| 1 | Supply, laying, jointing, testing and commissioning cross-linked polyethylene (XLPE) insulated cable for working voltages of 1100 V, PVC sheathed, armoured, 4 core, nominal cross sectional area of main conductor 10 sqmm, stranded aluminium conductor, ISI marked as per IS 7098(Part-I): 1988 including cable glands, lugs etc. to suit the cable size and to be laid in trenches, fixed along pole, under floors, through GI pipe laid under floors/roads, through concealed GI pipe along wall etc. including taking out old unsv cable complete all as specified and as directed. |
| 2 | S&F in renewal of MS flanged pipe of 100mm nominal bore, heavy duty, for multistorey building duly painted with two coats of synthetic enamel paint (color as per IS norms of fire fighting color code) over a coat of Zinc chromate pirmer complete all as specified and directed. |
| 3 | S&F in renewal of Butterfly valve, 100 mm dia bore, heavy duty with CI body, liver operated IS-13095 marked including jointing materials i.e rubber gaskets, nuts, bolts etc complete all as specified and directed. |
| 4 | Supply and fixing in renewal of motor protection relay for capacity 12.5 HP to 15 HP motors, relay scale 8-22 Amps, with inbuilt earth fault protection having features such as overload, earth fault, locked rotor, single phasing, current unbalance, phase sequence reversal, under current, inbuilt CT's (1 A to 88 A), Trip indication, selectable trip class-10A, 10, 20 & 30 as per IEC 947-4-1, Aux. supply 240 V AC complete all as specified and directed. |
| 5 | Supply and fixing in renewal of motor starter timer of suitable size and as per site requirement for pump motor of any capacities starters, complete all as specified and directed. |
| 6 | S & F in renewal of 3 phase contactor of suitable size and as per site requirment for pump motor of any capacities starters complete all as specified and directed. |
| 7 | S&F in renewal of existing single phase preventer complete all as specified and directed. |
| 8 | Supply only rubber gaskets for flanged joint superior quality for 100 mm dia flanges pipe complete all as specified and directed. |
| 9 | Supply only rubber gaskets for flanged joint superior quality for 80 mm dia flanges pipe complete all as specified and directed. |
| 10 | Dismantling carefully the AC electric motors of capacity upto 12.5 HP induction type, three phase, from the foundation, cutting down and removing the old burnt winding wire from the motor unit, rewinding the same with new super enameled copper winding wire as per existing size/gauge of wire, providing necessary insulation by varnishing and drying the same upto specific temperature of heat, replacing insulation paper sleeves with connecting insulating material, tapping and providing necessary connection to the motors assembly reinstalling, commissioning and testing the pumping set upto good working performance complete all as specified and directed. |
| 11 | Taking out carefully the Centrifugal pump upto 12.5 HP capacity from its foundation duly decoupling the suction and delivery lines and transporting the pump to civil workshop, dismantling and strip opening the complete pump and sort out the defective spare cleaning/servicing the pump by renewal of defective spare like brass bush-02 Nos, ball bearing of existing size-02 Nos, rubber for studes of existing size and other packing materials, greasing all spares, necessary lathe mechinery and welding work, painting of pumps with two coats of synthetic enmelled approved paints after preparation of old painted surfaces of pump set, refixing and alignement with motor on its original location including testing complete all as specified and directed.Note : The cost of spare parts shall be measured and paid seperatly under relevent item of this BOQ as supply only. |
| 12 | Supply only in renewal of following spare parts of existing make for centrifugal pump capacity upto 12.5 HP for srl item No 11.00 (here-in-before) : -Inter staging rings (Set of two Nos) |
| 13 | Inter casing rings (Set of two Nos) |
| 14 | Bushes Gun Metal |
| 15 | Bearing NDE/DE |
| 16 | Motor terminal plate having Nuts and bolts studs. |
| 17 | Shaft sleeves mild steel. |
| 18 | Coupling set with nut bolt and washer. |
| 19 | S&F in renewal of Star-Delta Starter with sheet enclosure outdoor type 3mm thick of suitable size for 12.5 HP capacities motor in existing location incl making electric connections with PVC insulated 1100 volts grade single core multi stranded copper conductor complete all as specified & directed. |
| 20 | Supply, fixing, testing and commssioning horizontal centrifugal pump with motor of 12.5 HP , 415 Volts, 3 Phase, 50 Hz, 900-1200 LPM, Head 50-60 meter, 2900 RPM, cast iron casing, stainless steel shaft, IP-55 protection, insulation class F with all connected items including taking down old unserviceable existing pump & deposit to MES store, complete all as specified and directed. |
| 21 | M&L for earthing with galvanized steel earth plate electrode of size 600 mm x 600mm x 6.0 mm, buried directly in ground (earth plate not less than 2.25 Mtr below normal ground level) connected to galvanized earth strip of 25x4 mm dia by means of bolts, buts, check nuts and washers of galvanized iron on steel including 50 mm bore light grade GI tubing for protection of earth strip, MS sheet metal funnel with wire mesh, watering pipe medium grade 20 mm bore, charcoal or coke and common salt in alternative layer of 15 Cm compacted thickness all around the electrode with concrete earth pit of PCC 1:3:6 type 75 mm thick precast RCC (1:2:4) type B1 pit cover reinfored with 8 mm dia deformed bar and suitable handle made of 10 mm dia round bar including GI earth strip of 25x4 mm size for extension of earth lead and necessary excavation, earth work, in soft/loose soil and disposal of spolis to a distance not exc 50 Mtr and necessary connection and testing complete all as shown in electrical plate No. 3 and including dismantling of old unserviceable earthing complete all as specified and directed. |
