| 1 | PART-AWiring for light point/fan point/exhaust fan point/call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface/recessed medium class PVC conduit with modular type switch, phenolic laminated sheet suitable M.S. box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc. as required. Group A |
| 2 | Wiring for Twin Control light point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface/recessed medium class PVC conduit with modular type switch, phenolic laminated sheet suitable M.S. box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc. as required. Group C |
| 3 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required. |
| 4 | Supply and fixing suitable size GI box with modular plate and cover in front on surface on in recess, including providing and fixing 6 pin 5/6 & 15/16A modular socket outlet and 15/16 A modular switch, connections etc. as required |
| 5 | Supplying and fixing 20 A, 240 V, SPN Industrial type socket outlet, with 2 pole and earth, metal enclosed plug top along with 20 A \\"C\\" curve, SP, MCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required. |
| 6 | Supplying and fixing 20 A, 415 V, TPN Industrial type socket outlet, with 4 pole and earth, metal enclosed plug top along with 20 A \\"C\\" curve, TPMCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required |
| 7 | Supplying and fixing 30 A, 415 V, TPN Industrial type socket outlet, with 4 pole and earth, metal enclosed plug top along with 30 A \\"C\\" curve, TPMCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required. |
| 8 | Supplying and drawing of 1.5 Sqmm FRLS/HFFR PVC insulated copper conductor, single core cable in the existing surface/recessed steel/ PVC conduit as required for inverter wiring complete in all respect. |
| 9 | Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required 63 Amp. |
| 10 | Supplying and fixing of TP sheet steel enclosure on surface/recess for 63 Amp. 4 pole residual current circuit breaker (RCCB) complete in all respect. |
| 11 | Supply, Installation, Testing and Commissioning of ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos.metal(Aluminium alloy) blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, steel/Al body. Power Factor not less than 0.9, Service Value (CM/M/W) minimum as below, 350 RPM (tolerance as per IS : 374-2019), THD (Total Harmonic Distortion) less than 10%, remote (preferably mobile app based) for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 0C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC supply Ceiling Fan compliant to IS 374:2019 fan i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required. 1200mm, service value ≥ 6.0 CM/Min/Watt, airdelivery 210 CM/Min (Minimum) |
| 12 | Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 13 | Installation, Testing and Commissioning of exhaust fan in the existing opening, including making good the damage, connection, testing, commissioning etc. as required. Upto 450 mm sweep |
| 14 | LED Panel light 2x2 ft. (System lumen efficacy ≥105<120 lm/Watt) Supplying, installation, Testing & Commissioning of Panel light 2x2 ft., of following body material and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range -5 0C to 40 0C, internal surge protection of 2.5 KV with Short & Open circuit protection, THD < 10% , P. F.≥0.95, IP20, CRI >80, UGR (Unified Glare Rating) < 19, Flicker free, (flicker should be below 5 %), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with, 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K/6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. 45 watt |
| 15 | LED Down lighter (SMD Type) (System lumen efficacy ≥105 < 120 lm/Watt) Supplying, installation, Testing & Commissioning of LED Recessed/ surface Down lighter (Round/square/ Rectangular) COB Type of following body material and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range -5 0C to 40 0C, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P.F.≥0.95, IP20, CRI >80, UGR (Unified Glare Rating) < 19, Flicker free (flicker should be below 5%), lifetime (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K/ 5700°K / 6500°K (As per ANSI Bin), SDCM (Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be confirming to relevant BIS standards. 12 -15 watt |
| 16 | LED Batten light (System lumen efficacy ≥120 <135 lm/Watt) Supplying, installation, Testing & Commissioning of LED surface mounted Batten light of following body material and construction as per IS : 10322 with driver (Replaceable) as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range -5 0C to 40 0C, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P.F.≥0.95, IP20, CRI >80, Flicker free (flicker should be below 5 %), lifetime (LED,Driver & electrical circuitry), of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K /6500°K 46 DELHI SCHEDULE OF RATES (E&M)-2025 (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. 18- 22 Watt |
