| 1 | WIRING POINTS AND ELECTRICAL FIXTURES |
| 2 | 1.10.1:Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVCinsulated copper conductor single core cable in surface / recessed medium class PVC conduit,with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLSPVC insulated copper conductor single core cable etc as required.Group A |
| 3 | 1.14.2:Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required2X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
| 4 | 1.17.3:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 X 1.5 sq.mm |
| 5 | 1.21.1:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm |
| 6 | 1.21.2:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.25 mm |
| 7 | 1.26:Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required. |
| 8 | 1.24.7:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.TV antenna socket outlet |
| 9 | 1.27.1:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.1 or 2 Module (75mmX75mm) |
| 10 | 1.33:Supplying and fixing 3 pin, 5 amp ceiling rose on the existing junction box/ wooden block including connection etc as required. |
| 11 | 1.58:Supplying and fixing PVC batten/ angle holder including connection etc. as required. |
| 12 | 1.17.20:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.2 x 4 sq. mm |
| 13 | 90.15.4.1:Supply Conveyance, installation, testing and commissioning of 20W LED street light output greater than 105lumen/W 4000-6000 K with IP 66 protection LED Chip make Cree/Lumilled/Nichea with power factor greater than 0.95 at full load, internal surge protection up to 8 KV,and Aluminium pressure die-cast Powder coated housing,acrylic cover complete with THD Less than10%, power factor greater than 0.98, RoHS compliant, duly wired up for use on 230 V AC supply. Driver compartment should be seperatly accessible for maintenance (LM 79&80 certificates from NABL accredited Third party lab to be produced mentioning chip manufacturer) |
| 14 | 90.3.18.2:Supply, fabrication, conveyance and fixing the following sizes of B class GI pipe bent to shape / cut and welded to shape and fixing the same to wall / parapet using clamps as noted along with each size, painting with 2 coats of synthetic enamel paint over a coat of zinc chromate primer, making good the damages, colour washing etc as required.32 mm dia with HG company fabricated clamps |
| 15 | OD52118/2026-2027:Supply and providing the following types and power-rated lamps in the existing angle holder / fittings as required. 8 W LED bulb |
| 16 | DB AND ITS ACCESSORIES |
| 17 | 2.10.1:Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, \\"\\"C\\"\\" curve, miniaturecircuit breaker suitable for inductive load of following poles in the existing MCBDB complete with connections, testing and commissioning etc. as required.Single pole |
| 18 | 2.13.1:Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps |
| 19 | 2.15.2:Supplying and fixing following rating, four pole, (three phase and neutral), 415volts, residual current circuit breaker (RCCB), having a sensitivity current 30milli Amperes in the existing MCB DB complete with connections, testing andcommissioning etc. as required.40 amps |
| 20 | 2.5.1:Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 volts, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 amps tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCB's (butwithout MCB's and incomer ) as required .(Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.)4 WAY(4+12), DOUBLE DOOR |
| 21 | Earthing system |
| 22 | 5.4:Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 23 | 90.16.1.2:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required2.65 mm copper conductor (12 SWG) |
| 24 | 90.16.5.2:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.2.65 mm (12 SWG) |
| 25 | 90.16.1.3:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required3.15 mm copper conductor ( 10 SWG) |
| 26 | 90.16.5.3:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.3.15 mm (10 SWG) |
| 27 | Cabling |
| 28 | 90.12.7.3:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.2 core 10 sq mm with factory made clamp |
| 29 | 90.12.7.41:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 16 sq mm with factory made clamp |
| 30 | 9.1.2:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.2 X 10 sq. mm (19mm) |
| 31 | 9.1.33:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 16 sq. mm (28mm) |
| 32 | OD52195/2026-2027: Supplying straight through joint with cast resin compound including ferrules andother jointing materials for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 2 X 10 sq. mm |
| 33 | Pumps and Accessories |
| 34 | 90.14.28.14:S & F Motor starters of the following ratingsSubmersible pump controllers with ammeter,TPMCB for three phase 5 to 7.5HP submersible motor pumps (DOL) |
