| 1 | Material and Labour for point wiring using approved colour coding as per IS ( Red, black and green for single phase circuits), with multi stranded copper conductor 1.5 Sqmm nominal cross sectional area,single core, PVC insulated and sheathed FRLS cable1100 volts grade , ISI-694 (1990) marked with valid CML No in and including medium grade,PVC casing & capping of suitable size on walls/roof/floor etc, ISI marked with suitable accessories , PVC box including Modular Plate and Covers for one Fan/Light/bell point controlled by one switch/bell push complete all as specified and directed by engr in charge.Make: Polycab /Finolex/ RR |
| 2 | Material and Labour for point wiring using approved colour coding as per IS ( Red, black and green for single phase circuits), with multi stranded copper conductor 1.5 Sqmm nominal cross sectional area,single core, PVC insulated and sheathed FRLS cable1100 volts grade , ISI-694 (1990) marked with valid CML No in and including medium grade,PVC casing & capping of suitable size on walls/roof/floor etc, ISI marked with suitable accessories , PVC box including Modular Plate and Covers for one 5 Amps socket on Independent board controlled by one switch complete all as specified and directed by engr in charge.Make: Polycab /Finolex/ RR |
| 3 | Supply and fix modular switch 1 way 6A 1 module complete all as specified and directed. |
| 4 | Supply and fix modular socket 6A 2/3 pin combined 2 module complete all as specified and directed. |
| 5 | Supply and fix modular socket 16A 2/3 pin combined 2 module complete all as specified and directed. |
| 6 | Supply and fix modular switch 1way 16A 1 module complete all as specified and directed. |
| 7 | Supply and Fix wall study lamp LED bush light with die cast aluminium housing with toughned glass 6 watts including necessary eletric connection with PVC insulated multistranded copper cable of suitable size from ceiling rose/junction box to fitting terminal complete all as specified and directed. |
| 8 | Material and Labour for point wiring complete with 1.5 Sqmm single core FRLS PVC insulated unsheathed cable 1100 V grade multi stranded copper conductor drawn through non metallic rigid PVC conduit and accessories in surface of walls/ceilings including 1.5 Sqmm dia multistranded copper cable as earth continuity conductor connected to common earth dolly, including PVC boxes of suitable size/thickness to provision of Modular switches to house switch/regulators etc including Modular Plate and Covers for one fan/light /bell point controlled by one switch/bell push complete all as specified and directed.Note :-(i) The work is to be carried out in bldg at a height upto 7 mtrs (Approx). (ii) The cost of T&P involved in doing the wiring work is included in the quoted cost.(iii) The contractor has to visit the site and check the site conditions before quoting the tender. |
| 9 | All as per item No 8 above for one 3 pin 5 Amps socket on same board controll with other switches on same board |
| 10 | All as per item No 8 above for one 3 pin 5 Amps socket on independent board |
| 11 | All as per Item No 8 here-in- before but with 2.5 Sqmm PVC insulated multistranded copper conductor with 2.5 sqmm cable as earth continuity conductor for Power Socket on independent board complete all as specified and directed. |
| 12 | All as per Item No 8 here-in- before but with 4 Sqmm PVC insulated multistranded copper conductor with 4 sqmm cable as earth continuity conductor for AC/Geysers on independent board with suitable size of casing & caping medium grade complete all as specified and directed. |
| 13 | Supply and fix Modular fan regulator 120 watts 2 module complete all as specified and as directed. |
| 14 | Supply and fix ceiling rose surface bakelite with three terminals complete all as specified and directed. |
| 15 | Supply and fix LED fitting for Bldg security, 35 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65 / 66 protection complete. including conncting with 1.5 sq mm copper conductor 3 core flexible cable from fitting connector to ceiling rose and fix on wall with clamps & nut bolts and necessary GI bracket made of 32 mm dia light grade GI pipe of 1 mtr lenth with necessary bending complete all as specified and directed . Make : Jaquar/Halonix/Philips/Havells . |
| 16 | Supply and fixing LED lights fitting 1x 22W, 220V,AC, decorative box type with driver, holder incl LED type light connecting up with flexible copper conductor cable of suitable size from ceiling rose complete all as specified and directed. Make : Jaquar/Halonix/Philips/Havells . |
| 17 | Supply and Fix wall/ceiling mounted LED tube light fitting aluminium body , Energy efficient high quality invertor batten having Lithium ion battery of 3.7V, 19 WH for backup upto 2Hrs with high power brightness having BIS certification, LED fitting should be LM 80 certified with system efficacy greater than 100 lumens/watt, including LED tube 22 watt having colour temperature 6500 K (4 feets long) , PF> 0.95, THD less 10%, with IP20 protection having open and short circuit protection, having input voltage range 90V to 300V connecting with flexible copper wire of suitable size from connector to ceiling rose/angle holder as per existing site requirement as directed by Engr-in-charge. Make : Jaquar/Halonix/Philips/Havells . |