| 17 | Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. |
| 18 | 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire |
| 19 | 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
| 20 | 2 X 4 sq. mm + 1 X 4 sq. mm earth wire |
| 21 | 2 X 6 sq. mm + 1 X 6 sq. mm earth wire |
| 22 | 4 X 6 sq. mm + 2 X 6 sq. mm earth wire |
| 23 | 4 X 10 sq. mm + 2 X 6 sq. mm earth wire |
| 24 | 4 X 16 sq. mm + 2 X 6 sq. mm earth wire |
| 25 | 11.1 Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed/XLPE aluminium conductor cable of 1.1 KV grade as required. |
| 26 | 2 X 16 sq. mm (22mm) |
| 27 | 3½ X 50 sq. mm (35mm) |
| 28 | 3½ X 95 sq. mm (45mm) |
| 29 | 3½ X 185 sq. mm (57mm) |
| 30 | 3½ X 400 sq. mm (82mm) |
| 31 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 32 | Single pole |
| 33 | Double pole |
| 34 | Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 35 | 40 Amp. 4 pole RCCB |
| 36 | 63 Amp. 4 Pole RCCB |
| 37 | 6 to 32 Amp. TPMCB |
| 38 | 63 Amp. TPMCB |
| 39 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 40 | 8 way, Double door |
| 41 | 12 way, Double door |
| 42 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator). |
| 43 | 4 way (4 + 12), Double door |
| 44 | 6 way (4 + 18), Double door |
| 45 | 8 way (4 + 24), Double door |
| 46 | Supplying and fixing of following ways surface/recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer ) as required . (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.) |
| 47 | 8 way (4 + 24), Double door |
| 48 | Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, Ics=100% Voltage 690V etc. as required. Icu and Operational Voltage 690V etc. as required. |
| 49 | 100 A,30KA,FPMCCB |
| 50 | 200 A,36KA,FPMCCB |
| 51 | 400 A,50KA,FPMCCB |
| 52 | Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 Meter long etc. (but without charcoal/ coke and salt) as required. |
| 53 | Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 Meter long etc. with charcoal/coke and salt as required. |
| 54 | Providing and fixing earth strip of 50 mm X 5 mm copper strip on surface for connections etc. as required. |
| 55 | 5.9 Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm) |
| 56 | Supply and fixing of Recess/pendent mounting having Size 36 to 46 Watt seamlessly integrated LED luminaire with High purity/transmissivity UV Stabilized Non yellowish diffuser/ Reflector for uniform light distribution, integral/detachable driver set, open and short circuit protection, suitable for 24 Hr Continuous Operation, Complete in All respect. 1 ft.X4ft.4320-5520 system lumens, >120 Lm/W, PF>0.95, THD< at full load, CRI >80, 300V over voltage protection, 4 KV internal Surge Protection, with 5 years warrantee |
| 57 | Supplying, Installation, Testing & Commissioning of Street light LED fixture of 90 watt powder coated pressure die cast aluminium body with built in or separate driver as per the requirement with Driver efficiency >85%, Input voltage: 140-270 Volt AC, frequency 50/60 hz, Operating temp range -5 0C to 50 0C, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2, P. F.≥0.95, IP-66,IK-10, CRI >70, under voltage and over voltage protection, EMI-EMC as per CISPR-15, lenses for beam angle as per IESNA type I/II/III as per the width of the road and the project requirement., suitable to fit in up to 65mm dia pipe, life time (LED,Driver & electrical circuitary) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy >135 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted.. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). |
| 58 | Supply & fixing of water tight oblong 10 watt LED Bulkhead luminaire having pressure die cast housing with driver set conforming to IP65 and above protection, IK 03, High purity/ transmissivity UV Stabilized Non yellowish diffuser/ for uniform light distribution detachable, driver set, open and short circuit protection, suitable for 24 Hr Continuous Operation, Complete in All respect complete in all respect1100 system lumens, >110 Lm/W, PF>0.95, CRI >70, with 3 years warrantee |
| 59 | Supply and laying of aluminium conductor PVC insulated armoured served sheathed cables 1100 Volts grade at a depth of 750 mm below ground level over a cushion of 75 mm. thick sand all around and protected with burnt bricks on sides and on top. On surface the cable run shall be fixed on M.S. clamps etc. of suitable size or as directed by the Engineer-Incharge, complete in all respect. The armouring of the cable shall be properly connected with the earth conductor by clamps etc. |
| 60 | 16 sq. mm 2 core |
| 61 | 50 sq. mm 3.5 core |
| 62 | 95 sq. mm 3.5 core |
| 63 | 185 sq. mm 3.5 core |
| 64 | 400 sq. mm 3.5 core |
| 65 | Supply of Fresh Air Fan 300mm Sweep metalic |