| 35 | OD52166/2026-2027:Supply, Installation , Testing and commissioning of of 3.70 kw , 5 Hp, 38 stage Three phase Submersible bore well pump standard make and model with the following specification Pump Type (Installation) Submersible,Pump Type (Application),Power (In KW) 3.70, Power (In HP) 5.00, Delivery Size (in mm)38, Rated Voltage (Volts) 415, Speed (rpm) 2800, Phase 3, Frequency (in Hz) 50, No. of Stages 38, Product Dimensions Approximately 2695 x 226 x 226 MM;51 KG, Head Minimum (in m) 10,Head Maximum (in m) 296, Discharge Minimum 15 LPM, Discharge Maximum 90 LPM, Impeller Noryl, Motor Body Stainless Steel,Pump Shaft Stainless Steel, Sealing Oil Seal, Net Contents Pump set comprising 1 Pump, 1 Motor,op, good quality including required 3 Phase flat cable , rop, good quality HDPE Pipe & all other accessories except three phase starter for operation of 5 hp bore well pump Including all connection for operation of pump , hire charges, charges for tools and plants required for the works as per direction of Engineer in charge ( approximate depth 180 meter - 6 inch bore ) |
| 36 | Panel |
| 37 | OD52302/2026-2027:Fabrication, supply, conveyance, installation testing and commissioning floor /wall mounting, dust and vermin proof, cubicle type LV Metering panel board comprising of the following components/ devices complying to IS 8623.Fabrication of fully partitioned, dust and vermin proof enclosure for panel assembly using 1.6 mm POWDER COATED CRCA /GI sheet as per approved design and requirement 1.6 mm for frame , with front access facility, bus bar chambers with copper bus , hinged doors for all switch gear compartments and earthing the doors using braided copper conductor and providing danger notice board, LED indicator, feeder compartment lock, terminal block, PVC trunking, slotted channel, suitable connector, termination lug, copper wire if required, meter viewing glass if required etc. The board should be powder coating the assembly after subjecting to 7 tank process as required. 2 Nos Copper earth bar of size 25 mm x 3 mm at the rear with 2 No. earth stud. Angles/ flats/ slotted angles etc shall not be used for the fabrication of panel assembly. Insulated copper bus bar for phase of size 25X6, Insulated neutral copper bus of size 25 x 3. The panel Board should be fitted on the base frame for panel board using channels of class designation 75 including cutting,welding, drilling holes,painting two coats of synthetic enamel paint over a coat of zinc chromate paint bolting the frame to the panel and to the furnished floor using required bolts and nuts making good the damages colour washing and including providing and fixing the following switch gears etc as required.INCOMER 100AMP,4P Cubical Isolator -1 NO ,OUT GOINGS 63 AMP 4P MCB,- 1 No and 13 nos SP 40AMP 2 Pole MCB and including provision for required RCCB, Porcelain fuse, nutral link necessary requirements for metering panel with sealing provision. The charges for all control wiring, loading and unloading, testing and commissioning are included. The cable entry may be bottom or top as per direction of Engineer in charge, The Panel shall be Fabricated as per Electrical Inspectorate, KSEB, other relevant codes and standards( METERING PANEL NO I) |
| 38 | OD56463/2026-2027:Fabrication, supply, conveyance, installation testing and commissioning floor /wall mounting, dust and vermin proof, cubicle type LV Metering panel board comprising of the following components/ devices complying to IS 8623.Fabrication of fully partitioned, dust and vermin proof enclosure for panel assembly using 1.6 mm POWDER COATED CRCA /GI sheet as per approved design and requirement 1.6 mm for frame , with front access facility, bus bar chambers with copper bus , hinged doors for all switch gear compartments and earthing the doors using braided copper conductor and providing danger notice board, LED indicator, feeder compartment lock, terminal block, PVC trunking, slotted channel, suitable connector, termination lug, copper wire if required, meter viewing glass if required etc. The board should be powder coating the assembly after subjecting to 7 tank process as required. 2 Nos Copper earth bar of size 25 mm x 3 mm at the rear with 2 No. earth stud. Angles/ flats/ slotted angles etc shall not be used for the fabrication of panel assembly. Insulated copper bus bar for phase of size 25X6, Insulated neutral copper bus of size 25 x 3. The panel Board should be fitted on the base frame for panel board using channels of class designation 75 including cutting,welding, drilling holes,painting two coats of synthetic enamel paint over a coat of zinc chromate paint bolting the frame to the panel and to the furnished floor using required bolts and nuts making good the damages colour washing and including providing and fixing the following switch gears etc as required.INCOMER 100AMP,4P Cubical Isolator -1 NO ,OUT GOINGS 13 nos SP 40AMP 2 Pole MCB and including provision for required RCCB, Porcelain fuse, nutral link necessary requirements for metering panel with sealing provision. The charges for all control wiring, loading and unloading, testing and commissioning are included. The cable entry may be bottom or top as per direction of Engineer in charge, The Panel shall be Fabricated as per Electrical Inspectorate, KSEB, other relevant codes and standards( METERING PANEL NO I) Please Enable Macros to View BoQ information |