| Sl. No. | Item Description |
| 1 | CIVIL WORKS:2.8 Earth work in excavation by mechanical means (Hydraulic excavator) / manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m. 2.8.1 All kinds of soil |
| 2 | 2.27 Supplying and filling in plinth with sand under floors, including watering, ramming, consolidating and dressing complete |
| 3 | 2.25 Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift upto 1.5 m |
| 4 | 2.35 Diluting and injecting chemical emulsion for POST-CONSTRUCTIONAL anti-termite treatment (excluding the cost of chemical emulsion) :2.35.3 Treatment of soil under existing floors using chemical emul sion @ one litre per hole, 300 mm apart including drilling 12 mm diameter holes and plugging with cement mortar 1 :2 (1 cement : 2 Coarse sand) to match the existing floor: 2.35.3.1 With Chlorpyriphos/Lindane E.C. 20% with 1% concentration |
| 5 | 4.1 Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level :4.1.5 1:3:6 (1 Cement : 3 coarse sand (zone-III) derived from natural sources : 6 graded stone aggregate 20 mm nominal size derived from natural sources) |
| 6 | 5.1 Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level : 5.1.2 1:1.5:3 (1 cement : 1.5 coarse sand (zone-III) derived from natural sources : 3 graded stone aggregate 20 mm nominal size de rived from natural sources) |
| 7 | 5.3 Reinforced cement concrete work in beams, suspended floors, roofs having slope up to 15° landings, balconies, shelves, chajjas, lintels, bands, plain window sills, staircases and spiral stair cases above plinth level up to floor five level, excluding the cost of centering, shuttering, finishing and reinforcement with 1:1.5:3 (1 cement : 1.5 coarse sand(zone-III) derived from natural sources : 3 graded stone aggregate 20 mm nominal size derived from natural sources). |
| 8 | 5.2 Reinforced cement concrete work in walls (any thickness), including attached pilasters, buttresses, plinth and string courses, fillets, columns, pillars, piers, abutments, posts and struts etc. above plinth level up to floor five level, excluding cost of centering, shuttering, finishing and reinforcement : 5.2.2 1:1.5:3 (1 cement : 1.5 coarse sand(zone-III) derived from natu ral sources : 3 graded stone aggregate 20 mm nominal size derived from natural sources) |
| 9 | 4.10 Providing and laying damp-proof course 40mm thick with cement concrete 1:2:4 (1 cement : 2 coarse sand (zone-III) derived from natural sources : 4 graded stone aggregate 12.5mm nominal size derived from natural sources) |
| 10 | 5.9 Centering and shuttering including strutting, propping etc. and removal of form for 5.9.1 Foundations, footings, bases of columns, etc. for mass concrete |
| 11 | 5.9.3 Suspended floors, roofs, landings, balconies and access platform |
| 12 | 5.9.5 Lintels, beams, plinth beams, girders, bressumers and cantilevers |
| 13 | 5.9.6 Columns, Pillars, Piers, Abutments, Posts and Struts |
| 14 | 6.1 Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in foundation and plinth in: 6.1.1 Cement mortar 1:4 (1 cement : 4 coarse sand) |
| 15 | 11.2 Dry brick on edge flooring in required pattern with bricks of class designation 7.5 on a bed of 12 mm mud mortar, including filling joints with Jamuna sand, with common burnt clay non modular bricks. |
| 16 | 6.13 Half brick masonry with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V level. 6.13.2 Cement mortar 1:4 (1 cement :4 coarse sand) |
| 17 | 10.14 Providing and fixing pressed steel door frames conforming to IS: 4351, manufactured from commercial mild steel sheet of 1.60 mm thickness, including hinges, jamb, lock jamb, bead and if required angle threshold of mild steel angle of section 50x25 mm, or base ties of 1.60 mm, pressed mild steel welded or rigidly fixed together by mechanical means, including M.S. pressed butt hinges 2.5 mm thick with mortar guards, lock strike-plate and shock absorbers as specified and applying a coat of approved steel primer after pre-treatment of the surface as directed by Engineer-in-charge:10.14.1.1 Fixing with adjustable lugs with split end tail to each jamb |
| 18 | 9.21 Providing and fixing ISI marked flush door shutters conforming to IS : 2202 (Part I) non-decorative type, core of block board construction with frame of 1st class hard wood and well matched commercial 3 ply veneering with vertical grains or cross bands and face veneers on both faces of shutters: 9.21.1 35 mm thick including ISI marked Stainless Steel butt hinges with necessary screws |
| 19 | 9.141 Providing and fixing PVC Door Frame of size 50x47 mm with a wall thickness of 5 mm (± 0.2 mm), made out of single piece extruded PVC profile, with mitred cut joints and joint with 2 nos of PVC bracket of size 190 mm x 100 mm long arms of cross section size 35 x 15 mm & self driven self taping screws, the vertical door profiles to be reinforced with 40x20 mm M.S. rectangular tube of 0.8 mm , including providing EPDM rubber gasket weather seal throughout the frame, including jointing 5 mm PVC frame strip with PVC solvent cement on the back of the profile. The door frame to be fixed to the wall using 8 x100 mm long anchor fasteners complete, all as per manufacturer's specification and direction of Engineer -in- charge. |
| 20 | 9.142 35 mm thick factory made Solid panel PVC Door shutter, made out of single piece extruded soild PVC profiles, 5 mm (± 0.2 mm) thick, having styles & rails (except lock rail) of size 95 mmx 35 mm x 5 mm, out of which 75 mm shall be flat and 20 mm shall be tapered (on both side), having one side thickness of 15 mm integrally extruded on the hinge side of the profile for better screw holding power, including reinforcing with MS tube of size 40 mm X 20 mm x 1 mm, joints of styles & rails to be mitered cut & joint with the help of PVC solvent cement, self driven self tapping screws & M.S. rectangular pipes bracket of size 190 mm X 100 mm of cross section size 35 mm x 17 mm x 1 mm at each corner. Single piece extruded 5 mm thick solid PVC Lock rail of size 115 mm x 35 mm, out of which 75 mm to be flat and 20 mm to be tapered at both ends, having 15 mm solid core in middle of rail section integrally extruded, fixing the styles & rails with the help of solvent and self driven self tapping screws of 125 mm x 11 mm, including providing 5 mm Single piece solid PVC extruded sheet inserted in the door as panel, all complete as per manufacturer's specification and direction of Engineer in-charge. 9.142.1 Non decorative finish (matt finish) |
