G.I. pipe 20mm dia. (A-class) of suitable Length should be laid in the hole of excavation 1 feet below ground level and having GI Reducer 50mm x 20mm with PVC Cap (For pouring water) fixed on the top level of the pipe. 300mm x 300mm x 300mm deep haudi of First class bricks finished with 1:4 cement plaster and haudi covered with cast iron lid having size 300mm x 300mm (Heavy) around the hole of excavation:- |
| 269 | Earthing with 8 SWG (4mm dia.) copper wire thimbled with 30cm x 60cm x 2mm thick copper plate burried 10.50 metre (34.44 feet) below ground level (up to 14metre in Length) with G.I. pipe 20mm dia. (A-class), 9metre long |
| 270 | Fixing additional Length of earthing with 8 S.W.G. (4mm dia.) copper wire in G.I. pipe with sockets, elbows, steel hooks and GI saddle clamps including painting etc.:- |
| 271 | Additional Length copper wire 8 S.W.G. (4mm dia.) in 20mm dia. G.I. pipe (Flushed) |
| 272 | COPPER EARTHING :-(Upto 14 metre in Length):-Earthing with electrolytic Copper Tape rivetted (with 5Nos. copper rivets)/Steel Nut & bolts (with 4Nos. 32mm long, 8mm thick with washer and double nut) to 30cm x 120cm x 2mm thick copper plate (made cylindrical) burried 10.50 metre (34.44 feet) below ground level in the hole of excavation having bore dia. 125mm and surrounded by salt & charcoal dust mixture (20 kg.) including fixing the Copper Tape recessed in wall and in floor etc., up to 14metre in Length (including bore Length). G.I. pipe 20mm dia. (A-class), 9metre long should be laid in the hole of excavation 1 feet below ground level and having GI Reducer 50mm x 20mm with PVC Cap (For pouring water) fixed on the top level of the pipe. 300mm x 300mm x 300mm deep haudi of First class bricks finished with 1:4 cement plaster and haudi covered with cast iron lid having size 300mm x 300mm (Heavy) around the hole of excavation:- |
| 273 | Earthing with 20mm x 3mm Copper Tape (upto 14Metre in Length) |
| 274 | Earthing with 25mm x 3mm Copper Tape (upto 14Metre in Length) |
| 275 | COPPER EARTHING STRIP (As Additional Length):Fixing additional Length of earthing with Copper Tape (On Surface/Flushed) with petty material as required etc.:- |
| 276 | Additional Length 20mm x 3mm thick Copper Tape . |
| 277 | Additional Length 25mm x 3mm thick Copper Tap |
| 278 | INDOOR LT CABLES, CABLE TRAY, DWC PIPE , BRASS GLANDS & THIMBLES: |
| 279 | XLPE INSULATED UN-ARMOURED CABLES (LOOSE):-Supply, laying and erection of aluminium conductor XLPE insulated PVC sheathed Un-armoured and served cable 1100 volts grade as per IS 7098 (Part-1)1988 to be laid loose in the existing trench or pipe as per PWD General Specifications:- |
| 280 | Overall size 16sq.mm (4 Core) Un-armoured (Loose) |
| 281 | Overall size 240sq.mm (3½ Core) Un-armoured (Loose) |
| 282 | CABLE TRAY:Supply and erection of MS perforated cable tray (MS Sheet thickness 2mm) with DA gray paint on the existing surface with the help of MS angle iron support (to be painted with approved paint) of size 50mm x 50mm x 6mm thick to be fixed with fastners/ nut & bolts etc., complete in all respect as desired by the Engineer-in-charge and as per PWD General Specifications:- |
| 283 | Cable Tray Size 300mm x 50mm x 50mm (2mm thick) |
| 284 | DOUBLE WALLED CORRUGATED (DWC) HDPE PIPES:Supply and erection of Double Walled Corrugated (DWC) HDPE pipe to be laid 1/2mtr. below ground level including excavation placing the pipe in position and back filling with excavated soil etc. of the required size:- |
| 285 | Double walled corrugated (DWC) HDPE pipe 63/51 mm (outer/ inner dia.) |
| 286 | Double Walled Corrugated HDPE Pipe 90/76mm (Outer/ Inner dia.) |
| 287 | Double walled corrugated (DWC) HDPE pipe120/103.50mm (outer/ inner dia.) |
| 288 | Double Walled Corrugated HDPE Pipe 160/ 136mm (Outer/ Inner dia.) |
| 289 | Double Walled Corrugated HDPE Pipe 180/152mm (Outer/ Inner dia.) |
| 290 | Supply and erection of heavy duty brass single compression gland for cable end termination duly complete with checknuts etc. including making necessary connections:- |
| 291 | Brass Gland for Aluminium cable 2/3/4 Core size 16sq.mm |
| 292 | Brass Gland for Aluminium cable 3/3½/4 Core size 240sq.mm |
| 293 | Supply and erection of heavy duty aluminium thimbles/lugs for cable end termination duly crimped including making necessary connections completely:- |
| 294 | Aluminium thimble cable Core size 4 - 6sq.mm |
| 295 | Aluminium thimble cable Core size 10 -16sq.mm |
| 296 | Aluminium thimble cable Core size 120sq.mm |
| 297 | Aluminium thimble cable Core size 240sq.mm |
| 298 | Supply and erection of heavy duty Copper thimbles/lugs for cable end termination duly crimped including making necessary connections etc. completely:- |
| 299 | Copper thimble cable Core size 4 - 6sq.mm |
| 300 | Copper thimble cable Core size 10 - 16sq.mm |
| 301 | SAFETY EQUIPMENTS: |
| 302 | Providing and fixing of 4.5 Kg. Capacity FIRE EXTINGUISHER,CO2 type as per IS:15683 complete with all accessories as per Manufactures Specification. ISI Mark complete in all respect |
| 303 | Providing and fixing of 6 Kg. Capacity FIRE EXTINGUISHER, ABC Powder type (stored pressure) asper IS:15683 complete with all accessories as per Manufactures Specification. ISI Mark complete in all respect |
| 304 | Providing 2Nos. 13 Passenger, 3Stops: |
| 305 | Supply, installation, testing and commissioning of 1 No. lift of 13 passengers machine room less.Type and Capacity : Approximately 884 Kg, 13 Passengers Speed:1.0 Meter per second Type of drive: AC Variable Voltage Variable Frequency with 16-Bit Microprocessor. Motor: Permanent Magnet Gearless Machine to be hoisted on the top of guide rail within the elevator hoist way Travel: Approximately 8 meter________ Serving: _3 Floors _3Stops _ 3Openings _3Levels (All on the same side) Hoist way Required: 2050mm (Wide) x 2500mm (Deep) Clear dimensions Headroom Height (HR): 5000 mm beyond finished floor level of last landing Pit Depth: 1600mm below the finish floor level of first landing Car Size Area: Minimum 2.06 square meter and Maximum 2.20 square meter Car Enclosure: Constructed out of stainless steel Scratch proof Finish (Vandal Proof) with Honeycomb finish.Car Entrance: Center Opening Automatic Doors with AVCF Drive (all landing doors must be fire-rated for a minimum of 120 minutes) of Stainless steel with Honey comb /Hairline Finish with a clear opening of 900mm/1000mm (wide) x 2000mm/2100 mm (high) Door operation: Automatic DC Door operation with adjustable door opening and closing timings Control: Simplex full selective collective control with and without attentdent Operation: Automatic Power Supply: 415 Volts, 3- phase, 50Hz Alternating Current Flooring: Floor Skid - Resistant as per standard Fan: Blower Fan in Car for ventilation with Auto cut off Lighting: LED for Car Lighting Indicators: LED Dot matrix / Digital 3 segement direction and position indicators in the car and at all landings Hand Rail: Stainless Steel round Hand rail not less than 600mm long at 900mm above floor level (Side LH,Side RH & Rear) Call Button Height: Call button (Outside the lift) placed at a height between 800mm-1meter from the floor level Control Panel Height: Control panel placed at a height between 800mm-1meter from the floor level Std. Govt. features. |
| 306 | Other Features: 1. Battery operated emergency light with rechargeable battery 2. Battery operated emergency alarm with rechargeable battery 3. Adjustable Guide shoes 4. Micro movement LED based buttons 5. Door Open and Close buttons 6. Emergency Intercom provided inside the elevator 7. Emergency Intercom usable without the voice communication 8. Load weighing device with overload bypass feature and Overload function with Audio Visual Indication 9. Steel items, door frames sill angle's, fascia plates, spring buffers10. Automatic phase reversal device and Phase Failure protection11. Call registration 12. Audio & Video System installted in the lift indicating arrival at a floor 13. Manual Rescue System 14. Additional car gate lock 15. Automatic break testing infrared safety curten 16. Braille Buttons (Inside and outside) with Braille instructions for the communication system 17. Kick plate/Skirting 18. Lift anoucement system to announce floor level's in english language only and indication of door for entrance / exit is either Open or Close 19. Car Operating Panel 20. Car plateform constructed out of cold rolled grain oreinted formed sheets of steel 21. Phase two device fire man drive 22. Fire Man switch at main lobby 23. Car false ceiling in stainless steel 24. Pit ladder 25. Anti Nuisance car call protection 26. Door Nudging 27. Automated Resuce Device to bring the elevator to the nearest landing in case of power failure.28. The use of visually and accoustically reflective wall surace should be minimized within the lift car as visual reflections can cause discomfort and affect the visual acuity of people with impairements.29. The floor of lift car should be slip resistant and have similar frictional qualities to thye floor of lift landing to decrease the risk of stumbling.30. The provision of mirror on the wall of the lift car opposite the lift door not extend below 900mm from the lift floor to avoid confusing people with impaired sight.31. The emergency communication system should be coupled with an induction loop system installed all around the lift. Telephone units, where provided, should have an inbuilt inductive coupler to assist persons using hearing aids. |
| 307 | XLPE INSULATED UN-ARMOURED CABLES (LOOSE):-Supply, laying and erection of aluminium conductor XLPE insulated PVC sheathed Un-armoured and served cable 1100 volts grade as per IS 7098 (Part-1)1988 to be laid loose in the existing trench or pipe as per PWD General Specifications:- |
| 308 | Overall size 16sq.mm (4Core) Un-armoured (Loose) |
| 309 | XLPE INSULATED UN-ARMOURED CABLES (ON SURFACE):Supply, laying and erection of aluminium conductor XLPE insulated PVC sheathed Un-armoured and served cable 1100 volts grade as per IS 7098 (Part-1)1988 to be laid (On Surface) as per PWD General Specifications:- |
| 310 | Overall size 16sq.mm (4Core) Un-armoured (On-Surface) |
| 311 | DOUBLE WALLED CORRUGATED (DWC) HDPE PIPES:Supply and erection of Double Walled Corrugated (DWC) HDPE pipe to be laid 1mtr. below ground level including excavation placing the pipe in position and back filling with excavated soil etc. of the required size:- |
| 312 | Double walled corrugated (DWC) HDPE pipe 63/51 mm (outer/ inner dia.) |
| 313 | COPPER EARTHING (8 SWG COPPER EARTHING): Earthing with 8 SWG (4mm dia.) electrolytic copper wire thimbled (1No. copper thimble with suitable size steel bolt, washers & double nut) with 30cm x 60cm x 2mm thick copper plate (made cylindrical) burried below ground level in the hole of excavation having bore dia. 125mm and surrounded by salt & charcoal dust mixture (20 kg.) including fixing the copper wire run through 20mm dia. G.I. pipe (A-Class) recessed in wall and in floor etc., up to suitable Length in metre (including bore Length). G.I. pipe 20mm dia. (A-class) of suitable Length should be laid in the hole of excavation 1 feet below ground level and having GI Reducer 50mm x 20mm with PVC Cap (For pouring water) fixed on the top level of the pipe. 300mm x 300mm x 300mm deep haudi of First class bricks finished with 1:4 cement plaster and haudi covered with cast iron lid having size 300mm x 300mm (Heavy) around the hole of excavation:- |
| 314 | Earthing with 8 SWG (4mm dia.) copper wire thimbled with 30cm x 60cm x 2mm thick copper plate burried 10.50 metre (34.44 feet) below ground level (up to 14metre in Length) with G.I. pipe 20mm dia. (A-class), 9metre long |
| 315 | Additional Length copper wire 8 S.W.G. (4mm dia.) in 20mm dia. G.I. pipe (On Surface) |
| 316 | MCCB's (MOULDED CASE CIRCUIT BREAKER):Supply and erection of Moulded Case Circuit Breaker (Panel mounting Cubicle type) in the existing Cubical Panel (conforms to IEC:60947-II) having Ics=100% Icu, 100% neutral with spreader links and relevant PWD General Specifications (Electrical Works) complete with G.I. Bolts, Nuts & Connection on both sides of MCCB with sutiable size of Thimbles etc. |
| 317 | MCCB Four Pole 40amp., 415volts, ≥25kA Fixed Magnetic and Adjustable Thermal Setting |
