| 1 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS / HFFR PVC insulated copper conductor single core cable etc. as required. (GROUP-C) |
| 2 | Wiring for light/ power plug with 2X4 sq. mm FRLS / HFFR PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit along with 1 No. 4 sq. mm FRLS/ HFFR PVC insulated copper conductor single core cable for loop earthing as required. |
| 3 | Wiring for light/ power plug with 4X4 sq. mm FRLS / HFFR PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit along with 2 Nos. 4 sq. mm FRLS / HFFR PVC insulated copper conductor single core cable for loop earthing as required. |
| 4 | Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. |
| 5 | 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire |
| 6 | 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
| 7 | 2 X 6 sq. mm + 1 X 6 sq. mm earth wire |
| 8 | 4 X 10 sq. mm + 2 X 6 sq. mm earth wire |
| 9 | Supplying and drawing Cat-6 Networking Cable (Grey) in the existing surface/ recessed steel/ PVC conduit as required. (Make- D-Link/Superior) |
| 10 | Supply and laying of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. |
| 11 | Supply and fixing of following modular switch/ socket on the existing modular plate/switch box including connections but excluding modular plate etc. as required. |
| 12 | 5/6 A One-way Modular switch (ISI) |
| 13 | 15/16A Modular switch (ISI) |
| 14 | 3 pin 5/6 A Modular socket (ISI) |
| 15 | 6 pin 6/16A Modular twin socket (ISI) |
| 16 | Telephone Socket - RJ11 -with Shutter - 1 Module (Legrand-Arteor) |
| 17 | Information Socket - RJ45 - Cat 6 - UTP - 1 Module (Legrand-Arteor) |
| 18 | Supplying and fixing following size/ modules, GI box along with modular base & cover plate for modular switches in recess etc. as required |
| 19 | 1 or 2 Module (75 mmX75 mm) |
| 20 | 3 Module (100 mmX75 mm) |
| 21 | 6 Module (200 mmX75 mm) |
| 22 | 8 Module (125 mmX125 mm) |
| 23 | 12 Module (200 mmX150 mm) |
| 24 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required. (Make: Legrand /Havells/Anchor/Schneider) |
| 25 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 A & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required. (Make: Legrand /Havells/Anchor/Schneider) |
| 26 | Supply and fixing of computer power supply boards in surface/recessed, consisting of 4nos modular type 10Amps 5 pin shuttered socket and 4nos 10 amps modular type switch with modular GI box, modular plate and front facia i/c interconnections with suitable size PVC insulated copper conductor cable etc. as required. (Make: Legrand/Havells/Schneider) |
| 27 | S/F of 8 modular facia with mounting plate in the existing cut outs of work stations for fixing of modular type switches, sockets and RJ45 jack for providing power supply and ethernet connections to the work station computers etc. as required. (Make: Legrand /Havells/Anchor/Schneider) |
| 28 | Supply of the following sizes PVC insulated & PVC sheathed copper conductor multicore un armoured cable including fixing/laying on wall with C-clamps/in existing conduits/on cable trays with cable ties etc. as required. |
| 29 | 3 coreX1.5sqmm |
| 30 | 3 coreX2.5sqmm |
| 31 | 4 coreX2.5sqmm |
| 32 | 3 coreX4.0 sqmm |
| 33 | 25sqmm with copper socketing at both ends |
| 34 | Supplying and fixing of 6way vertical type, 3 phase and neutral sheet steel MCB distribution board with metal door and IP-43 protection, suitable for flush/surface mounting with 250 A copper bus bar for each phase, 2 neutral bar, 2 earth bar and cable ties for cable management, fully insulated bus bar & shrouded neutral bars, pre-fitted masking sheet, reversible door with provision for fixing 160Amps 3 pole MCCB as incomer and SP/TP MCB's as outgoing etc. as per IEC 61439-3 and grouting in wall as required. |
| 35 | Supply and fixing of 160 Amps 415 volts 3 pole MCCB of minimum 25KA breaking capacity with Thermal and magnetic protection, Ics = 100 Icu, Thermal adjustable 0.8 to 1In, Fixed magnetic at 10In, connection and testing etc. as required. ((Make- Legrand/ L&T / Schneider Electric/ Siemens) |
| 36 | Supply and fixing following way 1 phase and neutral MCB distribution board of sheet steel, IP-43 with metal door, suitable for flush mounting and surface mounting with 100Amps copper bus bar with neutral bar, earth bar and cable ties for cable management, fully shrouded neutral bars, pre-fitted masking sheet, reversible door etc. as per IEC 61439-3 and grouting in wall as required. |
| 37 | 12 way with metal door |
| 38 | 4 way with metal door |
| 39 | Supply and fixing of Cable End box for the following IP 43 MCBDBs suitable for mounting on the top/bottom of the DB and provision for keeping extra cables/mounting terminal blocks/use as terminal box adaptor. (Make: (Same make of MCBDBs)) |