| 21 | 5.22 Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete upto plinth level. 5.22.6 Thermo-Mechanically Treated bars of grade Fe-500D or more. |
| 22 | 10.16 Steel work in built up tubular (round, square or rectangular hollow tubes etc.) trusses etc., including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer, including welding and bolted with special shaped washers etc. complete. 10.16.1 Hot finished welded type tubes |
| 23 | 11.41 Providing and laying vitrified floor tiles in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS: 15622, of approved make, in all colours and shades, laid on 20mm thick cement mortar 1:4 (1 cement : 4 coarse sand), jointing with grey cement slurry @ 3.3 kg/ sqm including grouting the joints with white cement and matching pigments etc., complete. 11.41.2 Size of Tile 500x500 mm |
| 24 | 11.21 Providing and fixing 10 mm thick acid and/or alkali resistant tiles of approved make and colour using acid and/or alkali resisting mortar bedding, and joints filled with acid and/or alkali resisting cement as per IS : 4457, complete as per the direction of Engineer-in- Charge. 11.21.1 In flooring on a bed of 10 mm thick mortar 1:4 (1 acid proof cement : 4 coarse sand) 11.21.1.1 Acid and alkali resistant tile |
| 25 | 8.31 Providing and fixing Ist quality ceramic glazed wall tiles conforming to IS: 15622 (thickness to be specified by the manufacturer), of approved make, in all colours, shades except burgundy, bottle green, black of any size as approved by Engineer-in-Charge, in skirting, risers of steps and dados, over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand) and jointing with grey cement slurry @ 3.3kg per sqm, including pointing in white cement mixed with pigment of matching shade complete. |
| 26 | 11.56 Providing and laying Polished Granite stone flooring in required design and patterns, in linear as well as curvilinear portions of the building all complete as per the architectural drawings with 18 mm thick stone slab over 20 mm (average) thick base of cement mortar 1:4 (1 cement : 4 coarse sand) laid and jointed with cement slurry and pointing with white cement slurry admixed with pigment of matching shade including rubbing, curing and polishing etc. all complete as specified and as directed by the Engineer-in-Charge. 11.56.1 Polished Granite stone slab colour of Black, Cherry/Ruby Red or equivalent |
| 27 | 11.20 Chequerred precast cement concrete tiles 22 mm thick in footpath & courtyard, jointed with neat cement slurry mixed with pigment to match the shade of tiles, including rubbing and cleaning etc. complete, on 20 mm thick bed of cement mortar 1:4 (1 cement: 4 coarse sand). 11.20.1 Light shade pigment using white cement |
| 28 | 16.91 Providing and laying factory made chamfered edge Cement Concrete paver blocks in footpath, parks, lawns, drive ways or light traffic parking etc, of required strength, thickness & size/ shape, made by table vibratory method using PU mould, laid in required colour & pattern over 50mm thick compacted bed of sand, compacting and proper embedding/laying of inter locking paver blocks into the sand bedding layer through vibratory compaction by using plate vibrator, filling the joints with sand and cutting of paver blocks as per required size and pattern, finishing and sweeping extra sand. complete all as per direction of Engineer-in-Charge.16.91.1 60mm thick cement concrete paver block of M-35 grade with approved colour, design & pattern. |
| 29 | 13.4 12 mm cement plaster :13.4.1 1:4 (1 cement : 4 coarse sand) |
| 30 | 13.5 15 mm cement plaster on rough side of single or half brick wall of mix:13.5.1 1:4 (1 cement : 4 coarse sand) |
| 31 | 13.42 Distempering with 1st quality acrylic distemper (ready mixed) having VOC content less than 50 gms/litre, of approved manufacturer, of required shade and colour complete, as per manufacturer's specification. 13.42.1 Two or more coats on new work |
| 32 | 13.43 Applying one coat of water thinnable cement primer of approved brand and manufacture on wall surface : 13.43.1 Water thinnable cement primer |
| 33 | 13.48A Finishing walls with 100% Premium acrylic emulsion paint having VOC less than 50 gm/litre and UV resistance as per IS 15489:2004, Alkali & fungal resistance, dirt resistance exterior paint of required shade (Company Depot Tinted) with silicon additives. 13.48A.1 New work (Two or more coats applied @ 1.43 litre/ 10 sqm. Over and including priming coat of exterior primer applied @ 0.90 litre/10 sqm. |
| 34 | General Purpose (Asian Paint/ Barger Paint/ ICI Paint/ J&N Paint/ Nerolec) |
| 35 | 13.52 Finishing with Epoxy paint (two or more coats) at all locations prepared and applied as per manufacturer's specifications including appropriate priming coat, preparation of surface, etc. complete. 13.52.1 On steel work |
| 36 | 13.80 Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete. |
| 37 | 12.50 Providing and fixing precoated galvanised iron profile sheets (size, shape and pitch of corrugation as approved by Engineer-in-charge) 0.50 mm (+ 0.05 %) total coated thickness with zinc coating 120 grams per sqm as per IS: 277, in 240 mpa steel grade, 5-7 microns epoxy primer on both side of the sheet and polyester top coat 15-18 microns. Sheet should have protective guard film of 25 microns minimum to avoid scratches during transportation and should be supplied in single length upto 12 metre or as desired by Engineer in-charge. The sheet shall be fixed using self drilling /self tapping screws of size (5.5x 55 mm) with EPDM seal, complete upto any pitch in horizontal/ vertical or curved surfaces, excluding the cost of purlins, rafters and trusses and including cutting to size and shape wherever required. |
| 38 | 12.51 Providing and fixing precoated galvanised steel sheet roofing accessories 0.50 mm (+0.05 %) total coated thickness, Zinc coating 120 grams per sqm as per IS: 277, in 240 mpa steel grade, 5-7 microns epoxy primer on both side of the sheet and polyester top coat 15-18 microns using self drilling/ self tapping screws complete : 12.51.1 Ridges plain (500 - 600mm) |