| 18 | Supply and Fix Recess mounting LED flat panel light fitting of size 600mmX 600mm of wattage 40 watts with efficient LEDs lumen 2000 to 3000, PF> 0.9, THD less 15% fabricated CRCA sheet steel housing (70mm) duly powder coated with high efficient LEDs & glare free full opal diffuser with system efficacy of 120lm/W complete all as specified and directed. Make : Havells/wipro/Halonix |
| 19 | Material and Labour for submain wiring in PVC conduit with two runs of 6 sq mm and one runs of 6 sqmm for earth continuity 1100 v grade PVC insulated unsheathed FRLS grade copper conductor cable single core multistranded ISI marked (IS 694) drawn through and including 25 mm dia PVC rigid conduit heavy grade ISI marked (IS 9537 Part III) includung accessories such as bends, supports etc all as specified and directed. Note: Two runs of 6 sq mm and one runs of 6 sqmm cable along with conduit shall be measured as one length. |
| 20 | Supply and Fix MCB DB SPN 12 way double door type horizontal with 200A busbar including disconnecting from mains and making good the disturbed surfaces complete all as specified and directed. |
| 21 | Supply and Fix MCB SP of capacity 5A - 32A \\"B' curve all as specified and directed. |
| 22 | Supply and Fix MCB, SPN (Double Pole) 32 amps, 240 Volts, 10 KA ‘’C” curve all as specified and directed. |
| 23 | Taking down unservicable earthing and Material and Labour for earthing complete in repairs with galvansihed steel earth plate electrode 600 mm x 600 mm x 6 mm thick buried directly in ground (earth pit not less than 2.25 mtr deep below ground level) with top edge of plate not less than 1.5 mtr below normal ground level connected to 4.0 mm dia galvansihed earth lead wire by means of nuts bolts check nuts and GI washers including PCC pit in PCC 1:2:4 type B-1 (20mm graded stone aggregate) RCC cover 20 mm dia (medium grade) GI watering pipe with funnel wire mesh and protection pipe of GI of suitbale size upto 7.5 mtr length including charcoal black cotton soil as required at site to achieve the earthing result and common salt, excavation earth work etc in any type of starta complete all as shown in electrical plate No 3 as specified, GI wire suitable size and length for continuity earth wire from test point to main distribution Board and all as directed. (Note: (i) Rate for achieving required depth by compressor machine if required is deemed to be included in item unit rate. |
| 24 | Supply and fixing in repair ceiling fans complete with blades, down rods, electronic regulator and accessories, 230 V, 1200 mm sweep. Min air delivery 210 CFM with service value 6.00 BEE. Five star rated with brushless direct current motor (BLDC) and depositing old ceiling fan to MES store complete all as specified and as directed.Make : USHA/Halonix/Philips/Havells .Note :- The cost is inclusive of down rod of ceiling fans of length upto 3 mtrs.including necessary fabrication work for fixing MS clamps. |
| 25 | Supply and fixing single pole and neutral enclosure with a two pin and earth plug and socket complete with 20 Amp DP MCB all as specified and directed.(for AC) |
| 26 | Material and Labour for Precast cement concrete block masonry type C1 1:3:6 (20mm graded aggregate) with solid blocks, exc. 10cm in width and, setting in cement mortar 1:6 complete all as Specified. |
| 27 | Material and Labour for rendering 15mm thick in CM 1:6 on fair faces of brick work or concrete surfaces finished even and smooth (without using extra lime or cement) complete all as specified and as directed. |
| 28 | Material and Labour for 10mm thick PVC insulated panels 600x600mm with EPS stuck to 1mm printed PVC sheet suitable placed in and including flase ceiling grid made of GI frame work for seamless ceiling comprising of GI perimeter channel 0.55 mm thick with two unequal flanges of 20 and 30 mm and web 27 mm fixed to surrounding wall using nylon sleeves and screw at 450 mm centre to centre/intermediate channel 0.9 mm thick having two equal flanges of 15 mm each and web of 45 mm suspended from soffit at approx. 900 mm centre to centre with GI cleat and steel expansion fasteners with and including ceiling section (not exc 1.2 mtr length) of 0.55 mm fixed to the intermediate channel with connecting clips across the intermediate channel with connecting clips across the intermediate channel at 457 mm centre ot centre. Hangers 6 mm dia. GI (upto 1200mm length) adjusting level fixed to roof slabs by means of ceiling cleats made out of G.I. Flat 40x3mm size 60mm long and expansion hold fasteners 12.5mm dia. 40mm long complete all as specified. |
| 29 | Material and Labour for Preparation of new or untreated plastered surfaces of wall and applying two coats of oil bound distemper of approved colour and pattern over a coat of primer finished even and smooth complete all as specified. |
| 30 | Material and Labour for complete removal of existing finishes , preparation of old surfaces and applying two coats of oil bound distemper on walls over a coat of alkali resistant primer over 3mm thick wall care putty on plastered surfaces prepratary to distempering all as specified. Please Enable Macros to View BoQ information |