| 1 | DSR item no.2.2Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required. |
| 2 | 63/100 A,30KA,FPMCCB |
| 3 | 250 A,36KA,FPMCCB |
| 4 | 630 A,50KA,FPMCCB |
| 5 | DSR item no.4.1Supplying and installing following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required. |
| 6 | 300 mm width X 50 mm depth X 1.6 mm thickness |
| 7 | DSR ITEM NO.5.6Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 8 | DSR ITEM NO.5.8Supplying and laying 25 mm X 5 mm copper strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm) |
| 9 | DSR Item No 15.16Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc. direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required. |
| 10 | 63 mm dia (OD-63 mm & ID-51 mm nominal) |
| 11 | 160 mm dia (OD-160 mm & ID-135 mm nominal) |
| 12 | Supply and laying of PVC insulated PVC sheathed Aluminum conductor cable of 1.1 KV grade as per IS 7098 (Part-I) 1988 (amended up to date) of the following sizes to be laid direct on surface with the help of M.S. clamp of suitable thickness. The job include the cost of making connections with suitable size of Al. Lugs / thimbles, testing, commissioning etc. as required to the entire satisfaction of Engineer In Charge. The cable should be of Polycab / Havells / Finolex / RR Kabel/ KEI/ RPG/ Universal/Grandlay make only. |
| 13 | Size 16 Sq.mm 4 core PVC Al. Arm. Cond. Cable |
| 14 | Size 300 Sq.mm 3.5 core PVC Al. Arm. Cond. Cable |
| 15 | Supply and Laying of following XLPE insulated and PVC sheathed, armored, aluminum conductor cable of 1.1KV grade as per IS 7098 (Part-I) 1988 (amended up to date) of the following sizes to be laid in existing trench/ DWC/RCC/HUME pipe as required at site. The job include the cost of making connections with suitable size of Al. Lugs/ thimbles, testing, commissioning etc. as required to the entire satisfaction of Engineer In Charge. The cable should be of Polycab / Havells / Finolex / RR Kabel/ KEI/ RPG/ Universal/Grandlay make only. |
| 16 | Size 16 Sq.mm 4 core PVC Al. Arm. Cond. Cable |
| 17 | Size 120 Sq.mm 3.5 core PVC Al. Arm. Cond. Cable |
| 18 | Size 300 Sq.mm 3.5 core PVC Al. Arm. Cond. Cable |
| 19 | Size 400 Sq.mm 3.5 core PVC Al. Arm. Cond. Cable |
| 20 | Shifting of existing AMF panel from one location to another location with the help of crane required to complete the job. The job include cost of dismantling of incoming, outgoing connection and re-erection of the same after shifting. The job includes the cost oflabour, crane charges and other petty material required to complete the job to the entire satisfaction of Engineer in charge of the work. |
| 21 | Supplying, Installation, Testing & Commissioning of Modular, Sectionalized (Form-4B Construction) Low Voltage Panel suitable for 415 V, 3 Phase, 4 wire 50 Hz AC supply system as per standard IEC 61439 Part-1 & Part-2 as Totally Type Tested Assembly and of suitable size fabricated in compartmentalized design from CRCA sheet steel of 2mm thick for frame work and covers & doors of 1.6mm thick sheet, 3 mm thick for gland plates with stiffeners wherever required, having vibration free structure chemically treated with seven tank process before painting for surface treatment and powder coated, with suitable electrolytic grade high conductivity Aluminium busbar extensible type, DMC/SMC bus bar supports, bottom base channel of MS section not less than 100mm x 50mm x 5 mm thick, fabrication shall be done in transportable sections, entire LENGTH panel shall have a common copper earth bar of suitable size at the rear with 2 Nos. earth stud, solid connections from main bus bar to switch gears with required size of Aluminium bus bars and control wiring with 2.5 Sq.mm. PVC insulated copper FR conductor S/C cable for voltage & Current respectively. The board shall be dust and vermin proof with degree of protection IP42, free standing type mounted on base channel. The job includes all material cost (ACB, MCCBs Space&other Accessories) labour, carriage of panel to the site, testing and commissioning as required to complete the job as per drawing of the panel to the satisfaction of the Engineer in charge.The job includes making connection of the outgoing cable with lugs/thimbles duly crimped and making connection with the incoming existing O/H bus trunking or cable as per site requirement. The LT panel should have following switchgear and accessories as mentioned below: - |