| 39 | 9.48 Providing and fixing M.S. grills of required pattern in frames of windows etc. with M.S. flats, square or round bars etc. including priming coat with approved steel primer all complete. 9.48.1 Fixed to steel windows by welding |
| 40 | 22.14 Grading roof for water proofing treatment with 22.14.1 Cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20mm nominal size) |
| 41 | 21.1 Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS: 733 and IS: 1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/ neoprene gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminium snap beading for glazing / paneling, C.P. brass / stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge. (Glazing, paneling and dash fasteners to be paid for separately) :21.1.1 For fixed portion21.1.1.2 Powder coated aluminium (minimum thickness of powder coating 50 micron) |
| 42 | 21.1.2 For shutters of doors, windows & ventilators including providing and fixing hinges/ pivots and making provision for fixing of fittings wherever required including the cost of EPDM rubber / neoprene gasket required (Fittings shall be paid for separately)21.1.2.2 Powder coated aluminium (minimum thickness of powder coating 50 micron) |
| 43 | 21.3 Providing and fixing 12mm thick prelaminated particle board flat pressed three layer or graded wood particle board condorming to IS:12823 Grade I Type II, in Panelling fixed in aluminium doors, windows shutters and partition frames with C.P. brass./ stainless steel screws etc. complete as per architectural drawings and direction of engineer in chare. |
| 44 | 21.3 Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions etc. with EPDM rubber / neoprene gasket etc. complete as per the architectural drawings and the directions of engineer-in-charge . (Cost of aluminium snap beading shall be paid in basic item):21.3.1 With float glass panes of 4.0 mm thickness (weight not less than 10kg/sqm) |
| 45 | 9.97 Providing and fixing aluminium tower bolts, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868 ) transparent or dyed to required colour or shade, with necessary screws etc. complete : 9.97.1 300x10 mm |
| 46 | 9.97.2 250x10 mm |
| 47 | 9.100 Providing and fixing aluminium handles, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade, with necessary screws etc. complete : 9.100.1 125 mm |
| 48 | 9.101 Providing and fixing aluminium hanging floor door stopper, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour and shade, with necessary screws etc. complete. 9.101.1 Single rubber stopper |
| 49 | 4.17 Making plinth protection 50mm thick of cement concrete 1:3:6 (1 cement : 3 coarse sand (zone-III) derived from natural sources : 6 graded stone aggregate 20 mm nominal size derived from natural sources) over 75mm thick bed of dry brick ballast 40 mm nominal size, well rammed and consolidated and grouted with fine sand, including necessary excavation, levelling & dressing & finishing the top smooth. |
| 50 | 16.12 Dry brick pitching half brick thick in drains including supply of bricks and preparing the surface complete : 16.12.1 With common burnt clay F.P.S. (non modular) bricks of class designation 7.5 |
| 51 | Supply, Installation, Fixing of DRY CHEMICAL POWDER Fire Extinguisher confirming to IS:2171 with ISI mark and CO2 cartridge will be confirming to IS:4947 with ISI mark, Powder will be confirming to IS:4308 with ISI Mark (5 KG) |
| 52 | Supply, Installation, Fixing of ABC Stored pressure Fire Extinguisher with built- IN pressure Gauge to Know the Ready ness of the Extinguisher Squeeze Grip Handle As per IS:13849 with ISI mark (05 kg capacity)BRAND: FIRESTOP/ FIREND/ FIRE SHIELD |
| 53 | SANITARY AND WATER SUPPLY17.1 Providing and fixing water closet squatting pan (Indian type W.C. pan ) with 100 mm sand cast Iron P or S trap, 10 litre low level white P.V.C. flushing cistern, including flush pipe, with manually controlled device (handle lever) conforming to IS : 7231, with all fittings and fixtures complete, including cutting and making good the walls and floors wherever required: 17.1.1 White Vitreous china Orissa pattern W.C. pan of size 580x440 mm with integral type foot rests |
| 54 | 17.2 Providing and fixing white vitreous china pedestal type water closet (European type W.C. pan) with seat and lid, 10 litre low level white P.V.C. flushing cistern, including flush pipe, with manually controlled device (handle lever), conforming to IS : 7231, with all fittings and fixtures complete, including cutting and making good the walls and floors wherever required : 17.2.1 W.C. pan with ISI marked white solid plastic seat and lid |
| 55 | 17.7 Providing and fixing wash basin with C.I. brackets, 15 mm C.P. brass pillar taps, 32 mm C.P. brass waste of standard pattern, including painting of fittings and brackets, cutting and making good the walls wherever require: 17.7.1 White Vitreous China Wash basin size 630x450 mm with a pair of 15 mm C.P. brass pillar taps |
| 56 | 17.9 Providing and fixing kitchen sink with C.I. brackets, C.P. brass chain with rubber plug, 40 mm C.P. brass waste complete, including painting the fittings and brackets, cutting and making good the walls wherever required: 17.9.1 White glazed fire clay kitchen sink of size 600x450x 250 mm |
| 57 | 17.11 Providing and fixing white vitreous china laboratory sink with C.I. brackets, C.P. brass chain with rubber plug, 40 mm C.P brass waste and 40mm C.P. brass trap with necessary C.P. brass unions complete, including painting of fittings and brackets, cutting and making good the wall wherever required : 17.11.2 Size 600x450x200 mm |
| 58 | 17.32 Providing and fixing mirror of superior glass (of approved quality) and of required shape and size with plastic moulded frame of approved make and shade with 6 mm thick hard board backing : 17.32.1 Circular shape 450 mm dia |
| 59 | 17.33 Providing and fixing 600x120x5 mm glass shelf with edges round off, supported on anodised aluminium angle frame with C.P. brass brackets and guard rail complete fixed with 40 mm long screws, rawl plugs etc., complete. |
| 60 | 17.73 Providing and fixing PTMT towel rail complete with brackets fixed to wooden cleats with CP brass screws with concealed fittings arrangement of approved quality and colour.17.73.1 450 mm long towel rail with total length of 495 mm, 78 mm wide and effective height of 88 mm, weighing not less than 170 gms |
