| 1 | Supply, laying, testing and commissioning of 3.5 Core x 25 Sq.mm Copper Conductor, XLPE Insulated, PVC Sheathed, Steel Wire Armoured, 1100V Grade Power Cable conforming to IS 7098 (Part-1), including dressing, clamping, identification and all accessories as required. Approved Make: KEI/ Polycab or equivalent | Supply, laying, testing and commissioning of 3.5 Core x 25 Sq.mm Copper Conductor, XLPE Insulated, PVC Sheathed, Steel Wire Armoured, 1100V Grade Power Cable conforming to IS 7098 (Part-1), including dressing, clamping, identification and all accessories as required. Approved Make: KEI/ Polycab or equivalent |
| 2 | Supply and installation of cable end termination for above 3.5 Core x 25 Sq.mm Copper Armoured Cable, including double compression SS glands, tinned copper crimping lugs, and all incidental accessories complete. | Supply and installation of cable end termination for above 3.5 Core x 25 Sq.mm Copper Armoured Cable, including double compression SS glands, tinned copper crimping lugs, and all incidental accessories complete. |
| 3 | Supply, installation, testing and commissioning of 125 Amps, 4 Pole (TPN) MCCB, 415V AC, 50Hz, with adjustable thermal magnetic release, minimum 25 kA breaking capacity, including spreader terminals, mounting accessories and interconnection in existing LT Panel complete. | Supply, installation, testing and commissioning of 125 Amps, 4 Pole (TPN) MCCB, 415V AC, 50Hz, with adjustable thermal magnetic release, minimum 25 kA breaking capacity, including spreader terminals, mounting accessories and interconnection in existing LT Panel complete. |
| 4 | Supply and laying of 75 mm dia Galvanized Iron (GI) Pipe conforming to IS 1239, including couplers, alignment and fixing complete for cable protection purpose. | Supply and laying of 75 mm dia Galvanized Iron (GI) Pipe conforming to IS 1239, including couplers, alignment and fixing complete for cable protection purpose. |
| 5 | Road cutting, excavation, cable trenching, RCC backfilling, compaction, restoration of road surface with M25 Grade RCC, curing, disposal of debris, and reinstatement of the road surface to a smooth and even finish matching the existing paver block level and alignment, complete in all respects. | Road cutting, excavation, cable trenching, RCC backfilling, compaction, restoration of road surface with M25 Grade RCC, curing, disposal of debris, and reinstatement of the road surface to a smooth and even finish matching the existing paver block level and alignment, complete in all respects. |