| 318 | MS SHEET ENCLOSURE FOR MCCB's:Supply & Erection of indoor type MCCB enclosure of suitable size having provision for MCCB with extended rotary handle. The Enclosure shall be made from 14/16 SWG CRCA sheet, confirming to IS 8623/1977-82. The door should be double folded without edge and the gasket should be ‘S’ type puffed neutral rubber gasket for long life. The hinges of the door should be bolted type with double hole arrangement. The Enclosure door lock should be quick openable type spring loaded. There should not be any special tool or key to open the lock. The Enclosure will be wall mounting type having provision for cable entry from bottom/top with cable glands etc. The sheet metal is sprayed with corrosion resistant etch primer. The finishing treatment shall be applicable with air drying paint (7/9 tank Powder coated process should present in company pemises) after necessary putty work:- |
| 319 | MS Sheet Enclosure having provision for MCCB 40-160Amp.with extended rotary handle (Approx. Size 500mm x 300mm x 200mm) |
| 320 | SHEET METAL DOUBLE DOOR DISTRIBUTION BOARD FOR MCB/ RCBO/ RCCB's:Supply and erection of sheet metal Double Door Distribution Boards IP 43- IK09 metal door (dust protected) as per IS 8623-1&3, IEC 61439-1&3 suitable for flush mounting with fully insulated copper busbars, shrouded neutral bars, earth bars, cement spill protector, colorcoded interconnecting wire set, cable ties, blanking plates and circuit identifications label and of required no. of ways for mounting miniature circuit breakers/ RCBO's/ RCCB's in the distribution board (For SP&N distribution board with provision DP MCB's/ RCCB's/ RCBO's as incomer and SP MCB's as outgoings and for TP&N horizontal distribution board with provision TPN/ FP MCB's/ RCCB's/ RCBO's as incomer and SP MCB's as outgoings) as per PWD General specifications including connections with suitable size of thimbles and bonding to existing earth etc:- |
| 321 | SP&N Double Door Distribution Board 8 way each |
| 322 | Supply and erection of sheet metal Cable End Box (Make is same as MCB Distribution Board) mounting on the top or bottom of the MCB Distribution Board (Either Horizontal or Vertical) to keep loose wires & cables as per PWD General specifications including petty materials etc as required:- |
| 323 | Cable End Box for SPN 8 Way |
| 324 | MINIATURE CIRCUIT BREAKERS:Supply and erection of Miniature Circuit Breaker MCB's for circuit protection against overload and short circuit current fault suitable for 240/ 415 volts 50cycles AC supply with breaking capacity of 10kA, Curve-C and low watt losses as per IS/IEC 60898-1, energy limitation class-3, true contact indication, label holder facility in the existing MCB distribution board as per PWD General Specifications including connections with suitable size of thimbles/lugs:- |
| 325 | MCB Single Pole 6-32amp. (10kA, Curve-C) |
| 326 | MCB Double Pole 6-32amp. (10kA, Curve-C) |
| 327 | Providing EPABX System: |
| 328 | Supply, installtion, testing & commisioning of Analog phone with caller id and hand free facility. Make: Beetal/ Mitel/ Panasonic complete in all respect as per satisfaction of the Engineer in charge of the work. |
| 329 | Supply Installation Testing and Commissioning of 20 Pair DB with Original Krone Module lock & key facility complete along with erection of the same with connections, testing etc. complete in all respects as approved and desired by the Engineer-in-charge at site. |
| 330 | RECESSED TV, TELEPHONE & NETWORKING SOCKETS OUTLET POINTS (USED FOR HGW, PVC CONDUIT & HDPE PIPE WIRING SYSTEM WITH MODULAR ACCESSORIES):Supply and erection of TV socket, Telephone socket and Networking socket points in powder coated/anodized concealed metal boxes recessed in wall required for suitable number of modules (Modular accessories) for having TV sockets, Telephone sockets RJ11 & Networking socket RJ45 (one module), covered with Frame Plate and other petty material etc., including the cost of above material, cutting and filling up of chases (with finishing the surface):- |
| 331 | Wiring Telephone socket point RJ11 (one module) |
| 332 | Supply and erection of telephone cable with solid bare copper conductor, special grade PE insulation, paired, polyster taped, nylon rip cord, FR PVC sheathed, conforming to TEC Specification No. G/WIR-06/03 left bare in pipe or casing of suitable size complete in all respect as desired by the Engineer-in-charge:- |
| 333 | Telephone Cable 0.5 Sq.mm, 2 Pair |
| 334 | Telephone Cable 0.5 Sq.mm, 20 Pair |
| 335 | PVC, HDPE PIPES & PVC FLEXIBLE PIPES:Supply & erection of PVC Conduit Pipes (ISI marked) as per IS9537:Part-III & HDPE pipes (ISI marked) as per IS:4984:1995 for wiring purposes including bends, junction boxes, Steel hooks, M.S. saddle clamps and other petty materials etc., as per PWD General Specifications:- |
| 336 | Heavy gauge PVC conduit pipe 25mm dia. (ISI marked) Flushed |
| 337 | PVC, HDPE PIPES & PVC FLEXIBLE PIPES:Supply & erection of PVC Conduit Pipes (ISI marked) as per IS9537:Part-III & HDPE pipes (ISI marked) as per IS:4984:1995 for wiring purposes including bends, junction boxes, Steel hooks, M.S. saddle clamps and other petty materials etc., as per PWD General Specifications:- |
| 338 | HDPE Electrical Conduit Pipe 25mm dia. (Flushed) |
| 339 | HDPE Electrical Conduit Pipe 40mm dia. (Flushed) |
| 340 | Providing Networking System along with allied accessories: |
| 341 | Supply, Installation and Comissioning of Distribution Switch with minimum usable 24 10/100/1000BASE-T ports, 2 10GBASE-T ports , 4 10G SFP+ ports L3 Stackable Managed Switch with Redundant Power Supply Support.1 x RJ45 console port, RJ-45 port for out-of band-management port for accessing the CLI of the switch and USB port. 168 Gbps Switching capacity or higher or non-blocking architecture. 64 Bytes packet forwarding rate should be 125 Mpps or higher. Switch MAC table should be at least 16K or higher. Physical Stacking up to 9 units per stack. Stacking bandwidth up to 80G and up to 32 devices per virtual stack. Should have 802.1D STP, 802.1w RSTP and 802.1s MSTP Spanning Tree Protocol and ERPS as per standard ITU-T G.8032. BPDU Filter, BPDU restriction, Root restrction. Loopback detection (LBD). IGMP Snooping v1/V2/V3 & IGMP groups 1K or more IGMP groups and require support for IGMP Snooping Fast Leave. MLD Snooping v1/v2 & MLD group 1K or more and require support for MLD Snooping Querier. 16 L3 IP interfaces and IPv4/IPv6 Loopback interface. IPv6 Neighbor Discovery (ND). VRRPv3, Equal-Cost Multi-Path (ECMP) and UDP helper. Static route for both IPv4 and IPv6, OSPFv1, v2 & v3, RIP V1/V2/ng. Should have Policy-based Route (PBR). IEEE 802.1Q VLAN with different type of VLAN like Port based, Voice VLAN, Private, Double (Q-In-Q), Multicast VLAN (ISM VLAN for IPv4/IPv6), 802.1v Protocol VLAN ,VLAN Trunking. should have per-port broadcast, multicast, and unicast storm control to prevents faulty end stations from degrading overall systems performance. port security to secures the access port based on MAC address. Require prevention of DoS attacks, which include Land, Blat, TCP Null Scan, TCP Xmas Scan, TCP SYNFIN, Ping of Death Attack and TCP Tiny Fragment attack. DHCP snooping and DHCP server screening, DHCP server. 802.1X port based and 802.1X host based access control, Identity-driven Policy (VLAN, ACL or QoS) Assignment. RADIUS and TACACS+ authentication. Authentication database failover. QoS (quality of service) IEEE 802.1P for traffic prioritization. 8 queues per port. Different type of QoS priority like Strict Priority Queue and Weighted Round Robin, Strict + WRR, Congestion control using Weighted Random Early Detection (WRED) or WTD. Remark 802.1p priority, Remark ToS/DSCP and Rate limiting in Policy map. Support at least 2K ingress & 512 egress access control entries. ACL based on MAC, IPv4 and IPv6, TCP/UDP port number, User-defined packet contentm, CPU Interface Filtering. Able to manage trough Web-GUI, Fully functional CLI interface and Telnet. Should have multiple Image and configuration support to reduced down time for the switches. sFlow for monitoring traffic in data networks, SNMP v1, v2c, v3 and SNMP Traps and RMON. Support for DHCP Client support for IPv4/IPv6, DHCP server, DHCP Relay and DNS client. Should have SNTP/NTP protocol for time synchronization. CDP/UDLD, Link Layer Discovery Protocol (LLDP) and LLDP-MED.. CDP/UDLD, Link Layer Discovery Protocol (LLDP) and LLDP-MED. Operating temperature should be 0 to 50 ˚C. Switch should be EMI Certificates FCC, CE and Safety Certifications cUL/UL, CB. All Switches, Wireless and its Networkiing Components from Same OEM. OEM Should be International certification for the ISO 45001 Health and Safety Management System, Information Security Management System: ISO 27001, ISO 9001 Quality Management System, ISO 14001 Environmental Management System, and ISO 14064-1 Greenhouse Gas Inventory Standards. OEM should have Indian based operation at least for a period of 20+ years and should have an Annual Turnover of Rs. 500 Crores and above in any of last three consecutive Audited Financial years. (To ensure only principal networking companies participate having strong Product, Support and Service.) complete in all respect as per satisfaction of the Engineer in charge of the work. |
| 342 | Supply, Installation and Comissioning of Patch Panel should be made of cold rolled steel.Should conform to TIA / EIA 568-C.2 Component Compliant.Should terminate 24 UTP CAT 6 (4 pair) Cables.Should confirm to EIA/TIA 568A wiring Pattern.Each port Should be features the spring-loaded shutter.Should be prevents incomplete mating Should be protects from dust and contaminants.Should be Front and rear port labelling as well as panel identification label.Should be Integral cable management shelf ensures bend radius compliance.Operating Life should be minimum 750 insertion cycles.Should be RoHS compliant.. complete in all respect as per satisfaction of the Engineer in charge of the work. |
| 343 | Supply, Installation and Comissioning of Patch Cord 1 Mtr Patch cord Should be 4 Pairs 24 AWG copper cables.The Outer Jacket should be Low Smoke Zero Halogen.24 AWG stranded bare copper.Operating temperature range should be -20°C to 60°C.Should minimum comply with proposed ANSI/TIA/EIA-568-C.2.Should be verified by ETL (ETL certificate to be enclosed with the Bid)UL listed (UL certificate to be provided along with the Bid)Should Have cross separator.Standard length should be available 0.5M to 10M.Should be RoHS compliant. . complete in all respect as per satisfaction of the Engineer in charge of the work. |
| 344 | Supply, Installation and Comissioning of Patch Cord 2 Mtr. Patch cord Should be 4 Pairs 24 AWG copper cables.The Outer Jacket should be Low Smoke Zero Halogen.24 AWG stranded bare copper.Operating temperature range should be -20°C to 60°C.Should minimum comply with proposed ANSI/TIA/EIA-568-C.2.Should be verified by ETL (ETL certificate to be enclosed with the Bid)UL listed (UL certificate to be provided along with the Bid)Should Have cross separator.Standard length should be available 0.5M to 10M.Should be RoHS compliant..complete in all respect as per satisfaction of the Engineer in charge of the work. |
| 345 | Supply, Installation, Testing and Commissioning of 27U Network Enclosure Frame-600X800-STEEL with accessories like fan, pdu, cable manager etc. Supply of 27U Enclosure Frame-800X1000-STEEL, Caster Wheels Set of 4 (2 with Brakes & 2 without Brakes),Adjustable Levellers set of 4, Glass Door-800-27U, Metal Door-800-27U-Vented, Side Panels-1000-27U-Vented, Mounting Hardware-(Pack of 20), FHU with 4 FAN 360CFM, Vertical Power Distribution Unit with 12 x 5/15 sockets Round Pin, 230 Volts AC, 32 Amp with Plug, Vertical Cable Manager-27U-Loop, Horz. Cable Manager-1U-Loop, Conforms to DIN 41494 OR equivalent ISO Standards, Adjustable 19” equipment mounting verticals provide the better mounting flexibility maximizing the usable mounting space, Depth adjustable mounting slots, Top and bottom Panel with ventilation and cable entry facility, Provision to mount the cooling fans on the top panel, Powder coated finish with pretreatment process meeting all industry standards, Grounding and Bonding Options can be provided, 100% assured compatibility with all equipment conforming to DIN 41494. General industrial standard for equipment, Conforms to DIN 41494 or equivalent standard, Welded Frame, Lockable Toughened Glass Door, Metal Vented Door Steel, DIN Standard 10mm Sq. Slots / Direct M6 Tap, 19” Mounting angles made of formed steel Powder Coated, Welded to Frame, Vented and Field Cable entry exit cut outs complete in all respect as per satisfaction of the Engineer in charge of the work. |