| 61 | 17.70 Providing and fixing PTMT Bottle Trap for Wash basin and sink.17.70.1 Bottle trap 31mm single piece moulded with height of 270 mm, effective length of tail pipe 260 mm from the centre of the waste coupling, 77 mm breadth with 25 mm minimum water seal, weighing not less than 260 gms |
| 62 | 17.69 Providing and fixing PTMT Waste Coupling for wash basin and sink, of approved quality and colour.17.69.1 Waste coupling 31 mm dia of 79 mm length and 62mm breadth weighing not less than 45 gms |
| 63 | 17.35 Providing and fixing soil, waste and vent pipes :17.35.1 100 mm dia17.35.1.1 Sand cast iron S&S pipe as per IS: 1729 |
| 64 | 17.35.2 75 mm diameter :17.35.2.1 Sand cast iron S&S pipe as per IS: 1729 |
| 65 | 17.36 Providing and filling the joints with spun yarn, cement slurry and cement mortar 1:2 ( 1 cement : 2 fine sand) in S.C.I./ C.I. Pipes :17.36.1 75 mm dia pipe |
| 66 | 17.36.2 100 mm dia pipe |
| 67 | 17.38 Providing and fixing bend of required degree with access door, insertion rubber washer 3 mm thick, bolts and nuts complete.17.38.1 100 mm dia17.38.1.1 Sand cast iron S&S as per IS - 1729 |
| 68 | 17.38.2 75 mm dia17.38.2.1 Sand cast iron S&S as per IS - 1729 |
| 69 | Providing fitting and fixing 110mm dia, PVC cowel with ISI make complete as directed and specified |
| 70 | 17.60 Providing and fixing trap of self cleansing design with screwed down or hinged grating with or without vent arm complete, including cost of cutting and making good the walls and floors : 17.60.1 100 mm inlet and 100 mm outlet 17.60.1.1 Sand cast iron S&S as per IS: 3989 |
| 71 | 17.60.2 100 mm inlet and 75 mm outlet17.60.2.1 Sand cast iron S&S as per IS - 3989 |
| 72 | Internal water supply work18.9 Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply including all CPVC plain & brass threaded fittings This includes jointing of pipes & fittings with one step CPVC solvent cement, trenching, refilling & testing of joints complete as per direction of Engineer in Charge. External work 18.9.4 32 mm nominal dia Pipes |
| 73 | 18.8 Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer in Charge. Concealed work, including cutting chases and making good the walls etc. 18.8.1 15 mm nominal dia Pipes |
| 74 | 18.8.2 20 mm nominal dia pipes |
| 75 | 18.8.3 25 mm nominal dia pipes |
| 76 | 18.50 Providing and fixing C.P. brass long nose bib cock of approved quality conforming to IS standards and weighing not less than 810 gms. 18.50.1 15 mm nominal bore |
| 77 | 18.52 Providing and fixing C.P. brass stop cock (concealed) of standard design and of approved make conforming to IS:8931. 18.52.1 15 mm nominal bore |
| 78 | 18.17 Providing and fixing gun metal gate valve with C.I. wheel of approved quality (screwed end) : 18.17.1 25 mm nominal bore |
| 79 | 18.17.3 32 mm nominal bore |
| 80 | 18.48 Providing and placing on terrace (at all floor levels) polyethylene water storage tank, IS : 12701 marked, with cover and suitable locking arrangement and making necessary holes for inlet, outlet and overflow pipes but without fittings and the base support for tank. |
| 81 | INTERNAL ELECTRIFICATION SCHEDULE ITEMS:-WIRING IN PVC CONDUIT1.10 Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI boxand earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required.1.10.1 Group A |
| 82 | 1.10.2 Group B |
| 83 | 1.10.3 Group C |
| 84 | 1.12 Wiring for light/ power plug with 2X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/recessed medium class PVC conduit alongwith 1 No. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required. |
| 85 | 1.14 Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as reqd1.14.4: 2 X 6 sq. mm + 1 X 6 sq. mm earth wire |
| 86 | 1.14.4: 2 X 6 sq. mm + 1 X 6 sq. mm earth wire |
| 87 | 1.14.5: 2 X 10 sq. mm + 1 X 6 sq. mm earth wire |
| 88 | 1.14.10 : 4 X 10 sq. mm + 2 X 6 sq. mm earth wire Metre 543 |
| 89 | 1.24 Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.1.24.4: 3 pin 5/6 A socket outlet |
| 90 | 1.24.5: 6 pin 15/16 A socket outlet |
| 91 | 1.24.8: Bell push |
| 92 | 1.25 Supplying and fixing two module stepped type electronic fan regulator on the existing switch box including connections but excluding modular plate etc. as required. |
| 93 | 1.26 Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required. |
| 94 | 1.31 Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required. |
| 95 | 1.32 Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required. |
| 96 | 1.34 Supplying and fixing brass batten/ angle holder including connection etc. as required. |
| 97 | 1.35 Installation ,Testing, Commissioning of wall bracket /ceiling fittings of all sizes and shapes containing upto two GLS/CFL/LED lamps per fitting, complete with all accessories including connections etc. as required. |
| 98 | 1.38 Supplying and fixing call bell/ buzzer suitable for single phase, 230 V, complete as required. |
| 99 | 1.41 Installation, testing and commissioning of pre-wired fluorescent fitting / compact fluorescent fitting of all types, complete with all accessories and tube/lamp etc. directly on ceiling/ wall, including connections with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable and earthing etc. as required. |
| 100 | 1.45 1.45 Installation, testing and commissioning ofceling fan, including wiring the down rods of standard length (upto 30cm) with 1.5 sq mm FRLS PVC insulated copper conductor, single coe cable including providing and fixing phenolic laminated sheet cover on the fan box etc. as required. |
| 101 | 1.50 Installation of exhaust fan in the existing opening, including making good the damage , connection, testing, commissioning eta as required.1.50.1 Upto 450 mm sweep |
| 102 | MCCB, MCB & DB'S2.3 Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)2.3.3 12 way , Double door |
| 103 | 2.4 Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)2.4.1 4 way (4 + 12), Double door |
| 104 | 2.10 Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.2.10.1 Single pole |
| 105 | 2.10.3 Double pole |
| 106 | 2.11 Supplying and fixing single pole blanking plate in the existing MCB DB complete etcas required. |
| 107 | 2.13 Supplying and fixing following rating, four pole, 415 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.2.13.2 63 A |