| 66 | Supply of Fresh Air Fan 450mm Sweep metalic |
| 67 | Shock Treatmnent Chart |
| 68 | Supply & fixing of CO2 type fire extinguisher, 4.5 kg. capacity (ISI Marked IS:2878 & TAC approved) comlete with initial charge and wall bracket, along with supply of all materials and labour for proper completion of work. |
| 69 | Supply & fixing of fire extinguisher, ABC Type 4.00 kg. capacity (ISI Marked IS:15683 & TAC approved) comlete with initial charge and wall bracket, along with supply of all materials and labour for proper completion of work. |
| 70 | Fire Bucket |
| 71 | S/F of Computer Board with 3 Nos. 5 Amp. Switch & socket and 15 Amp. Switch & socket complete in all respect |
| 72 | Rubber Matting (1800x900x12)MM |
| 73 | Danger Board |
| 74 | Dismentling of Old Wiring and deposit to store |
| 75 | Shifting of 6 Nos. Pannel Board from Old place to New place |
| 76 | Supplying and installaton following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with two numbers MS/GI Suspenders i/c base of suitable size MS/GI angle, bolts & nuts, painting suspenders, fastener etc as required. |
| 77 | 750 mm width X 75 mm depth X 2.0 mm thickness |
| 78 | Supplying and installation following size of perforated painted with powder coating M.S. cable trays bends with perforation not more than 17.5%, joined with connectors, suspended from the ceiling with two numbers MS/GI Suspenders i/c base of suitable size MS/GI angle, bolts & nuts, painting suspenders, fastener etc as required. |
| 79 | 750 mm width X 75 mm depth X 2.0 mm thickness |
| 80 | PART-B Repairing Servicing of 8 zones fire alarm main panel microprocessor based with public addess system in complete in all respect. |
| 81 | Repairing Servicing of 4 zones fire alarm main panel microprocessor based complete in all respect. |
| 82 | Supplying, installation, testing & commissioning of smoke detector with builtin LED and mounting base complete with all connections etc. as required. |
| 83 | Servicing Cleaning of Smoke detector as per specification including making connections with wires. |
| 84 | Supplying, installation, testing & commissioning of manual call box of ABS type in surface/recess with assembly complete with glass and push button etc. as required. cement concrete blocks as supports, anticorrosive treatment with coaltar/asphalt tape as per IS 10221, refilling the trench etc. of following sizes complete as required. |
| 85 | Supply and replacement with laying, testing & commissioning of 'C' class heavy duty MS Pipe conforming to IS 1239/3589 i/c fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. in ground including welding, excavation & providing cement concrete blocks as supports, anticorrosive treatment with coaltar/asphalt tape as per IS 10221, refilling the trench etc. of following sizes complete as required. |
| 86 | 100 mm Dia |
| 87 | 80 mm Dia |
| 88 | 25 mm Dia |
| 89 | Supplying, fixing, testing & commission of butterfly valve of PN-1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required. |
| 90 | 100 mm dia |
| 91 | 80 mm dia |
| 92 | Providing, installation, testing and commission of non-return valve of following sizes PN-10 as per design standerd IS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc.as required: |
| 93 | 100 mm dia |
| 94 | 80 mm dia |
| 95 | Supplying and fixing first-aid Hose Reel with MS construction spray painted in post office red, conforming to IS 884 complete with the following as required. 20 mm nominal internal dia water hose thermoplastic (Textile reinforced) type -2 as per IS: 12585. 20 mm nominal internal dia gun metal globe valve & nozzle. Drum and brackets for fixing the equipmets on wall. Connections from riser with 25 mm dia stop gun metal valve & M.S. Pipe and socket. |
| 96 | 30 mm |
| 97 | Dismantling and replacement with supply of rubber hose reel 19 mm internal dia 30 m length red in color with thread reinforcement complete in all respects. |
| 98 | Supplying Installation testing & Commissioning of 25 mm Air Release valve gunmental having rubber ball and with 25 mm BSP threaded male inlet including necessary accessories and connections complete in all respect. |
| 99 | Supplying Installation testing & Commissioning of SS/GM/Ball Valve 25 mm dia complete. |
| 100 | SITC of Hose Box of 18 SWG MS Sheet with glass fronted door to accommodate 2 nos. RRL hose & 1 no. SS Branch Pipe with nozzle (External/ Internal) Size 800x600x400 |
| 101 | painting of all existing pipe line, Box, Pump house pipe line with the two coat ISI Red Paint and primeretc. |
| 102 | Supplying and fixing 63 mm dia, 15 m long RRL hose pipe with 63mm dia male and female couplings duly bound with Gl wire, rivets etc. conforming to IS 636 (type-A) as required : |
| 103 | Stainless Steel |
| 104 | Supplying & fixing 63 mm dia gun metal short branch pipe with 20 mm nominal internal diameter size nozzle conforming to IS 903 suitable for instantaneous connection to interconnect hose pipe coupling as required: |
| 105 | Stainless Steel (Grade 304) |
| 106 | Supply Installation testing and commissioning of Pressure Gauge complete in all respects. |
| 107 | Supplying and fixing of fire brigade connection of cast iron body with gun metal male instantaneous inlet couplings complete with cap and chain as reqd. for suitable dia MS pipe connection conforming to IS 904 as required : |
| 108 | 2 way - 100 mm dia M.S. Pipe |
| 109 | Supplying Laying testing & Commissioning of 2 corex 1.5 sq.mm single standard copper conductor, PVC insulated armored cable. |
| 110 | Providing & fixing of pressure switch in M.S. pipe line including connection etc. as required. |
| 111 | Supplying and fixing single headed hydrant valve with instantaneous Gunmetal/Stainless Steel coupling of 63 mm dia with cast iron wheel ISI marked conforming to IS 5290 (Type -A) with blank Gunmetal/ Stainless Steel cap and chain as required : |
| 112 | Single headed Stainless steel |
| 113 | Servicing and maintenance of old fire electric motor and pump of 60 HP capacity with opening of motor and varnishing of its winding, changing of its bearing and other small parts; opening of pump and changing of its bearing, rubber gasket, painting of motor and pump complete in all respect. |
| 114 | Servicing and maintenance of old fire diesel engine and pump 63 HP with servicing, changing of mobile oil, filter etc, changing of bearing and other small part, Cleaning and painting of engine set complete in all respect. |
| 115 | Servicing and maintenance of old Jockey motor 10 HPand pump with opening of motor and its varnishing, changing of bearing. Opening of Jockey Pump and changing of its gasket, bearing, painting of pump etc complete. |
| 116 | Servicing and maintenance of old fire fighting panel with changing of main incoming switch, repairing and changing of wiring of panel, changing of Ammeter, voltmeter, indicating lamp, required relay, etc & painting of panel complete in all respect. |
| 117 | SITC of 100 MM CI Foot Valve complete with nuts, volts washers complete in all respect. (Make- Kalpana/ Kartar/Sir) |
| 118 | Refilling of ABC type fire extinguisher 4 kg Capcity. |
| 119 | Refilling of CO2 type fire extinguisher 4.5 kg Capcity. |
| 120 | PART-C Design, manufacture, supply, installation, testing and commissioning of 11kV/0.433kV, 630KVA Transformer 3 phase, 50 Hz delta/star connected, outdoor, oil filled, ONAN type transformer, complete with all fittings such as marhslling Box thermometers (OTI), WTI, Buchholz relay, Off Load Tapp Changer with + 5% to- 12.5%, tapping at the step of 1.25% bi-directional roller, diagrams & rating plate & Winding temperature indicator, oil temperature indicator, lifting lugs, H. T. cable box/ LT Cable Box suitable for Termination of Cable. transformner shall confirm to Latest IS: 1180 Energy Efficiensy Level-I latest amendmend. The Job Includes the Shifting of Transformer up to the Installation Place, and Installation of on Plingth including fixing of all parts of Transformer ie Finges Conservator Tank, Bucholz Relay, Silica Gel Breather, HT Cable BoxLT, Cable Box etc. The Job also includes the filling of Transformer Oil after Proper Oil Filtration and checking of BDV to meet the result as 60KV. The job Includes of making of suitable Trench with Labour Tools & Tackles etc. |
| 121 | Supply Installation Testing & Commissioning of 11 KV, 630A, 21KA for 3sec, SF6 insulated, Manual Outdoor, Non extensible RMU , type tested in line with latest IEC standards. The switchgear and busbar shall all be contained in a stainless steel enclosure filled with SF6 at 0.3 bar (300 hPa) relative pressure. The RMU tank shall provide full insulation, making the switchgear insensitive to the environment with degrees of protection of IP67 . The switchgear operating mechanism shall have an IP2X protection and cable chamber shall have IP54. The outer enclosure should be IP 55 type tested, should be powder coated with pure polyester based paint , suitable for the site installation condition. Internal Arc Type Test Report for IAC AFLR 21 kA for 1 sec for both tank & cable box should have been for minimum 3 way / 3 Function RMU.The Encosure of CSS shall be manufactured with 2.0/1.6 mm thick CRCA/GI sheet steel. The Outer Structure & Load bearing members shall be 2.0mm Thick sheet & Inneer partitions & Covers shall be 1.6mm hick sheet, duly painted with Epoxy based Powder coated paint of shade as per customer requirement or as per our standard shade. The CSS shall be suitable for outoor Installation for which necessary shed canopy shall be provided. The CSS shall be completed in all respetct & shall consist of following :- |
| 122 | 11kV 3 Way Ring Main Units : Each of the above Ring Main Unit shall comprise of the followings : Incoming Vaccum Circuit Breaker – 1 set each consisting of :A. 11 KV, 630A, 21KA for 3sec Manual VCB with spring assisted mechanism and series trip coil; with builtin manual line side three position disconnector cum earth switch. The circuit breakers shall have 2 positions: open or disconnected and closed 1 No. B. Self powered relay with O/C , E/F protection. Relay should have LCD display, fault records with time stamp – 1No. C. Live cable indicator with indications (Voltage Presence Indicator) - 1 set D. Cable box with termination bushing suitable for upto 2 RUN 3Cx300 Sq mm, XLPE cable -1 set E. Emergency trip push button F. PT Module along with Multifunction Metering – 1 setOutgoing Vaccum Circuit Breaker – 2 set each consisting of :A.11 KV, 630A, 21KA for 3sec Manual VCB with spring assisted mechanism and series trip coil; with built in manual line side three position disconnector cum earth switch. The circuit breakers shall have 2 positions: open or disconnected and closed 1 No. B. Self powered relay with O/C , E/F protection. Relay should have LCD display, fault records with time stamp along with Common connection for Transformer Fault Trip– 1No. C. Live cable indicator with indications (Voltage Presence Indicator) - 1 set D. Cable box with termination bushing suitable for upto 2 RUN 3Cx300 Sq mm, XLPE cable -1 set E. Emergency trip push button |
| 123 | Design manufacturing & Supply of 1250A Outdoor LT Panel. The Panel shall be fabricated out of 2.0mm thick CRCA sheet steel, painted with Powder coated paint of shade as per the direction of Engineer In-Charge after proper sheet treatment process of sheet steel. The Panel shall be suitable for Outdoor Installaion with Degree of protection IP:55. The Busbar of Feeder Pillar shall be of High grade Electrical grade High Conductive Aluminum alloy of appropriate cross section as per rating. The calculation of continuous rating of Bus Bar shall be submitted. The Bus Bar shall be supported by non hygroscopic SMC/DMC Bus Bar supports which shall be mounted on proper interval to ensure bear the jerks of short Circuit as fault level require. The Fault level of Panel shall be 35kA for 1sec. All Indicating Lights shall be LED type and all wiring shall be done from PVC Insulated copper flexible wire. The Panel shall be completed in all respect and shall consist of following material. Incomer: 1250A FP, 50kA Manually Operated Drawout Type ACB with Microprocessor Based O/L, S/C & E/F Release 2 SetBus Coupler: 1250A FP, 50kA Manually Operated Drawout Type ACB-1 SetInterlocking: Both Incomer & Bus Coupler shall be Mechanically Interlocked so that any 2 Breakers out of 3 shall be ON at a time - 1 setMetering (Incoming): Multifunction Meter showing all Electrical Parameter, Phase Indicating Lights, On/Off/ Trip Indicating Lights Current Transformer, Control MCB etc.- 2 Sets Outgoing: 1250A TPN Bus Bar with Phase Indicating Lights - 2 Set (TTA Pannel) |
| 124 | Supply and laying of aluminium conductor PVC insulated armoured served sheathed cables 1100 Volts grade at a depth of 750 mm below ground level over a cushion of 75 mm. thick sand all around and protected with burnt bricks on sides and on top. On surface the cable run shall be fixed on M.S. clamps etc. of suitable size or as directed by the Engineer-Incharge, complete in all respect. The armouring of the cable shall be properly connected with theearth conductor by clamps etc. 400 sq. mm 3-1/2 core |
| 125 | Supply and laying of 3 core standered aluminium conductor XLPE (Cross linked polyethylene) insulated PVC bedded, Galvanised flat steel strip armoured cables confirming to I.S. 7098 (Part-II with latest amendments) II KV grade at a depth of 900 mm below ground level over a cushion of 100 mm thick fine river sand all around and protected with well burnt bricks on sides and on top put across. The armouring of cable shall be properly connected with earth conductor by clamps etc.120 sq. mm 3 core |
| 126 | Cable Jointing kit indoor 11 KV3C X 120sq mm |
| 127 | Cable Jointing kit Outdoor 11 KV3C X 120sq mm |
| 128 | Charges for demolishing of floor, shifting of floor debris and making of cable trench including all Civil material, MS Channel support (Size 100X75X6), Labour T&P, etc. The whole work is to be executed as per direction of E-in-charge |
| 129 | Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 Meter long etc. (but without charcoal/ coke and salt) as required. |
| 130 | Providing and fixing earth bus of 50 mm X 5 mm copper strip on surface for connections etc. as required. |
| 131 | TOTAL RS. |
| 132 | Less 5% Please Enable Macros to View BoQ information |