| 346 | Supply, Installation, Testing and Commissioning of Wall Mount 15U x 600 W x 600 D ,Front Glass Door (tinted,Toughened) with Lock & Key, 2 pairs of 19\\" Mounting Rails with U-Marking , Welded Side Walls, Min Accessories : 1U Cable Manager (1), Hardware Packet (1 Pkt), 6 Socket 5 Amp. Power Distribution Unit (1 No), Roof Mounted Fan Unit / 90 CFM /230V AC.as per DIN 41494 Standards complete in all respect as per satisfaction of the Engineer in charge of the work. |
| 347 | Supply, Installation, Testing & Commissioning of 1000VA LIT UPS/ Power Plant with SMF batteries having 30 Minutes backup time, Cold Start, 3 No. plug Indian style, Automatic Voltage Controller, Overload protection, Over charging Protection, 2 No. 12v 7Ah Batteries, Wide Input Range, Fan Less Cooling system, Transfer time less than 8ms,Audible Alarm etc. complete in all respects as approved and desired by the Engineer in-charge at site. |
| 348 | RECESSED TV, TELEPHONE & NETWORKING SOCKETS OUTLET POINTS (USED FOR HGW, PVC CONDUIT & HDPE PIPE WIRING SYSTEM WITH MODULAR ACCESSORIES):Supply and erection of TV socket, Telephone socket and Networking socket points in powder coated/anodized concealed metal boxes recessed in wall required for suitable number of modules (Modular accessories) for having TV sockets, Telephone sockets RJ11 & Networking socket RJ45 (one module), covered with Frame Plate and other petty material etc., including the cost of above material, cutting and filling up of chases (with finishing the surface):- |
| 349 | Wiring Networking socket point RJ45 (one module) |
| 350 | COPPER CONDUCTOR CABLES FOR SPECIAL ELECTRICAL SERVICES:Supply and erection of CAT 6 with 23AWG solid bare copper conductor, special grade PE insulation with star separator, 4pair Unshielded Twisted Pair (UTP) industrial cable, FR PVC sheathed, Class-E, 250 MHz of bandwidth, supporting data transfer speeds of up to 10 Gbps (10GBASE-T) for distances up to approximately 180 feet, cables are manufactured and tested to meet the ANSI/TIA 568-C.2 and ISO/IEC 11801 Class E standards left bare in pipe or casing of suitable size complete in all respect as desired by the Engineer-in-charge:- |
| 351 | CAT 6 LAN cable |
| 352 | PVC, HDPE PIPES & PVC FLEXIBLE PIPES:Supply & erection of PVC Conduit Pipes (ISI marked) as per IS9537:Part-III & HDPE pipes (ISI marked) as per IS:4984:1995 for wiring purposes including bends, junction boxes, Steel hooks, M.S. saddle clamps and other petty materials etc., as per PWD General Specifications:- |
| 353 | Heavy gauge PVC conduit pipe 25mm dia. (ISI marked) Flushed |
| 354 | Providing CCTV System: |
| 355 | Supply, erection, testing & commissioning of Indoor STQC Approved 3 MP IP WDR IR Rugged Mini Dome Camera OPERATIONAL: Video Standard: NTSC / PAL, Scanning System: Progressive, Image Sensor: 1/2.7” CMOS, Sensor Size (H x V): 4.608 mm x 2.592 mm, Number Of Pixels (H x V): 2304 x 1296, Minimum Illumination (Color/BW): .005 Lux / F1.6 (Color, 30 IRE), 0 Lux / F1.6 (IR ON), S/N Ratio: 50 dB, Electronic Shutter Speed: 1/8 ~ 1/32,000, IR Distance: up to 40 m, IR Light Control, Smart IR ( Auto / Manual ) / OFF, IR Light Number: 2, Day/Night: Auto (ICR) / Color / BW, Backlight Compensation: WDR, BLC, HLC, White Balance: Auto/Tungsten/ Fluorescent/ Daylight/Shadow/Manual, Gain Control: 0-100%, Wide Dynamic Range: 120 dB, Noise Reduction: 2D / 3D DNR, Lens: : 2.8 mm Fixed Iris, F1.6, Angle Of View: H: H:88°°, V:47°, Privacy Masking: Off / On (4 Areas), Defog: Not supported, Local Storage: Micro SD (up to 256 GB), Alarm Inputs/Outputs: Not supported, Pan Range: 0°-330°, Tilt Range: 0°-75°, Rotation Range: 0°-337°, Video Compression:H.265 HEVC/H.264/MJPEG, Smart Codec, Resolution: 1st: 2304 x 1296 / 1920 x 1080 / 1280 x 720 2nd: 704 x 576 (PAL) / 704 x 480 (NTSC) / 640 x 480 / 352 x 288 (PAL) / 352 x 240 (NTSC) 3rd: 640 x 480 / 352 x 288 (PAL) / 352 x 240 (NTSC) / 320 x 240, Number of Video Streams: 3 (2 for encryption), Frame Rate*: MAX 30 fps, Bit Rate*: 100K ~ 6 Mbps, Audio Compression: Not supported, Audio Stream: Not supported, Audio Interface: Not supported, NETWORK: Ethernet: 10 Base-T/100 Base-TX Ethernet (RJ-45), Supported Web Browsers: Chrome / Edge, Supported OS: Microsoft Windows 10, Protocols**: IPv4, IPv6, TCP / IP, HTTP, HTTPS, RTSP / RTP / RTCP, IGMP / Multicast, SMTP, DHCP, NTP, DNS, QoS, SNMP, 802.1X, UDP, ICMP, ARP, TLS, Interoperability: ONVIF Profile G/S/T, Maximum Users Access: 10 Users, Security: User account and password protection, HTTPS, IP Filter, Digest authentication, TLS1.2 only, Stream encryption, AES128 / 256, SSH / Telnet closed, PCI-DSS compliance, EVENTS / ANALYTICS: Built-in Video: Analytics, Motion Detection, Tampering, Event Type: Video motion detection,Recording notification, Event Linkage: Event notification using Email and MicroSD card, Region Of Interest: 8, ELECTRICAL: Power Supply: DC12V, PoE (IEEE 802.3af) (Class 0), Power Consumption (Max): MAX 3.6 W, MECHANICAL: Dimensions: Ø110.0 mm × 85.6 mm (Ø4.33” × 3.37”), Dome Diameter Ø78.2 mm (3.08”), Product Weight 0.56 kg (1.23 lb), Package Weight 0.65 kg (1.43 lb), Body Material Die-cast aluminium housing, ENVIRONMENTAL: Operating Temperature: Starting Temperature:-40°C ~ 60°C (-40°F ~ 140°F), Working Temperature: -40°C ~ 60°C (-40°F ~ 140°F), Relative Humidity Less than 90 %, non-condensing, Ingress Protection IP67, Impact Resistance IK10, REGULATORY: Emissions: FCC PART 15, CE (EN 55032), Complies with RCM and UKCA, Immunity CE(EN 50130-4), Complies with RCM and UKCA, Safety: UL LISTED TO UL/CSA 62368-1, CE(EN 62368-1), Complies with RCM and UKCA, RoHs: CE(EN 63000).complete in all respect as per satisfaction of the Engineer in charge of the work. |
| 356 | Supply, erection, testing & commissioning of 64 Channel NVR (Network Video Recorder shall be support the STQC Cameras) Main Processor ARM Processor Operating System Embedded LINUX Onvif Compliance ONVIF Profile S User Management User level: Administrator, Regular user Log System, Recording, User Date & Time Time Zone, Manual, Automatic Sync NTP, Daylight Saving Time Fan Yes Security Encrypted streaming and control, Inputs 64 channels, Audio Input/ Output 3.5 mm Line in x1 3.5 mm Line out x1 Two-way Communication Supported Audio Format G.711, Interface HDMI 1 (4K Max), HDMI 2 (1080P), VGA x1 (1080P), Resolution : 3840 x 2160, 1920 x 1080, 1280 x 1024, 1024 x 768, Display Split : 1/4/9/16/32/64, OSD Time OSD, channel OSD, Stream Application 1 X 1: 1 ch 12 MP MAX 2 x 2: 4 ch 4 K 4 x 4: 16 ch 2 MP 8 x 8: 64 ch D1, PTZ Operation Direction control, Home, Iris, Preset, Patrol(group), Focus +/- Zoom+/ Compression H.265/H.264 Resolution Up to 3840 x 2160 Frame Rate 30 fps Recording Mode Continuous, Manual, Event Pre-Event Recording Interval Main stream: 2M Sub stream: 1M Post-Event Recording Interval 30 s (Max. 60 s) Recording Stream Camera Stream 1 Camera Stream 2, Recording Throughput 320M, Event Camera: Camera Alarm In, Motion detection, Camera disconnection,Tampering detection System: System Alarm in/out, Disk failure, Disk full, VA (SMD/intrusion/crowd/Multi loitering detection) Event Action Video recording, Send email, Buzzer, FTP, Camera Alarm Out, PTZ-Preset, System Alarm Out,Send video to full screen, Alarm Input 16, Alarm Out 6, RS485 Supported RS232 Supported e-SATA Supported, INTERNAL HDD Internal x8 (3.5\\"), HDD Max. Capacity 10TB Manual Backup USB Dongle (FAT Format) Raid Raid 1\5\6, Sync Playback 16 channels, Decoding H.265/H.264: 4000 x 3000 @ 30 fps (1-CH) 3840 x 2160 @ 120 fps (4-CH) 720 x 576 @ 480 fps (16-CH) Search Mode Time search, Event Search, video clip Playback Function Regular (play, pause, stop), play backwards, next frame, Go back 30 seconds, Go forward 30 seconds, speed control, timeline, timeline scale,Digital zoom, snapshot, back up Snapshot JPG, Ethernet 10/100/1000Mbps Ethernet (RJ-45) x 2 PoE N351604xxR: 802.3at/af compliant PoE ports x 16 Supported Protocols IPv4, IPv6, TCP/IP, HTTP, HTTPS, UPnP, RTSP/RTP/RTCP, SMTP, FTP, DHCP, NTP (Secure), DNS, DDNS, IP Filter, P2P, SNMP Maximum Number Of Users 16, Network Throughput 400M, Smart Phone Compatibility IOS 11 or later and Android 5.0 or later support Browers Edge, Chrome, Firefox, safari, USB Ports Front x 2, usb2.0; Back x1, usb3.0, Power Supply :100-240V AC, 50/60HZ,DUAL SMPS, Operating Temperature -10°C ~ 55°C (14°F ~ 131°F) Relative Humidity Less than 90% RH Storage Temperature –40°C to 60°C (-40°F ~ 140°F), Emissions FCC Part 15, CE (EN 55032, EN 61000-3-2, EN 61000-3-3, EN 61000-6-4), ICES-003, Comply with UKCA and RCM Immunity CE (EN 50130-4, EN 55035) Comply with UKCA and RCM Safety UL LISTED TO UL/CSA 62368-1, CE(EN 62368-1), Comply with UKCA and RCM RoHS CE(EN 63000), UAE (Cabinet Decree No.10 of 2017) complete in all respects as approved and desired by the Engineer-in-charge at site. |
| 357 | Supply, erection, testing & commissioning of Switches: 24 Ports 10/100/1000 Mbps PoE + 4 Ports 10G SFP+ Smart Managed Layer 2 Switch, Power budget 370W from day1, Support 802.3af/at), Switching Capacity 128 Gbps, MAC Address Table 16K, Packet Forwarding Rate, 95.24 Mpps, Flash Memory 64 MB, DRAM Size 256 MB DDR3, IGMP v1/v2/v3 Snooping & MLD snooping v1/v2, 802.3x Flow Control, HOL Blocking Prevention, LLDP/ LLDP-MED, 802.1D, 802.1W, 802.1s, 802.1Q, 802.1p QOS, SPQ, WRR, WDRR, Bandwidth Control, Static routing, IPv6 Neighbor Discovery (ND), ACL Max. 768 rules shared by IPv4, MAC, & IPv6, Traffic segmentation, ARP Spoofing Prevention, ARP Inspection, DHCP Snooping, MAC authentication, SSH v2, TLS v.1.2, DoS attack prevention, 802.1X Port-based Access Control, Port Security, RADIUS/TACACS+, MD5 authentication, GUI, Full CLI, Telnet Server, TFTP Client, MDI/MDIX, SNMP v1/v2c/v3. Internal/External 6 kV surge protection on all RJ-45 access ports, Operating Temperature -5 to 50°C, Storage Temperature -20 to 70°C, Operating Humidity 0% to 95% relative humidity, Certifiate: EMC EN 55032, Class A; EN 61000-3-2; EN 61000-3-3; EN 55024, Safety EN 62368-1, ROHS EN IEC 63000, 47 CFR FCC part 15: 2017, Subpart V, Class A, ICES-003, IEC 62368-1, IEC 60950-1, IEC 60950-1/AMD1, IEC 60950-1/AMD2, UL 62368-1 & CAN/CSA C22.2 No. 62368-1-14. MTCTE/TEC-ER (as notified vide Indian Telegraph (Amendment) Rules, 2017, OEM Should be ISO 45001, ISO 27001 & ISO 14001 Certified, OEM Should have Certificate for Industrial Cyber Security Capability (Like - IEC-62443-4-1:2018 or Equivalent) complete in all respects as approved and desired by the Engineer-in-charge at site. |
| 358 | Supply, erection, testing & commissioning of Switch 8 x 10/100/1000BASE-T PoE Ports, 2 x SFP ports & RJ-45 console port. 802.3at PoE+ & 802.3af PoE power 130W, IEEE 802.3i 10BASE-T Ethernet, IEEE 802.3u 100BASE-TX Fast Ethernet, IEEE 802.3ab, IEEE 802.3az, IEEE 802.3x, IEEE 802.3z. 20 Gbps Switching Capacity & Packet Forwarding Rate 14 Mpps, 8K MAC address. DRAM Size DDR3 128MB, Flash Memory Size 32MB, Fanless Design, CPU Speed 500MHz. Packet Buffer Size 4.1MBits. Operating & Storage Temperature -5 to 50 °C & -40 to 70 °C. Operating & Storage Humidity 10% to 90% & 5% to 90%, Loopback detections. IGMP Snooping v1, v2 & MLD snooping v1/v2. IEEE 802.1AB LLDP & LLDP-MED. IEEE 802.3az (EEE), 4K VLAN ID's, Min 256 static VLAN, Multicast VLAN & Auto Voice & Video VLAN, Port Mirroring 1 x to one/Many to One, 802.1p Quality of Service (QoS), SPQ, WRR, Bandwidth Control, Static routing for inter-VLAN Communication, Access Control List (ACL), L2 & L3 ACL (IPv4 & IPv6), Broadcast/Multicast/Unicast Storm Control, Traffic segmentation, TLS, DoS attack prevention, 802.1X Port-based Access Control, Port Security, ARP Spoofing Prevention, DHCP Server Screening, IP-MAC-Port Binding, ARP Inspection, DHCP Snooping, 802.1X Authentication local/RADIUS database (IPv4 & IPv6), port-based access control, EAP, OTP, TLS, TTLS, PEAP & Support MD5 authentication, features Cable diagnostics, IPv4 & IPv6 Inspection, SSH v2 feature, 802.3x Flow Control & HOL Blocking Prevention, Management thru Web-based & CLI, SNMP v1/v2c/v3, NTP/SNTP, IPv4/v6 Dual Stack, Dual image, Dual configuration. Product Should Approved from TEC under Mandatory Testing & Certification of Telecom Equipment as notified vide Indian Telegraph (Amendment) Rules, 2017. CE, FCC, UL, IEC/EN 60950 & IPv6 Ready compliance. OEM Certification for ISO 45001, ISO 9001, ISO 14001, & ISO 14064-1, IEC 62443-4-1 complete in all respects as approved and desired by the Engineer-in-charge at site. |