| 108 | 2.14 Supplying and fixing following rating, double pole, (single phase and neutral), 240 V, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required.2.14.2 40 A |
| 109 | 2.15 Supplying and fixing following rating, four pole, (three phase and neutral), 415 V, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required.2.15.3 63 A |
| 110 | 2.18 Supplying and fixing 20 A, 240 V, SPN Industrial type socket outlet, with 2 pole and earth, metal enclosed plug top alongwith 20 A \\"C\\" curve, SP, MCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required. |
| 111 | EARTHING5.2 Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc.with charcoal/ coke and salt as required. |
| 112 | 5.6 Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 113 | 5.12 Providing and laying earth connection from earth electrode with 6 SWG dia G.I. Wire in 15 mm dia G.I. pipe from earth electrode including connection with G.I. thimble excavation and re-filling as required. |
| 114 | 5.15 Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required. |
| 115 | 7.1 Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required.7.1.3 Above 95 sq. mm and upto 185 sq. mm |
| 116 | NON SCHEDULE ITEMS:-FiITTING ITEMSAnalysis Rate: Supplying, Installation, testing and commissioning of LED Bulb in the existing bracket in wall/ceiling with making necessary connection as required complete. Make Syska or Equivalent |
| 117 | Analysis Rate: Supplying, Installation, testing and commissioning of LED Florescent Tube in the wall/ceiling with making necessary connection as required complete. Make Wipro or Equivalent |
| 118 | Analysis Rate: Supplying, Installation, testing and commissioning of LED Panel Light (2x2) in the ceiling with making necessary connection as required complete. Make Philips or Equivalent |
| 119 | Analysis Rate: Supplying installation testing and commissioning of A.C. Ceiling fan 1200 mm complete with all accessories like down rod, canopy etc. of following sweeps with making necessary connection as approved by the Deptt. [ without regulator ] Make Orient or equivalent |
| 120 | Analysis Rate: Supplying, Installation, testing and commissioning of Exhaust fan, Domestic,250 mm sweep in the existing hole on the wall with making necessary connection as required complete. Make Orient or equivalent |
| 121 | Analysis Rate: Supplying with installation testing and commissioning of Split type air conditioner of the following capacity with cordless remote complete with copper pipe and electrical connection cable, as approved by the Deptt.)up to 5 m between the room unit and out door unit as directed by the department.Bluestar make, 1.5 Ton Capacity ,Premium Model |
| 122 | Analysis Rate: Supplying with fitting and fixing Voltage stabilizer of 4.0 KVA Automatic Input 120-280 V Out put 210-250 V complete including making necessary connection as approved, specified and directed by the deptt. Make Servokon or equivalent |
| 123 | Analysis Rate: Supplying with fitting and fixing Single Phase D. O. L Starter of the following specification complete including making necessary connection as specified and directed by the deptt. (a) Overload Relay Range 3.8 - 6.0 Amps for 2.2 KW |
| 124 | Analysis Rate: Supply and laying of following size PVC/XLPE insulated and PVC sheathed 1.1 KV Grade Solid Aluminium conductor up to 10 sq mm balance stranded conductor, XLPE Insulated, cores laid up, PVC tape inner sheathed, Armour1988 armoured U.G. cable U.G. cable laid in ground/partially in air (as required for termination over ground including excavation of cable trench up to depth of 75cm, refilling, protective brick covering, Sand cushioning etc complete handling of surplus spoil, debris et to proper place as specified and directed by the deptt.3 & 1/2 C 120 Sq MM |
| 125 | Main L.T. PanelAnalysis Rate: Supplying and installation of metal enclosed wall/floor mounted front operated cubical type switch gear panel suitable for indoor installation conforming to IS: 8623 (Part I & II). The Panel should be made of sheet steel and thickness not less than 2mm and structural steel having light section. The panel shall be completely dust tight and vermin proof and shall be painted with anti corrosive and anti condensation type two coats of primer and two coats of paint. All wiring shall be PVC insulated and PVC sheathed of 1100 volt grade of required size. The panel should have provision of entry of cable at the bottom and also provision of out going feeders from the bottom of the panel. The bus bar shall be of high quality copper of uniform cross section. The panel shall consist of the following items (viz. voltmeter, ammeter, CT, indicating lamps, selector switch etc.) connected as per drawing and shall be flush mounted on the front of the panel.Incommer: 125 A ,4P, MCCB - 1 No125 A, COS - 1 NoDigital Ammeter - 2 NosDigital Voltmeter - 2 NosSwitch Fuse Unit - 6 NosSelector Switch - 4 NosIndicating Lamp- 2 SetsBus-Bars: 250 A TPN electrolytic Copper Bus Bar of uniform cross-section (30mmx10mm) – 1 setOutgoing:63 A 4P MCB – 4 Nos.40A 4P MCB - 4 Nos32A DP MCB - 3 NosMotor Pump Set |
| 126 | Analysis Rate: Supplying including installation, connection as approved by the Deptt., testing and commissioning of SUBMERSIBLE PUMP SET 2HP, 3 (Three Phase) with steel cable rope and submersible cable complete as directed and specified by the deptt. Three phase Submersible motor pump set (Texmo / Crompton Greaves/ Aquatic/ CRI/ V-Guar suitable for 100 mm bore well and above. 5 HP STAGE 14 to 50 with MCB controlled Submersible motor pump set control panel. |
| 127 | CONSTRUCTION OF 11 KV HT LINE & 63 KVA SUB-STATION SCHEDULE ITEMS:-13.1 Supplying and erection of galvanised stay set for 11 KV over head lines complete with 19/ 20 mm dia X 1.8 metres long stay rod, anchor plate of size 45 cm X 45 cm X 7.5 mm thick, thimble, stay clamps, turn buckle ( 20 mm X 600 mm ), 7/ 4.00 mm dia G.I. stay wire and 11 KV strain insulator etc in cement concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size ) foundation including excavation and refilling etc. as required. |
| 128 | 13.4 Supplying of channel iron 75 mm X 40 mm X 6 mm (7.14 kg per metre) cross arm for two 11 KV over head line conductors complete with 50 mm X 50 mm X 6 mm (angle iron bracket welded to the channel iron and complete with 50 mm X 6mm M.S. flat iron clamps, bolts and nuts including drilling holes for insulator pins, bolts, nuts and washers etc (as per drawing) and painting with primer and finish paint as required. |
| 129 | 13.7 Supplying of two lengths of channel iron 75 mm X 40 mm X 6 mm (7.14 kg per metre) double pole cross arm for three wire 11KV over head line conductors complete with through bolts and nuts for clamping to the poles, 50 mm X 6 mm M.S. flats welded on one side to the channel iron and with bolts and nuts on the other side for tying the cross arms together, including drilling holes for insulator pins/ fittings, bolts, nuts and washers etc (as per drawing) and painting with primer and finish paint as required. |
| 130 | 13.10 Supplying and erection of 11 KV pin insulator complete with large steel head G.I. pin, nuts, washers etc. as required. |
| 131 | 13.11 Supplying and erection of 11 KV disc insulator for 11 KV over head lines with galvanised insulator fittings, ball and socket type and complete with galvanised strain clamps, bolts, nuts, washers etc. as required. |
| 132 | 13.12 Erection of disc/ pin insulator for 11 KV over head lines as required. |
| 133 | 13.13 Supplying and erection of three piece nonlinear resistor type lightning arrestor suitable for 3 wire, 11 KV overhead lines with rated voltage 9 KV (rms) with a nominal discharge current rating of 5 KA and complete with galvanised clamping arrangement, G.I. bolts, nuts, washers etc. as required. |
| 134 | 12.22 Erection of ACSR conductor of 7/3.35 mm to 7/4.00 diameter and above including binding etc. as required. |
| 135 | 5.2 Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc.with charcoal/ coke and salt as required. |
| 136 | 5.12 Providing and laying earth connection from earth electrode with 6 SWG dia G.I. Wire in 15 mm dia G.I. pipe from earth electrode including connection with G.I. thimble excavation and re-filling as required. |
| 137 | NON SCHEDULE ITEMS:-Analysis Rate: Supplying including installation, testing and commissioning of 63 KVA 11/0.433 KV aluminium wound out door type Energy Efficiency Level 1 transformer complete including all accessories like Earthing terminal, Liftung Lungs, Drain Valve, Oil filling Hole with plug, Silicagel Breather, First filling of Oil as per 1S355, Arcing Horn, Radiator, Air ReleasePlug etc. Transformer should be as per CEA guidelines as ammended up to date. (As required materials for the sub station will be measured and paid seperately). |
| 138 | Analysis Rate: Supply, Erection of PSC Pole 8.5 Mtr for 11 KV H.T line as per direction & specified by the Deptt. |
| 139 | Supply and laying of following size PVC/XLPE insulated and PVC sheathed 1.1 KV Grade Solid Aluminium conductor up to 10 sq mm balance stranded conductor, XLPE Insulated, cores laid up, PVC tape inner sheathed, Armour1988 armoured U.G. cable U.G. cable laid in ground/partially in air (as required for termination over ground including excavation of cable trench up to depth of 75cm, refilling, protective brick covering, Sand cushioning etc complete handling of surplus spoil, debris et to proper place as specified and directed by the deptt.3 & 1/2 C 120 Sq MM |
| 140 | Supply & installation of 11 KV GOAB Switch 400 Amp |
| 141 | Supply & installation of 11 KV DO Fuse 150 Amp |
| 142 | Supply & installation of DTR Fencing |
| 143 | Payment to be made to APDCL for Meter Cabinet |
| 144 | Payment to be made to APDCL for AMR Modem with Accessories |
| 145 | Payment to be made to APDCL for HT Trivector Meter |
| 146 | Payment to be made to APDCL for load security |
| 147 | SEPTIC TANK (2 Nos.)2.8 Earth work in excavation by mechanical means (Hydraulic excavator) / manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m. 2.8.1 All kinds of soil. |
| 148 | 4.1 Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level :4.1.5 1:3:6 (1 Cement : 3 coarse sand (zone-III) derived from natural sources : 6 graded stone aggregate 20 mm nominal size derived from natural sources) |
| 149 | 6.12 Half brick masonry with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in foundations and plinth in : 6.12.2 cement mortar 1:4 (1 cement : 4 coarse sand) |
| 150 | 6.1 Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in foundation and plinth in: 6.1.1 Cement mortar 1:4 (1 cement : 4 coarse sand) |
| 151 | 6.13 Half brick masonry with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V level. 6.13.2 Cement mortar 1:4 (1 cement :4 coarse sand) |
| 152 | 5.1 Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level : 5.1.2 1:1.5:3 (1 cement : 1.5 coarse sand (zone-III) derived from natural sources : 3 graded stone aggregate 20 mm nominal size de rived from natural sources) |
| 153 | Reinforced cement comcrete work in beams, suspended floors, roofs having slope up to 15° langings, balconies, shelves, chajjas, lintels, bands, plain window sills, staircases and spiral stair cases above plinth level up to floor five level, exluding the cost of centering, shuttering, finishing and reinforcement with 1:1.5:3 (1 cement : 1.5 coarse sand(zone-III) derived from natu ral sources : 3 graded stone aggregate 20 mm nominal size derived from natural sources) |
| 154 | 5.22 Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete upto plinth level. 5.22.6 Thermo-Mechanically Treated bars of grade Fe-500D or more. |
| 155 | 5.9 Centering and shuttering including strutting, propping etc. and removal of form for 5.9.1 Foundations, footings, bases of columns, etc. for mass concrete |
| 156 | 5.9.5 Lintels, beams, plinth beams, girders, bressumers and cantilevers |
| 157 | 13.5 15mm Cement plaster on rough side of single or half brick wall of mix:13.5.1 1:4 (1 cement : 4 coarse sand) |
| 158 | 19.33 Constructing soak pit 1.20x1.20x1.20 m filled with brickbats including S.W. drain pipe 100 mm diameter and 1.20 m long complete as per standard design. |
| 159 | 19.19 Providing and fixing in position precast R.C.C. manhole cover and frame.19.19.1 LD- 2.519.19.1.1 Rectangular shape 600x450mm internal dimensions |
| 160 | 19.30 Constructing brick masonry chamber for underground C.I. inspection chamber and bends with bricks in cement mortar 1:4 (1 cement : 4 coarse sand) C.I. cover with frame (light duty) 455x610 mm internal dimensions, total weight of cover with frame to be not less than 38 kg (weight of cover 23 kg and weight of frame 15 kg), R.C.C. top slab with 1:1.5:3 mix (1 cement : 1.5 fine sand : 3 graded stone aggregate 20 mm nominal size), foundation concrete 1:5:10 (1 cement : 5 fine sand : 10 graded stone aggregate 40 mm nominal size), inside plastering 12 mm thick with cement mortar 1:3 (1 cement : 3 coarse sand), finished smooth with a floating coat of neat cement on walls and bed concrete etc. complete as per standard design: 19.30.1 Inside dimensions 455x610 mm and 45 cm deep for single pipe line : 19.30.1.1 With common burnt clay F.P.S. (non modular) bricks of class designation 7.5 |
| 161 | DEEP TUBE WELL23.1 Boring/drilling bore well of required dia for casing/ strainer pipe, by suitable method prescribed in IS: 2800 (part I), including collecting samples from different strata, preparing and submitting strata chart/ bore log, including hire & running charges of all equipments, tools, plants & machineries required for the job, all complete as per direction of Engineer-in-charge, upto 90 metre depth below ground level. 23.1.1 All types of soil 23.1.1.1 300 mm dia |
| 162 | 23.2 Boring/drilling bore well of required dia for casing/ strainer pipe, by suitable method prescribed in IS: 2800 (part I), including collecting samples from different strata, preparing and submitting strata chart/ bore log, including hire & running charges of all equipments, tools, plants & machineries required for the job, all complete as per direction of Engineer -in-charge, beyond 90 metre & upto 150 metre depth below ground level. 23.2.1 All types of soil 23.2.1.2 350 mm dia |
| 163 | 23.3 Supplying, assembling, lowering and fixing in vertical position in bore well, unplasticized PVC medium well casing (CM) pipe of required dia, conforming to IS: 12818, including required hire and labour charges, fittings & accessories etc. all complete, for all depths, as per direction of Engineer -in-charge. 23.3.3 200 mm nominal size dia |
| 164 | 23.4 Supplying, assembling, lowering and fixing in vertical position in bore well unplasticized PVC medium well screen (RMS) pipes with ribs, conforming to IS: 12818, including hire & labour charges, fittings & accessories etc. all complete, for all depths, as per direction of Engineer-in-charge. 23.4.3 200 mm nominal size dia |
| 165 | 23.5 Supplying, filling, spreading & leveling stone boulders of size range 5 cm to 20 cm, in recharge pit, in the required thickness, for all leads & lifts, all complete as per direction of Engineer-in-charge. |
| 166 | 23.11 Supplying, assembling, lowering and fixing in vertical position in bore well, ERW (Electric Resistance Welded) FE 410 plain slotted (having slot of size 1.6/3.2 mm) mild steel threaded and socketed/ plain bevel ended pipe (type A) of required dia, conforming to IS: 8110, of reputed and approved make, having wall thickness not less than 5.40 mm, including painted with outside surface with two coats of anticorrosive bitumestic paint of approved brand and manufacture, including hire & labour charges, fittings & accessories, all complete, for all depths, as per direction of Engineer -in-charge.23.11.2 150 mm nominal size dia having minimum wall thickness 5.00m |
| 167 | 23.12 Development of tube well in accordance with IS : 2800 (part I) and IS: 11189, to establish maximum rate of usable water yield without sand content (beyond permissible limit), with required capacity air compressor, running the compressor for required time till well is fully developed, measuring yield of well by \\"V\\" notch method or any other approved method, measuring static level & draw down etc. by step draw down method, collecting water samples & getting tested in approved laboratory, i/c disinfection of tubewell, all complete, including hire & labour charges of air compressor, tools & accessories etc., all as per requirement and direction of Engineer-in-charge. |
| 168 | 23.13 Providing and fixing suitable size threaded mild steel cap or spot welded plate to the top of bore well housing/ casing pipe, removable as per requirement, all complete for borewell of: 23.13.2 150 mm dia |
| 169 | 23.14 Providing and fixing M.S. clamp of required dia to the top of casing/ housing pipe of tubewell as per IS: 2800 (part I), including necessary bolts & nuts of required size complete. 23.14.2 150 mm clamp |
| 170 | 23.15 Providing and fixing Bail plug/ Bottom plug of required dia to the bottom of pipe assembly of tubewell as per IS:2800 (part I). 23.15.2 150 mm dia |
| 171 | FIRE FIGHTING & FIRE ALARM SYSTEM: DSR 2021 (civil Work)/DSR (E & M) 202218.48 Providing and placing on terrace (at all floor levels) polyethylene water storage tank, IS : 12701 marked, with cover and suitable locking arrangement and making necessary holes for inlet, outlet and overflow pipes but without fittings and the base support for tank. |
| 172 | FIRE HYDRANT (A) Supplying, installation, testing and commissioning of electric driven terrace pump suitable for automatic operation and consisting of following, complete in all respects, as required: (Terrace Pump) (B) Horizontal type, multistage, centrifugal, split casing pump of cast iron body & bronze impeller with stainless steel shaft, mechanical confirming to IS : 1520 (C) Suitable HP squirell cage induction motor TEFC type suitable for operation on 415 volts, 3 phase, 50 Hz, AC supply with IP55 class of protection for enclosure, horiziontal foot mounted type with Class-'F' insulation, conforming to IS-325. (D) M.S. fabricated common base plate, coupling, coupling guard, foundation bolts etc. as required. (E) Suitable cement concrete foundation duly plastered and with anti vibration pads. 18.4.2 450 Ipm at 35 m Head |
| 173 | 18.7 Providing, laying, testing & commissioning of C class heavy duty MS pipe confirming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts, bolts, gasketsetc. And fixing the pipe on the wall/ceiling with suitable clamps/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required.18.7.5 65 mm dia |
| 174 | 18.7.6 80 mm dia |
| 175 | 18.7.7 100 mm dia |
| 176 | 18.9 Supplying and fixing single headed internal hydrantvalve with instantaneous Gunmetal/Stainless Steelcoupling of 63 mm dia with cast iron wheel ISI markedconforming to IS 5290 (Type -A) with blankGunmetal/Stainless Steel cap and chain as required :18.9.2 Single headed Stainless steel |
| 177 | 18.11 Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required : 18.11.5 100 mm dia |
| 178 | 18.13 Supplying and fixing orifice plate made out of 6 mm thick stainless steel (Grade 304) with orifice of required size to be fitted between flange & landing valve of external and internal hydrants to reduce pressure atthe outlet to the level of 3.5 kg/cm2 complete asrequired. |
| 179 | 18.13 Providing, installation, testing and commissioning of non-return valve of following sizes confirming to IS:5312 complete with rubber gasket, GI bolts, nuts,washers etc.as required :18.14.5 100 mm dia |
| 180 | 18.16 Supplying and fixing 63 mm dia, 15 m long RRL hose pipe with 63 mm dia male and female couplings duly bound with GI wire, rivets etc. conforming to IS 636(type-A) as required :certification (Two per each single landing valve ). 18.16.2 Stainless Steel (Grade 304) |
| 181 | 18.17 Supplying and fixing first-aid Hose Reel with MSconstruction spray painted in post office red, conforming to IS 884 complete with the following as required. 20 mm nominal internal dia water hose thermoplastic (Textile reinforced) type -2 as per IS: 12585 20 mm nominal internal dia gun metal globe valve & nozzle. Drum and brackets for fixing the equipmets on wall. Connections from riser with 25 mm dia stop gun metal valve & M.S. Pipe and socket.18.17.2 100 m |
| 182 | 18.18 Supplying & fixing 63 mm dia gun metal short branch pipe with 20 mm nominal internal diameter size nozzle conforming to IS 903 suitable for instantaneous connection to interconnect hose pipe coupling as required :18.18.2 Stainless Steel (Grade 304) |
| 183 | 18.19 Supplying and fixing of fire brigade connection of cast iron body with gun metal male instantaneous inlet couplings complete with cap and chain as reqd. for suitable dia MS pipe connection conforming to IS 904 as required :18:19:01 2 way-100 mm dia M.S. Pipe |
| 184 | 18.20 Supplying and fixing air vessel made of 250 mm dia, 8 mm thick MS sheet, 1200 mm in height with air release valve on top and flanged connection to riser, drain arrangement with 25 mm dia gun metal wheel valve with required accessories, pressure gauge and painting with synthetic enamel paint of approved shade as required. |
| 185 | FIRE ALARM SYSTEM17.2.1 Supplying, installation, testing and commissioning of microprocessor based intelligent addressable main fire alarm panel, central processing unit with the following loop modules and capable of supporting not less than 240 devices (including detectors) and minimum 120 detectors per loop and loop length up to 2 km, network communication card, minimum 320 character graphics/ LCD display with touch screen or other keypad and minimum 4000 events history log in the non volatile memory (EPROM), power supply unit (230 ± 5% V, 50 hz), 48 hrs back-up with 24 volt sealed maintenance free batteries with automatic charger. The panel shall have facility to connect printer to printout log and facility to have seamless integration with analog/digital voice evacuation system (which is part of the schedule of work under SH: PA System) and shall be complete with all accessories . The panel shall be compatible for IBMS system with open protocol BACnet/ Modbus over IP complete as per specifications.17.2.1.2 Two Loop Panel. |
| 186 | 17.2.3 Supplying, installation, testing & commissioning of repeater panel wih 320 character/ Touch screen LCD display with inbuilt reset, acknowledge and silence switches complete as required. |
| 187 | 17.2.4 Supplying, installation, testing & commissioning of intelligent analog addressable photothermal detector complete with mounting base complete as required. |
| 188 | 17.2.5 Supplying, installation, testing & commissioning of response indicator on surface/recessed MS Box having two LED, metallic cover complete with all connections etc as required. |
| 189 | 17.2.6 Supplying, installation, testing & commisssioning of intelligent addressable programmable sounder complete as required. |
| 190 | 17.2.7 Supplying, installation, testing & commissioning of fault isolator complete with base as required. |
| 191 | 17.2.9 Supplying, installation, testing & commissioning of intelligent addressable thermal detector with rate of rise cum fixed tempreature thermistor complete with base as required. |
| 192 | 17.2.14 Supplying, installation, testing & commissioning of addressable manual call point complete as required. |
| 193 | 17.2.15 Supplying, installation, testing & commissioning of addressable horn cum strobe complete as required. |
| 194 | 17.5 CABLING & WIRING17.5.2 Supplying & laying of 2x1.5 sqmm fire alarm armoured cable, 600/1000V rated with annealed copper conductor having XLPE insulation, steel wire armouring & FRLS outer sheath complete as required. |
| 195 | MCCB, MCB & DB'S2.2 Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required.'2.2.16 250 Amp, 36KA, FPMCCB |
| 196 | Non Schedule Item:Analysis Rate Supply and laying of following size PVC/XLPE insulated and PVC sheathed 1.1 KV Grade Solid Aluminium conductor up to 10 sq mm balance stranded conductor, XLPE Insulated, cores laid up, PVC tape inner sheathed, Armour1988 armoured U.G. cable U.G. cable laid in ground/partially in air (as required for termination over ground including excavation of cable trench up to depth of 75cm, refilling, protective brick covering, Sand cushioning etc complete handling of surplus spoil, debris et to proper place as specified and directed by the deptt.Analysis Rate 3 & 1/2 C 50 Sq MM |
| 197 | FIRE EXTINGUISHER:MR Supply, Installation, Fixing of ABC Stored Pressure Fire Extinguisher with built – In pressure Gauge to know the Ready ness of the Extinguisher Squeeze Grip Handle As per IS:13849 with ISI mark(6 kg capacity) BRAND : FIRESTOP / FIREND / FIRE SHIELD |
| 198 | MR Supply, Installation, Fixing of CARBON DIOXIDE Fire Extinguisher confirming to IS: 2878 with ISI Mark.(4.5 LITERS) BRAND: FIRESTOP / FIREND / FIRESHIELD |
| 199 | MR Supplying with fitting and fixing Hose cabinet as approved by the department |
| 200 | MR Supplying with fitting and fixing Terrace Pump Panel (Automatic Operation) as approved by the department Please Enable Macros to View BoQ information |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |
| 5 | Click here to download tender document | Tender Documents |
Copyright © 2026 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail