| 1 | Supply, Installation, Testing& Commisioning of Microprocessor based addressable OPC complied fully networkable fire alarm 2 loop control panel ( VDS/UL/LPCB/FMapproved) suitable for the device sasstatedin heprevious items of this BOQ along with 20% sparecapacitywith eachlooploadingnotexceeding80%ofthefullcapacityofdetectors and devices taken together, conplying to IS 2189:2008 or its latest amendments,andwithminimum320characteralpha-numericliquidcrystaldisplay.Thepanelshallbesoftaddressabletypeand shall be able to give pin point location of all fire/ fault conditions.Further, the panel must be able to automatically switch off respective control switches with help monitor modulewhenever any alarm is triggered.ThePanelshouldbeableto storeminimum 4000logevents in its memory (EPROM). The panel should have extra loop card slot for future expansion. |
| 2 | The panel shall have in built rectifier, provision for external & internal printer ( if required ), Loop cards, LCD unit to indicate Fire/Fault Signal with address and analog output, complete in all respects, in built Surge protection facility, integral SMF lead acid batteries with sealed cells of 24 V capable of running for 24 hours normal working and then be capable of operating the system for 30 minutes during Emergency condition, with integral battery charger complete in all respect as required. |
| 3 | The FACP shall be capable of being networked (future expansion) with other similar FACP located at different part of the premises through single RS 485 bus.The FACP shall have provision for interfacing with the public address system, remote computer and BMS interface. The system must be preloaded with licenced software. (Approved Make: Esser/Cerberus Pro/Bosch/Johnson Controls/Notifer / Edward /Secutron Securiton/Apollo / Morley /System sensor) |
| 4 | NOTE : 1. The Fire Alarm system shall comply with latest requirements of -- 2. National Fire Protection Association (NFPA) Standards IS:2189.3. NFPA 70 National Electric Code.4. NFPA 72 National Fire Alarm & Signaling Code.5. Local Statutory Regulations.6. Manufacturer Recommendation. |
| 5 | TESTS:1.The system shall be tested and commissioned by a qualified competent,trained engineer or technician authorized by the manufacturer of the fire alarm equipment to technically supervise and participate during all of the adjustments and tests for the system.2. Before energizing the cables and wires, check for correct connections and test for short circuits, ground faults, continuity, and insulation and other tests as per above standards must be done.3. The Commissioning Manuals, Tools, Dongles, USb Token, Software, or whatever is required for the Commissioning of the FACP, in whatever name it called must be handed over to the EIC, along with the passwords of the panel. |
| 6 | DETECTOR, INDICATOR, HOOTER & CALL POINT |
| 7 | Supply,Installation,Testing & Commisioning of Micropresssor controlled Addressable Multisensor detector(VDS/UL/LPCB/ FM approved ) withinbuilt optical smoke sensors and heat detector sensor with inbuilt short circuit fault isolator as per NFPA(Note : Detectors without built-in fault isolator is also acceptable withone independent short circuit fault isolator after every four (04) detector isto be provided without extra cost) the detectors should have built in response indicator with LED indicator. The detector should have 360 degreeopticalviewwithsingle/multipleLEDthatblinkson actuation of detector. Reverse polarity or faulty zone wiring shall not damagethedetectors.DegreeofprotectionasperOEMStandard. (Approved Make: Esser/Cerberus Pro/Bosch/Johnson Controls/Notifer / Edward /Secutron Securiton/Apollo / Morley /System sensor) |
| 8 | Supply, Installation, Testing & Commisioning of addressable Manual Call Point (VDS/UL/LPCB/FM approved) withinbuilt short circuit fault isolatoras per NFPA (Note : MCP without built-in fault isolator is also acceptable withone independent short circuit fault isolatoris to beprovided withoutextra cost).Degree ofprotection as per OEM Standard.(Approved Make: Esser/Cerberus Pro/Bosch/Johnson Controls/Notifer / Edward /Secutron Securiton/Apollo / Morley /System sensor) |
| 9 | Supply, Installation, Testing& Commissioning of Addressable Loop Powered /panel poweredHooter(sound output of minimum 90 db )cum strobe (strength of light 10 cd) complete with inbuilt short circuit fault isolator as per NFPA (Note:Hooterwithoutbuilt-infaultisolator is also acceptable with one independent short circuit fault isolatoris to be provided without extracost).(VDS/UL/LPCB/FMapproved)approved.DegreeofprotectionasperOEMStandard. (Approved Make: Esser/Cerberus Pro/Bosch/Johnson Controls/Notifer / Edward /Secutron Securiton/Apollo / Morley /System sensor) |
| 10 | Supply, Installation,Testing& Commisioning of Micropresssor controlle dAddressable Heat detector (VDS / UL / LPCB / FM approved) with combination of fixed type& Rate of Rise of Temperature feature. Detector shall have minimum triggering temperature programmable from 58 deg. C to 68 deg. C., having high level of immunity to electromagnetici fluancesandshowalarmsignal limit temperature is reached. Detector shall have inbuilt short circuit fault isolator as per NFPA(Note : Detectors without built-in fault isolator is also acceptable withone independent short circuit fault isolator after every four (04) detector in the loopis to be provided without extra cost) the detectors should have built in response indicator with LED indicator.Degree of protection as per OEM Standard. (Approved Make: Esser/Cerberus Pro/Bosch/Johnson Controls/Notifer / Edward /Secutron Securiton/Apollo / Morley /System |
| 11 | INTERCONNECTION |
| 12 | Supplying & laying of 2x1.5 sqmm FRLS shielded copper Conductor stranded cables in red/black color and generally confirming to IS-694-2010 and meet the signal cabling requirements (Make-Havells/Finolex/Polycab/Gloster/KEI as approved by E.I.C) |
| 13 | Supplying and fixing 20 mm PVC Rigid Conduit 'FR' [Precision Make] of following sizes on wall, ceiling with saddles and other accessories as required and mending good damages to building works [E-16/7(a)] |
| 14 | TERMS & CONDITIONS |
| 15 | The Agency must procure the materials from the Manufacturer / OEM or from their authorised sales channel so that the standard warranty / support of the Manufacturer / OEM becomes applicable to the products to be delivered and installed by them. |
| 16 | Documents that authenticates such procurement from the Manufacturer / OEM or from their authorized sales channel and standard warranty / support should be sent from the e-mail of the Manufacturer / OEM / authorized sales channel to the e-mail of Engineer-in-Charge and hard copy of it to be submitted during execution, of work/submission of bill. |
| 17 | If any refurbished material is supplied and installed, penal action will be taken as per existing rules. |