| 359 | Supply, erection, testing & commissioning of HDD Formatted capacity 6 TB, Data transfer rate (max) Buffer to host Host to/from drive (sustained) 6 Gb/s 171 MB/s, Cache (MB) 64, Rotational speed (RPM) IntelliPower, Load/unload cycles4 300,000, Non-recoverable read errors per bits read <1 in 1014,Operating (2 ms, read/write) 30,Operating (2 ms, read) 65, Non-operating (2 ms) 250,Average power requirements (W) Read/Write 5.90, Idle 4.90, Standby and Sleep 0.40 complete in all respects as approved and desired by the Engineer in-charge at site. |
| 360 | Supply, erection, testing & commissioning of Display : 50 inch, 4K (3,840 x 2,160), Direct LED, Professional Display with 4K Processor, Native Contrast ratio 5,000:1 or higher, Response time 12 ms or lower, Brightness 400 cd/m² or higher, 24/7, Portrait/Tilt functionality, HDMI Auto wake up, HTML5 platform, 16GB On Board Storage, HDMI*4 with HDCP 2.3 / RS232 / USB / RJ45 / Wi-Fi Direct / 20W Speakers / Android OS or similar, Viewing angle 178 degree, Apple AirPlay & Chromecast. complete in all respects as approved and desired by the Engineer-in-charge at site. |
| 361 | Supply, Installation, Testing & Commissioning of 6 Mtr HDMI Cable for NVR, UL Listed complete in all respects as approved and desired by the Engineer in-charge at site. |
| 362 | Supply, Installation, Testing & Commissioning of 1000VA LIT UPS/ Power Plant with SMF batteries having 30 Minutes backup time, Cold Start, 3 No. plug Indian style, Automatic Voltage Controller, Overload protection, Over charging Protection, 2 No. 12v 7Ah Batteries, Wide Input Range, Fan Less Cooling system, Transfer time less than 8ms,Audible Alarm etc. complete in all respects as approved and desired by the Engineer in-charge at site. |
| 363 | Supply, Installation, Testing and Commissioning of Wall Mount 15U x 600 W x 600 D ,Front Glass Door (tinted,Toughened) with Lock & Key, 2 pairs of 19\\" Mounting Rails with U-Marking , Welded Side Walls, Min Accessories : 1U Cable Manager (1), Hardware Packet (1 Pkt), 6 Socket 5 Amp. Power Distribution Unit (1 No), Roof Mounted Fan Unit / 90 CFM /230V AC.as per DIN 41494 Standards complete in all respect as per satisfaction of the Engineer in charge of the work. |
| 364 | COPPER CONDUCTOR CABLES FOR SPECIAL ELECTRICAL SERVICES:Supply and erection of CAT 6 with 23AWG solid bare copper conductor, special grade PE insulation with star separator, 4pair Unshielded Twisted Pair (UTP) industrial cable, FR PVC sheathed, Class-E, 250 MHz of bandwidth, supporting data transfer speeds of up to 10 Gbps (10GBASE-T) for distances up to approximately 180 feet, cables are manufactured and tested to meet the ANSI/TIA 568-C.2 and ISO/IEC 11801 Class E standards left bare in pipe or casing of suitable size complete in all respect as desired by the Engineer-in-charge:- |
| 365 | CAT 6 LAN cable |
| 366 | PVC, HDPE PIPES & PVC FLEXIBLE PIPES:Supply & erection of PVC Conduit Pipes (ISI marked) as per IS9537:Part-III & HDPE pipes (ISI marked) as per IS:4984:1995 for wiring purposes including bends, junction boxes, Steel hooks, M.S. saddle clamps and other petty materials etc., as per PWD General Specifications:- |
| 367 | Heavy gauge PVC conduit pipe 25mm dia. (ISI marked) Flushed |
| 368 | Providing Fire Detection/ Emergency Evacuation & PA System: |
| 369 | FIRE PANELS & ANNUNCIATORS: |
| 370 | Supply, installation, testing & Commissioning of Loop Cards Class A Wiring with min. supporting cable length Up to 1.2 Km UL & FM Approved complete in all respects as approved and desired by the Engineer in-charge at site. It includes the (CAMC of 2 Years after completion of one year defect liability period) |
| 371 | Supply, installation, testing & Commissioning of chassis (Small size) for Amplifier and Digital Series Distribution Board. Chassis should be fabricated from 14-gauge steel, e key-locked door is provided with a pin-type hinge, two keys and the necessary hardware to mount the door, Right- or left-hand hinges, selectable in the field. Door opens 180°, door should be heat dissipation refers to the process of transferring heat away from a system, component, or device to maintain its temperature within acceptable limits. Chassis should be of same make OEM as complete in all respects as approved and desired by the Engineer in-charge at site. It includes the (CAMC of 2 Years after completion of one year defect liability period) |
| 372 | Supply, installation, testing & Commissioning of Addressable photo-Thermal multi criteria Detector and base with sensitivity range as per NFPA 72. The intelligent detection device shall include the ability to combine the signal of the thermal sensor with the signal of the photoelectric signal in an effort to react hastily in the event of a fire situation. It shall also include the inherent ability to distinguish between a fire condition and a false alarm condition by examining the characteristics of the thermal and smoke sensing chambers and comparing them to a database of actual fire and deceptive phenomena. The detector shall have bi-colour LED for 360 deg viewing. Addressing shall be with user friendly rotary/ Electronic decimal switches. Designed to meet UL & FM Approved . The solution should be from single OEM. complete in all respects as approved and desired by the Engineer in-charge at site. It includes the (CAMC of 2 Years after completion of one year defect liability period) |
| 373 | Supply, installation, testing & Commissioning of Reponse Indicator for up side of ceiling complete in all respects as approved and desired by the Engineer in-charge at site. It includes the (CAMC of 2 Years after completion of one year defect liability period) |
| 374 | Supply, installation, testing & Commissioning of Addressable Smoke photo-Thermal Detector and base with sensitivity range as per NFPA 72. The intelligent detection device shall include the ability to combine the signal of the thermal sensor with the signal of the photoelectric signal in an effort to react hastily in the event of a fire situation. It shall also include the inherent ability to distinguish between a fire condition and a false alarm condition by examining the characteristics of the thermal and smoke sensing chambers and comparing them to a database of actual fire and deceptive phenomena. The detector shall have bi-colour LED for 360 deg viewing. Addressing shall be with user friendly rotary/ Electronic decimal switches. Designed to meet UL & FM Approved . The solution should be from single OEM. complete in all respects as approved and desired by the Engineer in-charge at site. It includes the (CAMC of 2 Years after completion of one year defect liability period) |
| 375 | Supply, installation, testing & Commissioning of Addressable Rate of Rise Heat Detector rated at 8.3 deg C/min.NFPA 72. The detector shall have bi-colour LED for 360 deg viewing. Addressing shall be with user friendly rotary/ Electronic decimal switches.UL & FM Approved The solution should be from single OEM.complete in all respects as approved and desired by the Engineer in-charge at site. It includes the (CAMC of 2 Years after completion of one year defect liability period) |
| 376 | Supply, installation, testing & Commissioning of Addressable High Sensitivity Photo Detector with sensitivity level of 0.02% to 2% Obs/Feet. Mandatory for critical room like Server room,Computer room ,UPS Room,Record Rooms , Mal-Khana and almed room. The detector shall have the optic block to amplify signals from smoke, but diminish stray internal reflections that can cause false alarms. The detector should have on board drfit compensation, transient rejecion algoritms with superiro EMI protection. The detector shall have twin bi-colour LED for 360 deg viewing. Addressing shall be with user friendly rotary decimal switches. Designed to meet UL268, 7th Edition. UL & FM Approved complete in all respects as approved and desired by the Engineer in-charge at site. It includes the (CAMC of 2 Years after completion of one year defect liability period) |
| 377 | Supply, installation, testing & Commissioning of Addressable wireless mesh technology based photo electric smoke detector. The detector shall work within the legitimate working freequency band between 865 MHz to 867 MHz. The detector shall be able to communicate with the wireless gateway. The detector shall have the sensitivity range of 0.5 to 4.0% obs/ft. The detector shall have twin bi-colour LED for 360 deg viewing. Addressing shall be with user friendly rotary decimal switches. The battery life shall have minimum of 2 years. the detector shall be configurable using software/dongle. The detector shall meet UL268, 7th guideline. It includes the (CAMC of 2 Years after completion of one year defect liability period) |
| 378 | Supply, installation, testing & Commissioning of Addressable wireless mesh technology based Multi-criteria Photo-Thermal Detector with sensitivity range of 0.5 to 4.0% obs/ft. The detector shall work within the legitimate working freequency band between 865 MHz to 867 MHz. The detector shall be able to communicate with the wireless gateway. The intelligent multi criteria detection device shall include the ability to combine the signal of the thermal sensor with the signal of the photoelectric signal in an effort to react hastily in the event of a fire situation. It shall also include the inherent ability to distinguish between a fire condition and a false alarm condition by examining the characteristics of the thermal and smoke sensing chambers and comparing them to a database of actual fire and deceptive phenomena. The detector shall have twin bi-colour LED for 360 deg viewing. Addressing shall be with user friendly rotary decimal switches. The detector shall meet UL268, 7th guideline. It includes the (CAMC of 2 Years after completion of one year defect liability period) |
| 379 | Supply, installation, testing & Commissioning of Addressable wireless mesh technology based Thermal Detector. The detector shall work within the legitimate working freequency band between 865 MHz to 867 MHz. The detector shall be able to communicate with the wireless gateway. The detector shall have twin bi-colour LED for 360 deg viewing. Addressing shall be with user friendly rotary decimal switches. Detector shall compluy UL521 guideline. complete in all respects as approved and desired by the Engineer in-charge at site. It includes the (CAMC of 2 Years after completion of one year defect liability period) |
| 380 | Supply, installation, testing & Commissioning of Addressable Manual Call Point (Pull down / Break Glass Type). The device shall have an LED which shall blink in normal state & get steady on activation to monitor the heath status of the device complete in all respects as approved and desired by the Engineer in-charge at site.UL & FM Approved complete in all respects as approved and desired by the Engineer in-charge at site. It includes the (CAMC of 2 Years after completion of one year defect liability period) |
| 381 | Supply, installation, testing & Commissioning of Sounder cum Strobe rated at 80 dBA @ 3m for Audible annunciation and Min.110 cd flashintg at 1 Hz for visual indication. UL & FM Approved complete in all respects as approved and desired by the Engineer in-charge at site. It includes the (CAMC of 2 Years after completion of one year defect liability period) |