| 40 | For VTPN 6 way DB |
| 41 | For SPN 12 way DB |
| 42 | For SPN 4 way DB |
| 43 | Supplying and fixing following rating, 240/415 V, 10 kA, “C” curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 44 | 6-32Amps Single pole MCB |
| 45 | 40-63Amps Double pole MCB |
| 46 | 40-63Amps Three pole MCB |
| 47 | Blanking plate |
| 48 | Supply and fixing 2'x2' 36watts 3600 lumen ultra-modern recess mounting luminaire of luminous flux not less than 3600 lumens for general purpose square shaped luminaire with CRCA housing and high transmittivity diffuser, inbuilt electronic driver, colour Temperature: 6500°K ± 5%, CRI: ≥80 , luminous efficacy: ≥100 Lm/W, operating voltage 220-240 volt, 50 Hz AC supply with high performance LEDs, suitable for mounting with Armstrong/grid ceiling along with Ceiling light fixtures suspension cable kit fitting, hanging chains, adjustable trim length (3.2ft) including connection, testing etc. complete as required. (Make :-Phillips / Havells / Crompton / Bajaj) |
| 49 | Supply and fixing of 65000K Cool Day Light 20watt 6500K LED full glow metal surface round light fittings minimum having luminous efficacy - 100lm/watt suitable for operation on 140 volts to 270 volts AC, 50Hz i/c connection etc. as required. (make- Phillips SM251/261 LED20S 6500 PSU WH/Equivalent model of Havells /Crompton) |
| 50 | Supply and fixing 20W 4ft ultra bright LED Tube light with very high efficacy 2100Lumen, 6500K & THD<15%, single side wiring suitable for installation in existing FLT fixtures having G13 lamp holders in replacement of conventional fluorescent tubes. faulty LED tubes i/c connection etc. as required. (Make-Phillips Essential LEDTube 20W B2B 865 T8/Bajaj/Crompton/Havells). |
| 51 | Supply and Fixing of 400mm sweep Mist Air flo 3 blade wall mounted fan suitable for operation on 230 volts 50Hz, AC supply, connection, testing etc. complete as required. (Make- USHA MAX Air /SS Make) |
| 52 | Supply of following sizes PVC insulated & PVC sheathed /LT XLPE insulated PVC sheathed Aluminium conductor un armoured cable (A2XY) 1100 V. grade confirming to IS:7098 (Pt-1) 1988 i/c transportation to respective sites etc. as required. |
| 53 | 3½ X70 sq.mm |
| 54 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required. |
| 55 | Above 35 sq. mm and up to 95 sq. mm (clamped with 25x3mm MS flat clamp) |
| 56 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing Duct/Air as required. |
| 57 | Above 35 sq. mm and up to 95 sq. mm |
| 58 | Supply and making MV cable end terminations with brass compression gland and copper / aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE copper/aluminium conductor cable of 1.1 KV grade as required. |
| 59 | 3½ X 70 sq. mm (38mm) Aluminium conductor cable |
| 60 | Providing and fixing 6SWG dia GI wire on surface or in recess for loop earthing along with existing surface/recessed conduit/submain wiring / cable as required. |
| 61 | Supply and fixing of 160 Amps 415 volts TPN SDFU in Sheet steel enclosure with DIN type HRC fuses with HRC fuse links in spacious sheet steel enclosures, so that there will be no need of separate cable gland boxes, having terminal shrouds and phase barriers on both sides suitable for Cylindrical/DIN type HRC fuse links, confirming to IEC-60947-3, IS/IEC:60947-3, . (Make: LK FN type/Equivalent model of Siemens/ABB/Havells) . |
| 62 | Supply and fixing of 40 Amps 230V volts Double Pole MCB Change over switch Conforms to IEC 60947-3 and IS/ IEC 60947-3 positions (I-O-II) with centre off position, Utilization category AC-22A, connection & testing etc. as required. (Make: LK /Equivalent model of Siemens/ABB/Havells) . |
| 63 | Supply and fixing of heavy duty Bu bar enclosure, wall mounting type made with 16SWG CRCA sheet duly powder coated, removable top and bottom gland plates made of 3mm thick CRCA sheet with knockouts for different size cables and sufficient space for cable entries & exits, consisting of 3 phase 4 pole 300Amps, 415V heavy duty Aluminium Bus bars including making drill holes, supply and fixing of suitable size tinned copper nuts, bolts and washers for connectin of cables (at least 3nos 3.5X50-95sqmm Al.conductor armoured cable) with embossed earthing terminals provided at both sides of the enclosure including fixing it on the wall surface with suitable grouted metal clamps etc. complete as required. |
| 64 | Dismantling of existing old and obsolete metal clad switches/cutout boxes/MCBDBs along with cable end boxes, angle iron base frames including making good the damages of the wall/ceiling etc. complete as required. Please Enable Macros to View BoQ information |