| 22 | M & L for in repair of Non return valve valve alongwith its gasket & connected accessories upto 100 mm dia complete all as specified and directed. |
| 23 | Supplying and fixing in renewal of Stainles Steel Single headed oblique pattern hydrant landing valve (internal/external) with 75 / 100 mm dia flanged inlet & 63 mm dia instantaneous type female outlet coupling with cast iron wheel complete with ABS cap and chain and all accessories as per IS:5290-93 (Type-A) in cluding matching flange (14 mm thick), nuts, bolts, washers, gaskets, etc as required complete all as specified and as directed & as per approved by GE. (Make -Safex) |
| 24 | Supply, installation, testing & commissioning in renewal of RRL fire hose Type A of 63mm dia x 15 mtr size ISI marked stainless steel with male and female coupling) complete all as specified and as directed. |
| 25 | S & F in renewal of hose box made of 18 SWG MS sheet of size 800 x 600 x 250mm with double door with 4mm thick glass and door frame made of 16 gauge MS sheet painted with fire red outside and brilliant white inside complete all as specified and directed. |
| 26 | S & F in renewal of hose box made of 18 SWG MS sheet of size 450 x 450 x 250mm with double door with 4mm thick glass and door frame made of 16 gauge MS sheet painted with fire red outside and brilliant white inside complete all as specified and directed. |
| 27 | S & F in renewal of Hose reel drum for upto length 36 m, ISI Marked complete all as specified and directed. |
| 28 | Supply, installation, testing & commissioning in renewal of HPSR 2C x 1.5sq.mm. MICA taped fire survival cable insulated overall shielded BASEC & LPCB certified cable conforming to BSL7846 & BS6837 CWZ, BSEN 50200. The cable shall withstand 950 degree centigrade for 3 hours conforming to BSL6387 standard with mounting accessories required for mounting & tagging with clamps, plastic pipes, fasteners and all accessories. (FOR Fire Alarm and Detection System) complete all as specified and as directed.MAKE: POLYCAB/KEI/RR. |
| 29 | M & L for painting MS pipe 100 mm dia, hose reel drum & metallic accessories with two coats of synthetic enamel paint (color as per IS norms of fire fighting color code) over a coat of Zinc chromate pirmer complete al as specified and as directed. Note :- Cost of T&P required for painting fire structure shall be included in the rate quoted. |
| 30 | Supply, installing, testing and commissioning in renewal of Sounder cum Strobe (Hooter) rated at 75 dBA @ 3m for Audible annunciation and 75cd flashing at 1 Hz for visual indication. Wall Mount Sounder by KAC’s base sounder, high quality loop powered device designed to alert building occupants of an emergency. It utilizes the System Sensor B501AP base for improved installation flexibility and integrates seamlessly with SS intelligent detectors. Triggered by the fire panel its powerful sounder gives an audible warning. A choice of output levels and tones make the device suitable for a wide variety of applications., complete all as specified and as directed with following Features & Benefits:- -Reduced install errors and easy fault finding-Reduced full life costs-Excellent system performance-Reduced inventory countCertifications:• EN54-3• VdS• LPCB |
| 31 | Supply, installing, testing and commissioning in renewal of Addressable Manual Call Point (Pull down / Break Glass Type). The device shall have an LED which shall blink in normal state & get steady on activation to monitor the health status of the device. UL and FM ApprovedInstallation efficiency, compliance with the latest standards are at the heart of the call point range LED Status The LED status is controlled by fire panel and shows blinking RED each time the device is polled, or continuous RED to indicate fire complete all as specified and as directed with following :- FEATURES & BENEFITS• Unique ‘Plug & Play’ installation concept • Analogue addressable communications • Fully compliant with EN54, Part 11 • Integral LEHM-MCP-GLASS SPECIFICATIONS MECHANICAL Dimensions Semi-flush mounting: 89 x 93 x 27.5 (WxHxD) Surface mounting : 89 x 93 x 59.5 (WxHxD) Weight IP Rating Operating Temperature Relative Humidity: 110g IP24D 0°C to 49°C 10% - 93% non condensing PART NUMBERS HM/MCP/GLASS Addressable break glass manual call point Operating Voltage 15V to 32Vdc max Current Consumption Quiescent: 385µA Alarm Current: 7.8 mA With TEST KEYS. |
| 32 | Supply, installation, testing & commissioning in renewal of FIRE SIGNAGES for indication / information of fire exit, alarm panel, fire extinguishers fire axe, hose reel, hydrents, lifts etc of size 12×4inches complete all as specified and as directed. |
| 33 | Supply, installation, testing & commissioning in renewal gun metal gate valve of size 25mm dia, lever operated including all connected items complete all as specified and as directed. |
| 34 | Supply, installation, testing & commissioning in renewal air release valve of size 25mm dia suitable for fire fighting 12.5 HP pump discharge pressure rating PN10/16 including all connected items complete all as specified and as directed. |
| 35 | Supply and fixing in renewal of water pressure gauge 0-300 PSI incl necessary valves reducers and nipple pipe as per existing complete all as specified and directed. (Make: H-Guru) |
| 36 | Supply, installation, testing & commissioning in renewal of Pressure switch For auto start/OFF of fire hydrant system complete all as specified and directed. (Make: DANFOSS) Please Enable Macros to View BoQ information |
| 37 | Supply, installation, testing & commissioning in renewal of Pressure switch For auto start/OFF of fire hydrant system complete all as specified and directed. (Make: DANFOSS) Please Enable Macros to View BoQ information |