| 382 | Supply, installation, testing & Commissioning of Addressable Control Module for Sounders / Strobes / Sounder cum Strobes/ Telephone Jack. The control module shall provide supervised NAC output rated at 24v DC, 2A. The device shall have an LED which shall blink in normal state & get steady on activation to monitor the heath status of the device. Addressing shall be with user friendly rotary / Electronic decimal switches UL & FM Approved complete in all respects as approved and desired by the Engineer in-charge at site. It includes the (CAMC of 2 Years after completion of one year defect liability period) |
| 383 | Supply, installation, testing & Commissioning of Monitor Module for Sprinklers, Panic Bars & other Third Party Inputs. The monitor module shall monitor potential free contacts. The device shall have an LED which shall blink in normal state & get steady on activation to monitor the heath status of the device. Addressing shall be with user friendly rotary/ Electronic decimal switches UL & FM Approved complete in all respects as approved and desired by the Engineer in-charge at site. It includes the (CAMC of 2 Years after completion of one year defect liability period) |
| 384 | Supply, installation, testing & Commissioning of Isolator Module for Isolating short / dewired / loose circuits with automatic resetting arrangement. Isolator Base can also be proposed, however in that case needs to be considered with each detector & module. The device shall have an LED which shall blink in normal state & get steady on activation to monitor the heath status of the device.UL & FM Approved Module shall be supplied with mounting plate from OEM for ease of installation & maintenance.The solution should be from single OEM.complete in all respects as approved and desired by the Engineer in-charge at site. It includes the (CAMC of 2 Years after completion of one year defect liability period) |
| 385 | Supply, installation, testing & Commissioning of Addressable Relay Module for AHU, Access Control, Lifts, Staircase Pressurization, Fire Suppression & other Third Party Outputs. The relay module shall provide contact rated at 24v DC, 2A. The device shall have an LED which shall blink in normal state & get steady on activation to monitor the heath status of the device. Addressing shall be with user friendly rotary/ Electronic decimal switches UL & FM Approved complete in all respects as approved and desired by the Engineer in-charge at site. It includes the (CAMC of 2 Years after completion of one year defect liability period) |
| 386 | Supply,installation, testing & Commissioning of Digital Audio Amplifier with transfarmer with cabinet and power supply as per site requierment . Amplifier shall be capable of N:N/N:1 configuration and shall be dual channel capable of processing Two of 8 audio channels and a total of Min 95 W ( It may be 1 unit or Combination of Multiple units to achieve the Requirement) at 70.7 VRMS output along with necessary enclosures with local FFT Raiser. The Digital Audio Amplifier shall be fully monitored for fault and alarm reporting. The proposed Digital Audio Amplifiers shall be (Wall/Panel Mounted). Integrated 8 channel Digital Voice Evacuation System Controller (as per requierment) capable of broadcasting Evacuation Messages on the same peer-to-peer Network and 2 ways Communication capable of supervising all the speaker circuits with adequate zone control and accessories. Failure of Fire Panel CPU shall not result in failure of DVC/Amplifier operation. Products not having this feature must provide dedicated CPU for DVC. The Evacuation System Controller shall have FFT Risers to control and conference minimum 30 Telephones.. Amplifiers shall be distributed across the building/floor to manage the sound attenuation problem & for the best sound intelligibility. All amplifiers can be back up of minimum 5 hours using secondary power source(battery power/UPS power) complete in all respects as approved and desired by the Engineer in-charge at site. It includes the (CAMC of 2 Years after completion of one year defect liability period) complete in all respects as approved and desired by the Engineer in-charge at site. |
| 387 | Supply, installation, testing & Commissioning of 2W Multi-Tap (0.25W; 0.5W; 1W; 2W), Ceiling/Wall Mount Speakers. The speakers shall be of the same make as that of the Control Panel & Amplifiers. They shall be compatible with supplied Amplifiers and shall work on 70.7Vrms UL Listed complete in all respects as approved and desired by the Engineer in-charge at site. It includes the (CAMC of 2 Years after completion of one year defect liability period) |
| 388 | Supply, installation, testing & Commissioning of Back Box for 2W Multi-Tap (0.25W; 0.5W; 1W; 2W), Ceiling/Wall Mount Speakers as per site requirement complete in all respects as approved and desired by the Engineer in-charge at site. It includes the (CAMC of 2 Years after completion of one year defect liability period) |
| 389 | Supply, installation, testing & Commissioning of Exit LED M ST LED LED based exit sign with dimming function, Reading distance, exit sign Two-sided 25m, Voltage 220-240VAC / 50-60Hz, Power consumption 3.3W / 3.5VA, Battery 3.6V/1.2Ah NiMH, Battery protection Over charge protection /deep discharge protection, Charging Time 16 hours, Battery back-up time 1 hour / 3 hours / 8 hours (from dip switch), Light source 15 LED, Approvals EN 60598-1, EN 60598-2-22, EN 55015, EN 61547, EN 61000-3-2, EN 61000-3-3, Ambient temperature 5 to 40 °C, Humidity Up to 95%, IK rating IK09, IP rating IP40, Dimensions 265 x 53 x 222 mm, Weight 540 / 742 gr , Colour Anodized aluminum / black plastic, Materials Aluminum, Acrylic Plate, Mounting method Ceiling, wall bracket, suspended, pendulum, flag mount, Delivered as self-contained/auto test luminaire Choice of 1, 3 or 8 hour autonomy via DIP switch IP 40 – dustproof luminaire Reading distance upto 25 meters.High lumen output – 1h = 180lm / 3h = 110lm /8h = 40lm Technical lifetime of LED > 100 000 hours , 4 Pictograms (left, right, down, up) are included in the luminaire ordering part code complete in all respects as approved and desired by the Engineer in-charge at site. It includes the (CAMC of 2 Years after completion of one year defect liability period) |
| 390 | Supply, installation, testing & Commissioning of Agora LED Emergency Light is a robust and efficient lighting solution designed to provide reliable illumination during power outages or emergency situations. Operating on a voltage range of 220–240VAC with a frequency of 50–60Hz, it consumes just 11.4W / 11.8VA of power, making it energy-efficient. It features a 12V / 7Ah lead-acid battery equipped with overcharge and deep discharge protection, requiring 23 hours to fully charge. Depending on the selected backup duration via DIP switch, it delivers 3200 lumens for 1 hour, 1600 lumens for 3 hours, or 800 lumens for up to 8 hours. The light source comprises two sets of six LEDs with a technical lifetime exceeding 100,000 hours. With an IP42 rating for dust and water resistance and an IK08 rating for impact protection, it’s built to withstand demanding environments. Certified under multiple international standards including Approvals: EN 60598-1 EN 60598-2-22 EN 55015 EN 61547 EN 61000-3-2 EN 61000-3-3, it operates effectively in ambient temperatures from 5 to 40 °C and humidity levels up to 95%. Constructed from durable PC/ABS, PC, and aluminum materials, it comes in a sleek white finish and is designed for wall mounting. Measuring 302 x 94 x 210 mm and weighing between 4150 g and 4370 g depending on configuration, this emergency light combines safety, performance, and durability in one compact unit. complete in all respects as approved and desired by the Engineer in-charge at site. It includes the (CAMC of 2 Years after completion of one year defect liability period) |
| 391 | Supply, installation, testing & Commissioning of Online UPS 1 kva 800 Watts Tower UPS with 1 hour battery backup. Operating Temperature Range 0 to 40 Degree @ 100% Load @ 50 Degree with 50% Load,Storage Temperature -15°C~60°C, Relative Humidity 0-95% No condensates, Acoustic Noise 40 dBA @ 1 Meter, Cooling Forced air cooling by the internal fans, Input Socket IEC C13, Output Socket IEC C14, No of output sockets 3 No's, Rated Input Voltage 208/220/230/240 Vac, Maximum working input voltage range 160 to 300 Vac @ 100% Load, 100 to 300 Vac @ 50% Load, Input Power Factor 0.99, Input THDi% 5%, Generator Set Yes 1.5 x UPS Capacity, Rated kVA 1000 VA, Rated kW 800 Watts, Load type Resistive load/ lagging load/ non-linear load/ transformer load/ lighting load, Load power factor range 0.5~1 lagging, Load Crest Ratio 3:1, Online Efficiency 88%, Rated Battery Voltage 36 Vdc, Battery Type VRLA (Valve Regulated Lead Acid Battery), 12VDC, Battery backup Back UP : 936VAH, Maximum charging current 10 Amps, ECO Mode Available, Communication (Independent SCI) Available, Intelligent Card slot (Independent SCI) Available, OVCD Available, EPO Function Available, Intelligent Fans Speed control Available, Auto restart function Available, Cold start Available complete in all respects as approved and desired by the Engineer in-charge at site. It includes the (CAMC of 2 Years after completion of one year defect liability period) |
| 392 | PVC INSULATED PVC SHEATHED FR ROUND FLEXIBLE COPPER CONDUCTOR CABLE:Supply and erection of PVC insulated PVC sheathed FR (2Core) round flexible wire with copper conductor cable (ISI marked) confirm to IS:694/1990 left bare in pipe or on surface with cleats of suitable size complete in all respect as desired by the Engineer-in-charge:- |
| 393 | Overall size 1.5sq.mm (48/0.20mm), 2Core |
| 394 | Supply and erection of fire survival cable for fire alarm & PA system with annealed stranded copper conductor, fire resistant mica tape wrapped (at 950°C for 180 minutes), XLPE insulated, LSHZ (low smoke & zero halogen) bedding, LSZH (low smoke & zero halogen) red outer sheath, galvanized steel wire armour, 600/1000 volts grade, Fire resistant to IEC 331 & BS7846 F2/BS6387 & CWZ, Acid gas emission to BS EN 50267 (IEC60754), smoke emission to BS EN 50268 (IEC61034) and flame propagation to BS EN 50265, BS EN 50266 (IEC 60332-3) left bare in pipe or casing or on surface with cleats of suitable size complete in all respect as desired by the Engineer-in-charge:- |
| 395 | Fire Survival cable 2Coe x 1.5 sq.mm |
| 396 | HEAVY GUAGE WELDED CONDUIT PIPES:Supply & erection of Heavy guage welded conduit pipe (ISI marked) as per IS:9537:Part-II for wiring purposes including bends, junction boxes, Steel hooks, GI saddle clamps and other petty materials etc., where necessary including painting as per PWD General Specifications:- |
| 397 | Heavy gauge welded conduit pipe 25mm dia. (ISI marked 1.60mm thick) Flushed |
| 398 | PVC, HDPE PIPES & PVC FLEXIBLE PIPES:Supply & erection of PVC Conduit Pipes (ISI marked) as per IS9537:Part-III & HDPE pipes (ISI marked) as per IS:4984:1995 for wiring purposes including bends, junction boxes, Steel hooks, M.S. saddle clamps and other petty materials etc., as per PWD General Specifications:- |
| 399 | Heavy gauge PVC conduit pipe 25mm dia. (ISI marked) Flushed |
| 400 | Providing PA System for Courts : |
| 401 | Supply, Installation, Testing & Comissioning of Amplifier Power Output:100W Max. THD. Output Regulation:≤ 2 dB, no load to full load at 1kHz. Input Channels: 5 X Mic 0.65mV/4.7kΩ, 2 X Aux 100mV/470KΩ. Frequency Response: 50-15,000Hz ± 3dB. Signal to Noise Ratio: 60dB. Tone Controls: Bass: ±8dB at 100Hz, Treble: ±8dB at 10kHz. Output: Preamp 200mV/600Ω, Line 1V/1kΩ. Speaker Output: 4Ω,8Ω,16Ω,70V & 100V. Digital Player: MP3 Player wih USB, SD & MMC Card Reader, Bluetooth. Power Supply: AC:220-240V 50/60Hz, DC:12V(12V Car Battery). Power Consumption: AC: 250VA DC: 5.5A..complete in all respect as per satisfaction of the Engineer in charge of the work. |
| 402 | Supply, Installation, Testing & Commissioning of Speaker Power Rating: 50W Max. Power Taps: 30/20/10W. Impedance/Voltage: 80Ω/100V. Frequency Response: 50-20,000Hz. SPL at 1KHz (1W/1m): 87dB. Speaker: Woofer 163mm (6 ½\\"), Tweeter 25mm (1\\"). Dimensions: W215 X H310 X D175 mm. Weight: 3.80Kg complete in all respect as per satisfaction of the Engineer in charge of the work. |