| 22 | INCOMING (For Metering panel) |
| 23 | Space for 630 Amps. four Pole, MCCBin the Panel:- 1 No. |
| 24 | BUS BAR |
| 25 | Supply and erection of TPN Aluminum bus bars (having 100% Neutral) of minimum of 630 Amps. Capacity with heat shrinkable colored sleeves and i/c DMC/SMC bus bar supports at required intervals complete for cross section, size supports & their spacing etc. for withstanding fault level of 31 MVA for 1 Sec. The current density of aluminum bus shall be 1 Amp/sq. mm.- 1 Set. |
| 26 | OUTGOING |
| 27 | Space for 630 Amps. four Pole, MCCB in the Panel:-1 No. |
| 28 | Space for 250 Amps. four Pole, MCCB in the Panel:-1 No. |
| 29 | Space for Spare MCCB |
| 30 | INCOMING (For DG panel) |
| 31 | Space for 250 Amps. four Pole, MCCB in the Panel:- 1 No. |
| 32 | BUS BAR |
| 33 | Supply and erection of TPN Aluminum bus bars (having 100% Neutral) of minimum of 250 Amps. Capacity with heat shrinkable colored sleeves and i/c DMC/SMC bus bar supports at required intervals complete for cross section, size supports & their spacing etc. for withstanding fault level of 31 MVA for 1 Sec. The current density of aluminum bus shall be 1 Amp/sq. mm.- 1 Set. |
| 34 | OUTGOING |
| 35 | Space for 63 Amps. four Pole, MCCB in the panel:-8 Nos. |
| 36 | Making of Haudi of following size for drawing of underground cable etc constructed with bricks wall 4½” thick and plastered from the inner side with cement, sand, mixture 1:5. The RCC cover molded in an angle frame of size 35mm x 35mm x 5mm should be provided above the Haudi which should rest on 40mm x 40mm x 5mm angle iron frame fixed on the upper portion of the Haudi. The cover should be provided with lifting arrangement. The rate includes all labour and material to complete the job with 1:4 CC mixture. |
| 37 | Size 2’ x 2’x 2’deep |
| 38 | Cutting and dismantling of existing broken and required floor and wall tile i/c old mortar using electric cutter, chisel, hammer etc. wherever required complete in all respect and removal of malba within 50 m lead clean the surface thoroughly as per the direction EIC. The job includes the cost of labourand other petty material required to complete the job to the entire satisfaction of the Engineer in charge of the work. |
| 39 | DSR civil 2.1Earth work in surface excavation not exceeding 30 cm in depth but exceeding 1.5 m in width as well as 10 sqm on plan including getting out and disposal of excavated earth upto 50 m and lift upto 1.5 m, as directed by Engineer-in- Charge: |
| 40 | All kinds of soil |
| 41 | DSR civil 2.27Supplying and filling in plinth with sand under floors, including watering, ramming, consolidating and dressing complete |
| 42 | DSR civil 4.1Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level : |
| 43 | 1:2:4 (1 cement : 2 coarse sand (zone-III) : 4 graded stone aggregate 20 mm nominal size) |
| 44 | 1:5:10 (1 cement : 5 coarse sand (zone-III): 10 graded stone aggregate 40 mm nominal size) |
| 45 | DSR civil 6.1Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in foundation and plinth in: |
| 46 | Cement mortar 1:6 (1 cement : 6 coarse sand) |
| 47 | DSR civil 10.2Structural steel work riveted, bolted or welded in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete. as required. |
| 48 | DSR civil 11.562 mm thick cement concrete flooring with concrete hardener topping, under layer 50 mm thick cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) and top layer 12 mm thick cement hardener consisting of mix 1:2 (1 cement hardener mix : 2 graded stone aggregate, 6 mm nominal size) by volume, hardening compound mixed @ 2 litre per 50 kg of cement or as per manufacture’s specifications. This includes cost of cement slurry, but excluding the cost of nosing of steps etc. complete. |