| 403 | Supply, Installation, Testing & Commissioning of Mic Frequency Response: 100-15,000Hz, Impedance: 1000Ω, Sensitivity: 7.0mV/Pa. Power Source: 3V-9V DC. Overall Length: 460mm(18\\") complete in all respect as per satisfaction of the Engineer in charge of the work. |
| 404 | Supply, Installation, Testing & Commissioning of Mic Stand Heavy Duty Base, XLR Connector, 10m Twin Core shielded , 6.3mm (¼\\") phone plug, On/Off Switch complete in all respect as per satisfaction of the Engineer in charge of the work. |
| 405 | Supply, Installation, Testing & Commissioning of Mic Cabling (5 Mtr) with connector complete in all respect as per satisfaction of the Engineer in charge of the work. |
| 406 | Supply, Installation, Testing & Commissioning of 1000VA LIT UPS/ Power Plant with SMF batteries having 30 Minutes backup time, Cold Start, 3 No. plug Indian style, Automatic Voltage Controller, Overload protection, Over charging Protection, 2 No. 12v 7Ah Batteries, Wide Input Range, Fan Less Cooling system, Transfer time less than 8ms,Audible Alarm etc. complete in all respects as approved and desired by the Engineer in-charge at site. |
| 407 | PVC, HDPE PIPES & PVC FLEXIBLE PIPES:Supply & erection of PVC Conduit Pipes (ISI marked) as per IS9537:Part-III & HDPE pipes (ISI marked) as per IS:4984:1995 for wiring purposes including bends, junction boxes, Steel hooks, M.S. saddle clamps and other petty materials etc., as per PWD General Specifications:- |
| 408 | Heavy gauge PVC conduit pipe 25mm dia. (ISI marked) Flushed |
| 409 | Providing Child Witness System for Courts : |
| 410 | Supply, Installation, Testing & Comissioning of Ceiling Tile/Array Microphone which shall have digital array system with pickup area of 600 Sq feet or more. It shall have Adaptive beamforming technology, automatic speaker alignment and speech reinforcement. It shall have noise reduction, echo cancellation and reverberation suppression to ensure good sound quality. It shall have array sensitivity of 26 feet or more. It shall have inbuilt Digital Signal processor with AEC. It shall have USB audio port for unified communication applications. It shall have one or more line input interface and two or more line output interface. It shall have Signal to noise ratio of Sixty four dB or better. It shall support twin analog and digital mode simultaneously. It shall have frequency response of 20Hz to 16KHz or better. It shall support HDB Audio. It shall support ANS, AGC, AEC and UAC. It shall have thirty two Kilo Hertz or better sampling rate. It shall be supplied with standard 16' USB 2.0 Cable, 30' Audio Cable as standard Accessory. .complete in all respect as per satisfaction of the Engineer in charge of the work. |
| 411 | Supply, Installation, Testing & Commissioning of camera shall have 1/2.5 inch high quality 8.5 MP HD CMOS sensor or better. It shall have an option of Auto or Manual White Balance. It shall have S/N Ratio of >50db. It shall have 5x digital zoom or better. It shall have USB 3.0 Type C interface for unified communication applications. It shall have dedicated hard button for Zoom so that the same can be achieved irrespective of the software application. The interface shall be detachable to use custom lengths. It shall support resolution of 3840x2160@30fps (2160p30), 2688x1512@30fps (1512p30), 1920x1080@30fps (1080p30), 1280x720@30 (720p30), 960x540@30fps (540p30), 640x360@30 (360p30). (4:3)- 2592x1944@30fps (1944p30), 2048x1536 @30fps, (1536p30), 1600x1200@30fps (1200p), 1280x960@30fps (960p30), 800x600@30fps, 640x480@30fps (480p30). It shall support YUV2/MJPG/H.264 or better. It shall have built In Dual Stereo Mics with Automatic Noise cancellation with Frequency Response: 100Hz-14KHz, Sampling Rate: up to 32 KHz, Coding Format: PCM, UAC1.0 compatible, 15 ft pickup. It shall have 115 Degree or better field of view. It shall support 50Hz/60Hz or better. It shall be supplied with 6 ft USB Cable. complete in all respect as per satisfaction of the Engineer in charge of the work. |
| 412 | Supply, Installation, Testing & Commissioning ofUSB 3.0 active extension optical cable features a USB 3.0 Type-A interface with locking screws on the host side and a USB 3.0 Type-A interface with locking threads on the device side, ensuring secure and reliable connections. It supports data transfer rates up to 5 Gbps and is backward compatible with USB 2.0 and USB 1.1 devices. Power is supplied via a USB micro interface on the host side, delivering a maximum current of 5 V, 900 mA for 15M lengths and 600 mA for 50 m length, with a low power dissipation of 0.94 W. The cable has a 3.0 mm diameter, a minimum bend radius of 20 mm, and compact connector dimensions of 44 × 27 × 13 mm (host side) and 82 × 26 × 14.5 mm (device side). Designed for dependable performance, it operates within a temperature range of 0°C to 55°C and can be safely stored between -20°C and 80°C, making it suitable for professional AV and industrial applications. complete in all respect as per satisfaction of the Engineer in charge of the work. |
| 413 | Supply, Installation, Testing & Commissioning of Powered USB 4 Port USB 3.0 Hub the device is built with a sturdy ABS case material and supports multiple transfer rates of 5 Gbps, 1.5 Mbps, 12 Mbps, and 480 Mbps. It is fully compatible with USB 1.0, 2.0, and 3.0 specifications, while also being backwards compatible with USB 2.0 and 1.0. A white LED indicator signals power ON status. Designed for versatility, it works seamlessly with Windows®7 (1080p and under only), Windows 8.1, Windows 10 or higher, MacOS™ 10.10 or higher, Google™ Chromebook™ Version 29.0.1547.70 or higher, and Linux operating systems. It supports USB-IF Rev 1.2 and BC 1.2 charging protocols along with UVC 1.1 communication protocol. The input/output interface includes 1x USB-B 3.0 upstream port and 4x USB-A 3.0 downstream ports, with upstream ports supporting SuperSpeed (SS), HighSpeed (HS), and FullSpeed (FS) traffic, while downstream ports support SS, HS, FS, and LowSpeed (LS) traffic. Power input can be supplied externally at DC 5V/3A with 2 Amps shared across the 4 USB ports, or drawn from the PC at DC 5V/3A with 900 mAmps shared. Compact in design, it measures 104.75 x 30.1 x 12mm and carries CE, FCC, and RoHS certifications for safety and compliance. complete in all respect as per satisfaction of the Engineer in charge of the work. |
| 414 | Supply, Installation, Testing & Commissioning of Display : 50 inch, 4K (3,840 x 2,160), Direct LED, Professional Display with 4K Processor, Native Contrast ratio 5,000:1 or higher, Response time 12 ms or lower, Brightness 400 cd/m² or higher, 24/7, Portrait/Tilt functionality, HDMI Auto wake up, HTML5 platform, 16GB On Board Storage, HDMI*4 with HDCP 2.3 / RS232 / USB / RJ45 / Wi-Fi Direct / 20W Speakers / Android OS or similar, Viewing angle 178 degree, Apple AirPlay & Chromecast. complete in all respect as per satisfaction of the Engineer in charge of the work. |
| 415 | Supply, Installation, Testing & Commissioning of PC i7, 16GB ram, 500gb SSD (NVME) professional window 10, with keyboard & mouse. complete in all respects as approved and desired by the Engineer in-charge at site. |
| 416 | Supply, Installation, Testing & Commissioning of optical HDMI cable 10 mtr as per the site requirement. complete in all respects as approved and desired by the Engineer in-charge at site. |
| 417 | PVC, HDPE PIPES & PVC FLEXIBLE PIPES:Supply & erection of PVC Conduit Pipes (ISI marked) as per IS9537:Part-III & HDPE pipes (ISI marked) as per IS:4984:1995 for wiring purposes including bends, junction boxes, Steel hooks, M.S. saddle clamps and other petty materials etc., as per PWD General Specifications:- |
| 418 | Heavy gauge PVC conduit pipe 25mm dia. (ISI marked) Flushed |
| 419 | Providing Flood Lighting: |
| 420 | PVC INSULATED SINGLE CORE FR COPPER CONDUCTOR CABLE:Supply and erection of PVC insulated FR single core Unsheathed copper conductor cable (ISI marked) suitable upto 1100 volts grade confirm to IS:694/1990 left bare in pipe or casing of suitable size complete in all respect as desired by the Engineer-in-charge:- |
| 421 | Overall size 1.5sq.mm (Un-sheathed) |
| 422 | XLPE INSULATED UN-ARMOURED CABLES (ON SURFACE):Supply, laying and erection of aluminium conductor XLPE insulated PVC sheathed Un-armoured and served cable 1100 volts grade as per IS 7098 (Part-1)1988 to be laid (On Surface) as per PWD General Specifications:- (For Flood Lights) |
| 423 | Overall size 10sq.mm (3Core) Un-armoured (On-Surface) |
| 424 | DOUBLE WALLED CORRUGATED (DWC) HDPE PIPES: Supply and erection of Double Walled Corrugated (DWC) HDPE pipe to be laid 1mtr. below ground level including excavation placing the pipe in position and back filling with excavated soil etc. of the required size:- |
| 425 | Double walled corrugated (DWC) HDPE pipe 63/51mm (outer/ inner dia.) |
| 426 | SHEET METAL CUBICAL PEDESTAL, TOWER STRUCTURES, HT & LT LINE ITEMS, MS CHANNELS, BRASS GLANDS, ALUMINIUM & COPPER THIMBLES: |
| 427 | Supply and erection of M.S. Channel bracket made from 100mm x 50mm of length 600mm and height 600mm with M.S. angle iron 40mm x 40mm x 5mm for installing metal halide flood light fitting on it. Bracket should be fixed/ welded with the existing pipe of cover shed. The bracket should be painted with one coat of primer and two coats of approved paint. (For Flood Lights on Parapet wall) |
| 428 | Supply and erection of SMC Junction Box (Glass Fibre reinforced polyester sheet moulding compound) confirm to IS:14772 (Recessed/ On surface), robustly constructed, safe & shock proof, rust & tamper proof of suitable inner & outer dimensions with ± 10% tolerance in size & hinged water tight cover with locking arrangement having 1No. terminal strip with 4Nos. terminals & 1No. Single pole MCB of required capacity fixed on din bar (Din Bar Provision for 2Nos. MCB's) complete in all respect as approved and desired by the Engineer In-Charge at site:- |
| 429 | SMC Junction Box (Glass Fibre reinforced polyester sheet moulding compound) confirm to IS:14772, inner dimensions 200mm x 140mm x 95mm with hinged water tight cover with locking arrangement (For Flood Lights on Parapet wall). |
| 430 | GALVANIZED IRON PIPES AND G.I. EARTHING:Earthing with G.I. wire/ rope in G.I. pipe partly recessed and partly on surface complete with 150cm long 50mm dia. G.I. earth pipe (Cutting threads and 36 Nos. holes, 1cm dia. to make a mesh around the GI Pipe) with G.I. reducing socket including erection of the same, 4.50 metre (14.76 feet) below ground level with 20Kg. charcoal & salt mixture etc., up to 8 metre in length (including boring & refilling).(For Cubical Pedestal) |
| 431 | Earthing with 8 S.W.G. (4mm dia.) G.I. wire in 15mm dia G.I. pipe with G.I. reducing socket 50mm x 15mm (upto 8Metre in length) |
| 432 | Additional length G.I. wire 8 S.W.G. (4mm dia.) in 15mm dia. G.I. pipe (On Surface) |
| 433 | Supply and erection of heavy duty brass single compression gland for cable end termination duly complete with checknuts etc. including making necessary connections:- |
| 434 | Brass Gland for Aluminium cable 2/3/4 Core size 10sq.mm |
| 435 | Supply and erection of heavy duty aluminium thimbles/lugs for cable end termination duly crimped including making necessary connections completely:- |
| 436 | Aluminium thimble cable Core size 10 -16sq.mm |
| 437 | SHEET METAL CUBICAL PEDESTAL, TOWER STRUCTURES, HT & LT LINE ITEMS, MS CHANNELS, BRASS GLANDS, ALUMINIUM & COPPER THIMBLES:CUBICAL PEDESTAL: Supply and erection of Sheet metal cubical pedestal made from 50mmx50mmx6mm thick MS angle iron frame with 5 sides welded & covered with MS sheet 2mm thick & front side hinged with 4\\" hinges & locking system with single/ double door openable placed on MS strip of size 12.5mm x 2.5mm thick welded with MS sheet, 4Nos. legs of 50mmx50mmx6mm thick MS angle iron each of 600mm long with MS sheet 100mmx100mmx6mm thick at the bottom end of the legs. Front door welded x-sectionally with MS flat 25mmx5mm. The front side with MS sheet each 75mm wide & a bend of 75mm width outwards & inwards on all sides with tappered top 200mm high and pedestal with 4 Nos. supporting members each of MS flat 50mmx6mm thick according to cubical size duly welded & complete pedestal to be painted with 1 coat of red oxide & 2 coats of paint & bonding to the existing earth. The Pedestal platform should be filled with 1:2:4 cement concrete mixture and erected 150mm high from the top of the cement concrete platform. The job is to be completed as approved by Engineer-in-charge:- |