| 49 | DSR civil 13.412 mm cement plaster of mix: |
| 50 | 1:6 (1 cement : 6 coarse sand) |
| 51 | DSR civil 15.60Disposal of building rubbish / malba / similar unserviceable, dismantled or waste materials by mechanical means, including loading, transporting, unloading to approved municipal dumping ground or as approved by Engineer-in-charge, beyond 50 m initial lead, for all leads including all lifts involved. |
| 52 | DSR civil 21.1Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS: 733 and IS: 1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/ neoprene gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminium snap beading for glazing / paneling, C.P. brass / stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge. (Glazing, paneling and dash fasteners to be paid for separately) : |
| 53 | DSR civil 21.1.1For fixed portion |
| 54 | Powder coated aluminum (minimum thickness of powder coating 50 micron) |
| 55 | DSR civil 21.1.2For shutters of doors, windows & ventilators including providing and fixing hinges/ pivots and making provision for fixing of fittings wherever required including the cost of EPDM rubber / neoprene gasket required (Fittings shall be paid for separately) |
| 56 | Powder coated aluminium (minimum thickness of powder coating 50 micron) |
| 57 | DSR civil 21.3 |
| 58 | Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions etc. with EPDM rubber / neoprene gasket etc. complete as per the architectural drawings and the directions of engineerin-charge . (Cost of aluminium snap beading shall be paid in basic item): |
| 59 | With float glass panes of 5 mm thickness (weight not less than 12.50 kg/sqm) |
| 60 | Providing and fixing 60mm thick PUF wall Panels continous line sandwitch with 0.5 mm thick TCTPPGI,( 120 gm, 240 mpa, coated sheet of make JSW, Lloyd, syntex, Rinac or equivalent ) on both side having polyurethane foam of density 40± 2kg/cum between sheets. The panel sheet shall have one meter width and panel height as per height of room without any joint. The panel shall be fixed in toungue and groove joint with help of flashing comprising of PPGI U channels, L- section, end cap ,POPrevits , screws and otheraccessories complete in all respect. The PUF shall be CFC free and ozone friendly made with blowing agent will be N-Pantene. The gap at joint shall be filled with silicon sealant of approved brand (Macoy, pidilite or its equivalent ).These panels shall be fixed in alignment and plumb complete in all respect to the entire satisfaction to the Engineer incharge. |
| 61 | Providing and fixing 40mm thick PUF celling Panels continuous line sandwich with 0.5 mm thick TCT PPGI,( 120 gm, 240 mpa, coated sheet of make JSW, Lloyd, syntex, Rinac or equivalent) on both side having polyurethane foam of density 40± 2kg/cum between sheets. The panel sheet shall have corrugated sheet at top having crest of approx 30mm and the bottom shall be plane sheet with ribs. The panel sheet have one meter width and panel length as per length of room without any joint. The panel shall be fixed in toungue and groove joint with help of flashing comprising of PPGI U channels, L- section, end cap,POP rivets, screws and other accessories complete in all respect. The PUF shall be CFC free and ozone friendly made with blowing agent will be N-Pantene. The gap at joint shall be filled with silicon sealant of approved brand (Macoy, pidilite or its equivalent).These panels shall be fixed in alignment and plumb complete in all respect to the entire satisfaction to the Engineer incharge. |
| 62 | Providing and fixing Asbestos cement sheet strips 40 mm x 6mm for conglomerate / tertazzo floors complete fixed in position to the entire satisfaction of the engineer-in-charge. Please Enable Macros to View BoQ information |