| 438 | Cubical Size 900mm high, 600mm wide and 350mm deep with platform dimensions 700mm x 450mm x 450mm |
| 439 | MS SHEET ENCLOSURE FOR MCCB's:Supply & Erection of indoor type MCCB enclosure of suitable size having provision for MCCB with extended rotary handle. The Enclosure shall be made from 14/16 SWG CRCA sheet, confirming to IS 8623/1977-82. The door should be double folded without edge and the gasket should be ‘S’ type puffed neutral rubber gasket for long life. The hinges of the door should be bolted type with double hole arrangement. The Enclosure door lock should be quick openable type spring loaded. There should not be any special tool or key to open the lock. The Enclosure will be wall mounting type having provision for cable entry from bottom/top with cable glands etc. The sheet metal is sprayed with corrosion resistant etch primer. The finishing treatment shall be applicable with air drying paint (7/9 tank Powder coated process should present in company pemises) after necessary putty work:- |
| 440 | MS Sheet Enclosure having provision for MCCB 40-160Amp.with extended rotary handle (Approx. Size 500mm x 300mm x 200mm) |
| 441 | MCCB's (MOULDED CASE CIRCUIT BREAKER):Supply and erection of Moulded Case Circuit Breaker (Panel mounting Cubical type) in the existing Cubical Panel (confirm to IEC:60947-2) having Ics=100% Icu, 100% neutral with spreader links and relevant PWD general specifications complete with G.I. Bolts, Nuts & Connection on both sides of MCCB with suitable size of thimbles etc:- |
| 442 | MCCB Four Pole 63amp., 415volts, ≥25kA Fixed Magnetic and Adjustable Thermal Setting |
| 443 | TIMER:- Supply and erection of Switch S/E of Microprocessor Based Street Light Controller with digital time switch daily programmed with stand by lithium battery with back up of 6 years with min. time between 2 switching operations is 1 minute, three pole power contactors 40A. with coil voltage 220-230V AC with 1 no. aux. contact NO, MCB 2 pole 40amp. (C-Curve, 10kA) & power wiring with single core PVC insulated FR cable 10 sq. mm and control wiring with PVC insulated FR cable 1 sq. mm, 1 no. two position selector switch to bypass timer and other accessories & petty material (din rail, 4 pole bakelite terminal strip 63A/ 440V AC, required nut bolts) should be fixed on bakelite sheet 6mm thick to be mounted in a IP54 surface/ flush mounting powder coated sheet metal (1.60mm thick) cabinet having size 450mm x 600mm x 150mm to switch ‘ON’ all the 3 phases & switch ‘OFF’ 3 phases pre-fixed timings complete in all respect as per satisfaction of Engineer-in-charge:- |
| 444 | Street Light Controller (For Three Single Phase Circuits) with 3 Nos. Three Pole Power Contactors 40A, 1 no. aux. contactor 6 amp. (2NO+2NC) with coil voltage 220V AC, 3 Nos. MCB 2 Pole 40amp. (C-Curve,10kA) & petty material (Din rail, 2 Nos. 4 pole bakelite terminal strip 63A/ 440V AC, required nut bolts) |
| 445 | Supply and erection of LED Flood Light 120 watt, AC supply voltage 140-270 volts, 50Hz ± 3% (including BIS Certified potted single diver with screen or laser printing logo LED driver) with pressure die cast or extruded aluminium housing with control gear (IP 66 protection), THD<10%, CRI minimum 70, High power LED (with wattage 1 to 5 watt) with mandatory secondary lenses, toughened glass fitting, 4 KV SPD within driver and 10KV external SPD, Min IK07, efficacy of LED fixture minimum 120 lumens per watt, 5 year warranty including their drivers complete in all respects as approved and desired by the Engineer in-charge at site. LED Fittings as per specifications approved by Hon'ble Technical Advisor to Punjab Govt. vide Letter ION No: AT/2021/GL/1410-1422 Dated: 06.05.2021. Besides this the lighting fixtures manufacturers should have in house NABL accredited lab. |
| 446 | Supply and erection of LED Street Light 45watt, Supply Voltage 140-270Volts AC supply, 50Hz ± 3% (including BIS Certified potted single diver with screen or laser printing logo LED driver) with pressure die cast or extruded aluminium housing with control gear (IP 66 protection), THD<10%, CRI minimum 70, High power LED (with wattage 1 to 5 Watt) with mandatory secondary lenses, toughened glass fitting, 4 KV SPD within driver and 10KV external SPD, Min IK07, efficacy of LED fixture minimum 120 lumens per watt, 5 year warranty including their drivers complete in all respects as approved and desired by the Engineer in-charge at site. LED Fittings as per specifications approved by Hon'ble Technical Advisor to Punjab Govt. vide Letter ION No:- AT/2021/GL/1410-1422 Dated:- 06.05.2021. Besides this the lighting fixtures manufacturers should have in house NABL accredited lab. |
| 447 | Supply and erection of LED Post top 40/45 watt Opal Diffuser Supply Voltage 140-270Volts AC supply, 50Hz ± 3% (including BIS Certified potted single diver with screen or laser printing logo LED driver) with pressure die cast or extruded aluminium housing with control gear (IP 66 protection), THD<10%, CRI minimum 70, High power LED with wattage 1 to 5 Watt with mandatory secondary lenses, toughened glass fitting, 4 KV SPD within driver and 10KV external SPD, Min IK07, efficacy of LED fixture minimum 120 lumens per watt, 5 year warranty including their drivers complete in all respects as approved and desired by the Engineer in-charge at site. LED Fittings as per specifications approved by Hon'ble Technical Advisor to Punjab Govt. vide Letter ION No:- AT/2021/GL/1410-1422 Dated:- 06.05.2021. Besides this the lighting fixtures manufacturers should have in house NABL accredited lab. |
| 448 | PUBLIC HEALTH SERVICES |
| 449 | Internal Sewerage System |
| 450 | Providing and fixing in position singel socket SWR UPVC soil waste or antisyphonage pipes as per IS 13592 of E.D.C manufacture or of any other reputed firm including cutting, jointing, wastage, but excluding cost of jointing. |
| 451 | Single Socket Type B |
| 452 | 110mm o/d SWR UPVC pipe lines laid complete |
| 453 | 90mm o/d SWR UPVC pipe lines laidcomplete |
| 454 | Providing and fixing in position SWR UPVC special for soil waste vent or anti syphonage pipes as per as per IS - 14735 including cutting and wastage etc. cutting holes in walls roofs or floors etc. and making good to its original condition but excluding cost of lead joining. |
| 455 | For 110 mm o/d pipes |
| 456 | Single Tee With Door |
| 457 | Door Elbow 90 Degree (All sidesocketed) |
| 458 | Elbow 90 Degree (All side socketed) |
| 459 | Vent Cowls |
| 460 | Coupler |
| 461 | P Trap/Floor Trap 110mm x 110mm |
| 462 | For 90 mm o/d pipes |
| 463 | Single Tee With Door |
| 464 | Door Elbow 90 Degree (All sidesocketed) |
| 465 | Elbow 90 Degree (All side socketed) |
| 466 | Vent Cowls |
| 467 | Coupler |
| 468 | Providing PVC solvent cement joints to SWR Pipes and specials including cost of PVC solvent cement and tools etc of approved make (to the approval of Engineer-in-charge) |
| 469 | 110mm o/d |
| 470 | 90mm o/d |
| 471 | Providing & Fixing in position M.S or heavy flat iron clamps made out of M.S flat iron not less than 5 mm of the approved design for fixing C.I. soil waste, vent or antisyhonage pipes to walls complete in all respects including cutting and making good the walls and floors etc. and painting. |
| 472 | M.S. Holder bats clamps for 100mm i/d |
| 473 | M.S. Holder bats clamps for 75mm i/d |
| 474 | Providing and fixing galvonised hanging clamp 100mm dia chimney type for PVC pipe, 12mm galvonised fully thread bar with nut bolt as per requirement at site & as desired by Engineer-in-Charge. |
| 475 | Core cutting in RCC slab 125mm dia or 150mm dia withe the help of core cutting machine as per requirement at site & as desired by Engineer-in-Charge. |
| 476 | Providing and fixing in position gully traps fixed in cement concrete 1:4:8 complete with Grating 150mm x 150mm, cover and frame clear opening 300mm x 300mm and out of side size 330mm x 330mm and chamber including cost of all bricks work in cement morter 1:5 cement concrete 1:2:4 in coping around cover and frame etc. as per standard design minimum depth of water should be 150 mm with a minimum seal 50mm110mm dia PVC gully traps.with PVC grating & SFRC Cover with Frame size 300x300mm complete in all respects and as desired by Engineer-in-Charge. |
| 477 | Construction of brick masonry inspection chambers size as given below upto 0.60 metre average depth in 1:5 cement sand mortar, C.C.1:4:8 ( 150mm thick) in foundation, cement concrete 1:2:4 benching 12.50mm thick cement plaster 1:2 with a floating coat of 1mm thick of neat cement, R.C.C. 1:2:4 slabs 100mm thick cement concrete topping 50mm thick with 455mm x 455mm, 455mm x 610mm inside R.C.C. inspection chamber cover and frame (Weight as per I.S.I specifications) painted with 3 coats of black bitumastic paint conforming to I.S.I complete as per standard design. |
| 478 | Size 450mm x 450mm inside with RCC 455mm x 455mm cover and frame light duty double seal |
| 479 | Internal Water Supply System |
| 480 | CONCEALED IN WALL: Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes as per IS 15778 (ISI marked with the prior approval of Engineer-in- Charge), having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings i/c fixing the pipe with clamps at 1.00 m spacing including jointing of pipes & fittings, with one step CPVC solvent cement and testing of pipes complete as per direction of Engineer-in-Charge. |
| 481 | SDR 11 CPVC pipes & fittings 20mm o/d |
| 482 | CPVC SDR 11 Pipe & fitting 25mm o/d |
| 483 | CPVC SDR 11 Pipe & fitting 32mm o/d |
| 484 | Cutting chase in brick walls in cement or in floor for embedding G.I. or C.I pipes line and making good the same to its original condition |
| 485 | Size 75 mm x 75 mm |
| 486 | Cutting holes upto 23cm square through B.B. in cement walls or stone masonary wall in cement for pipes, and making good the same & finishing according to existing finish where required. |
| 487 | Through wall 11.43 cm thick |
| 488 | Through wall 22.86 cm thick |
| 489 | Providing, fixing and jointing Cpvc Union Couplings(of approved make with the approval EIC) as per IS 1879 in G.I. Pipe lines complete in all respect. |
| 490 | Detail attached as per Inventory |
| 491 | 20mm i/d Cpvc Union |
| 492 | 25mm i/d Cpvc Union |
| 493 | 32mm i/d Cpvc Union |
| 494 | Upline and Downline |
| 495 | Providing ,laying, jointing, fixing and testing ISI Marked G.I. Pipe (as per IS 1239) B-Class including cost of specials (such as tees, bends, sockets, elbows etc.) ,painting with anti corrosive bitumastic paint, testing, cutting, threading Inside building complete. |
| 496 | 32mm i/d |
| 497 | 40mm i/d |
| 498 | Providing, fixing and jointing G.I Union Couplings(of approved make with the approval EIC) as per IS 1879 in G.I. Pipe lines complete in all respect. |
| 499 | 32mm i/d G.I. Union |
| 500 | 40mm i/d G.I. Union |
| 501 | Providing, fixing and jointing ISI Marked Gun-Metal peet valves (Heavy Pattern) as per IS 778 with hand wheels, on G.I. Pipe lines laid in the ground or inside buildings including all carriages complete. |
| 502 | 32mm i/d Gun Metal peet valve heavy pattern. |
| 503 | 40mm i/d Gun Metal peet valve heavy pattern.n. |
| 504 | Sanitary Installation including Drinking water cooler |
| 505 | Providing and fixing in position Chinaware European type water closet P trap or S trap of approved make (to the approval of the Engineer-in-charge) consisting of 10 ltr. PVC flushing cistern ISI marked, PVC short bend 32 mm dia including cost of seat cover complete in all respect and to the entiresatisfaction of Engineer-in-charge. |
| 506 | Providing and fixing in position set of EWC and WHB size 46x36 cm for Handicapped person of approved make (to the approval of the Engineer-in-charge) consisting of matching cistern, one pair mountingbrackets, seat cover, one no. hinges rail 76cm and 4 no. grab rails 60cm complete in all respect and to the entire satisfaction of Engineer-in-charge. |
| 507 | Providing and fixing in position Chinaware extended wall mounted E. W.C. type suite (size 66 x 46 x 77.5 cm ) with P trap or S trap of approved make (to the approval of the Engineer-in-charge) with or without 10 ltr. chinaware matching flushing cistern and seat cover complete in all respect and to the entire satisfaction of Engineer-in-charge.Chinaware wall mounted E.W.C withoutcistern including seat cover complete inall respect.Detail attached |
| 508 | Providing and fixing in position concealed cistern including flushing plate of approved make (to the approval of the Engineer-in-charge) complete in all respect.Detail attached |
| 509 | Providing & Fixing in position C.P. Brass Hexa Nipple 15mm of approved make (to the approval of Engineer-in-charge ) complete in all respect. |
| 510 | Providing and fixing jet spray with 2'-6\\" long PVC pipe.With PTMT nut |
| 511 | Providing and fixing Stainless steel health faucet complete in all respect |
| 512 | Providing and fixing in position vitreous chinaware white lavatory suites of approved make (to the approval of Engineer-in-charge) including Rack Bolt Screw Pair 115mm long without CP fittings complete in all respect. |
| 513 | Size 560mm x 450mm (Under counter oval) |
| 514 | Providing and fixing in position C.P. Brass Auto close Pillar Cock of approved make (to the approval of Engineer-in-charge) |
| 515 | Providing and fixing in position vitreous chinaware white lavatory suites of approved make (to the approval of Engineer-in-charge) consisting of C.P. brass waste 32mm dia with one C.P. brass pillar tap including Rack Bolt Screw Pair 115mm long complete in all respect |
| 516 | Size 550 mm x 400 mm x 815 mm |
| 517 | Providing and fixing vitreous chinaware standard pedestal of approved make (to the approval of Engineer-in-charge) for wash hand basin complete in all respect. |
| 518 | Providing and fixing in position vitreous Chinaware white lIndian make large flat back or angular lipped front urinal 375 x 390 x 590 mm of approved make (to the approval of the Engineer-in-charge) consisting of C.P. brass Urinal waste Coupling dome type 32mm outer length 75 mm , C.P. brass Urinal Spreader Ocular-Regular and C.P. brass tube connection 300 mm long complete. |
| 519 | Vitreous white Chinaware Partition |
| 520 | Large partition size 75 x 16.5 x36.5 cm |
| 521 | Providing & Fixing in postion stop cock / Angle valve of approved make (to the approval of Engineer-in-charge ) complete in all respect. |
| 522 | C.P.brass 15mm Angle valve without flange |
| 523 | Providing & Fixing in postion 15 mm i/d bib cock of approved make (to the approval of Engineer-in-charge )complete in all respect. |
| 524 | C.P. brass Bib cock foam flow without flange |
| 525 | C.P. brass Bib cock long nose/ long body foam flow without flange |
| 526 | Providing & fixing in position PVC flexible tube connection of approved make (to the approval of Engineer-in-charge ) complete in all respect. |
| 527 | PVC tube connection of size 15 mm x 450 mm with C.P. Brass nut |
| 528 | Providing and fixing P.V.C Waste Pipe Collapsiable 32mm complete in all respect. |
| 529 | Providing & Fixing in position C.P. Brass flange Dome of approved make (to the approval of Engineer-in-charge ) under various fixtures complete in all respect. |
| 530 | Providing & Fixing in position C.P. Brass extension piece 25mm long to 100mm long of approved make (to the approval of Engineer-in-charge )with various fixtures complete in all respect. |
| 531 | C.P. Brass extension piece, 25mm long to 50mm long |
| 532 | Providing & Fixing in position 5mm thick bevelled edge mirror of superior glass (of approved make) complete with 4mm thick hard board backing fixed in with rawl plugs 50mm, C.P. brass screws and washers and S/S Studs on top complete in all respect (as required by the Engineer-in- Charge) |
| 533 | Size 600mmx450mm |
| 534 | Providing and fixing in position C.P. brass soap dish of approved make (to the approval of Engineer-in-charge ) fixed into wall with rawl plugs and C.P brass screws complete in all respect. |
| 535 | Providing and fixing in position towel rails / ring of approved make (to the approval of Engineer-in-charge ) fixed in with rawl plugs embedded in walls with brass screws complete in all respect. |
| 536 | C.P brass towel ring |
| 537 | C.P. brass towel Rails size 15mm dia 610mm long |
| 538 | Providing and fixing in position paper holders of approved make (to the approval of Engineer-in-charge ) fixed in to wall with C.P brass screws complete in all respect. |
| 539 | C.P. brass toilet paper holder |
| 540 | Providing and fixing in postion storage type automatic electric water heater pressure typethermostatically controlled, single phase wall mounted of approved make (to the approval ofEngineer-in-charge) with thermostats, inner container of stainless steel, Inner glass lining with B-Rating minimum 3 stars complete with 1 Mtr. three core flexible cord with plug, non return valve and pressure release valve complete including fixing and testing complete in all respect. |
| 541 | Vertical Type |
| 542 | 15 litre capacity water heater |
| 543 | Providing and fixing in position stainless steel sinks of approved make (to the approval of Engineer-in-charge) 1mm thick,grade-304 (18/8) with waste coupling complete in all respect. |
| 544 | Rectangular Sink with Deluxe Border Single Bowl Overall Size 700 mm x 555 mm x 230 mm |
| 545 | Providing and fixing in position SS Grating with frame of approved make (to the approval of engineer in charge) complete in all respects |
| 546 | Qty same as floor trap |
| 547 | Providing & fixing in position Water Cooler without Stablizer of approved make (to the approval of Engineer-in-charge ) including carriage complete in all respect. |
| 548 | Water Cooler Full Steel Body 150/150 ltr without Stablizer |
| 549 | Providing & fixing in position Commercial RO without reservoir with four no cartridge/ membrane having flow rate 50 ltr/hr with 6 stage purification process of approved make (to the approval of Engineer-in-charge ) including carriage and fixing in positioncomplete in all respect. |
| 550 | Providing & fixing in position Water Dispenser Top Loading (with refrigration capacity 15 ltr) of approved make (to the approval of Engineer-in-charge ) dispensing hot/cold/ambient water including cost of two no. 20 ltrs packaged drinking water bottles and carriage complete in all respect. |
| 551 | Supply and erection of Single phase copper wound Automatic voltage stablizer of suitable capacity electronically controlled circuit with input voltage 140-260 volts single phase AC supply and output voltage 220 ± 5% volts single phase AC supply having main silicon core copper wound step up transformer with suitable nos. of turns on primary side and secondary side the transformer should be fully insulated inside the MS sheet box of suitable size. There should be power control relay and single pole MCB (C-curve, 10kA) of suitable capacity complete with internal copper wiring along with amp. meter and volt meter, high voltage cut off 280 volt input (240 volt output) and 90 volt maximum boost and overloading protection to be provided:-. |
| 552 | Automatic Voltage Stablizer 3 KVA |
| 553 | For Drinking Water Cooler |
| 554 | Supply & Installation of Sanitary pad vending machine NVM-50, fully Automatic Vending machine battery backup available visible window as per specification and as desired by Engineer-in-Charge complete in all respect. |
| 555 | Supply & Installation of Sanitary Napkin Vending machine storage capacity 25 Pad, Coin accepted : 5rs or dummy coin made from Mild steel as per specification and as desired by Engineer-in-Charge complete in all respect. |
| 556 | Providing & Fixing of Automatic Hand Dryer AK 2803D as desired by Engineer Incharge |
| 557 | VIP Range FITTING |
| 558 | Providing and fixing in position premium range C.P. Brass Fittings and accessories of approved make (to the approval of Engineer-in-charge ) complete in all respect. |
| 559 | C.P. Brass fittings: |
| 560 | C.P. brass Bib cock with Wall flange |
| 561 | C.P.brass 15mm Angular stop cock with Wall flange |
| 562 | C.P. Brass Accessories: |
| 563 | C.P. brass towel rail 600 mm long |
| 564 | C.P brass towel ring square |
| 565 | C.P. brass soap dish holder with glass dish |
| 566 | C.P. brass toilet roll holder with flap |
| 567 | Providing & placing in position on terrace (at all floor levels) HDPE water storage tanks of approved make (to the approval of Engineer -in-charge) with cover with suitable locking arrangement and making necessary holes for inlet, outlet and over flo pipes but without fittings and base support for tank. Tripple Layer Tanks |
| 568 | Providing and fixing in position automatic brass Ball Cock in tanks.Plastic Ball Cock with rod and Plastic Ball |
| 569 | 32mm i/d |
| 570 | Construction of Plateform complete as per specification & as desired by Enginer-in-charge |
| 571 | For 1000 ltr Water Tank |
| 572 | Flooring and Wall Tile |
| 573 | Screed of 50mm thick cement concrete 1:8:16 to be laid below the topping using mechanical mixer for mixing of material |
| 574 | Conglomerate floor 40mm thick cement concrete topping 1:2:4 (Using mechanical mixer for mixing of material). |
| 575 | Providing and laying water proofing treatmentin sunken portion of WCs, bathroom etc., by applying cement slurry mixed with water proofing cement compound consisting of applying : a) First layer of slurry of cement @0.488 kg /sqm mixed with water proofing cement compound @ 0.253 kg/sqm. This layer will be allowed to air cure for 4 hours. b) Second layer of slurry of cement @ 0.242 kg/sqm mixed with water proofing cement compound @ 0.126 kg/ sqm. This layer will beallowed to air cure for 4 hours followed with water curing for 48 hours. The rate includes preparation of surface, treatment and sealingof all joints, corners, junctions of pipes and masonry with polymer mixed slurry. |
| 576 | Providing and laying vitrified floor tiles in different sizes in light colour shades made using Full Body Technology (thickness to be specified by the manufacturer) with water absorption’s less than 0.08% and conforming to IS : 15622 of approved make in all colours and shades, laid on 20mm thick cement mortar 1:4 (1 cement: 4 fine sand), complete. ( Full body vitrified tiles have pigment in entire body / thickness of tile which makes chips and scratches less noticeable and make na ideal choice for high traffic zones.)Size 600x600 mm |
| 577 | Providing and fixing 1st quality ceramic glazedwall tiles Matt/Semi Matt/Glosy/Highly Gloss finish/Highlighter/emboss conforming to IS : 15622 (thickness to be specified by the manufacture of approved make in all colours,shades except burgundy, bottle green, black of size 600 x 300 mm as approved by Engineer-in- Charge in skirting, risers of steps and dados over 12 mm thick bed of cement Mortar 1:4 (1 cement: 4 fine sand) and jointing with grey cement slurry @ 3.3kg per sqm including pointing in white cement mixed with pigment of matching shade complete. |
| 578 | Coloured Granite stone tiles 15mm to 20mm thick in skirting, risers of steps, dado walls and pillars laid in 12.5mm thick cement mortar 1:3 (1 cement 3 coarse sand) and jointed with neat cement slurry mixed with pigment to match the shade of stone, including rubbing and polishing including labour for fixing dowel pins and cramps. |
| 579 | Extra for pre finished nosing to treads of steps of marble stone. ( Full gola, half round gola etc.) |
| 580 | Providing opening of required size & shape for wash basin/ kitchen sink in kitchen platform, vanity counter and similar location in marble/ granite/ stone work, including necessary holes for pillar taps etc.including moulding, rubbing and polishing of cut edges etc. complete. |
| 581 | Cement Concrete 1:2:4 with stone ballast or shingle.using concrete mixing volumetric type |
| 582 | Cold twisted deformed (Ribbed/ Tor Steel Bar/TMT) Bars Fe 500 grade as per IS 1786-2008, for R.C.C works, where not including in the complete rate of RCC including bending and placing in position complete |
| 583 | Centering and Shuttering for flat surface such as suspended floors, roofs, landings, chajjas, shelves etc. Please Enable Macros to View BoQ information |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |
Copyright © 2026 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail