| 1 | Distribution Transformer 100 to 250KVA (Erection Part):-Dismantlement & Safe unloading of 100 KVA,11/0.4 KV Transformer, Trivector meter & LT cable from transformer Str. to Ground & loading of 100 KVA,11/0.4 KV DTR through Mechanical as well as mannual mode complete in all respects as per direction of Engineer-In Charge i/c all kinds of lead lifts and other incidentals |
| 2 | Safe loading/unloading of 250 kVA 11/0.4 kV DTR from existing site through mechanical equipments as well as mannual labourer complete in all respect as per the directions of Engineer-in-charges. |
| 3 | Erection of Transformer, L.T.Box, Energy Meter, Providing earthing connection to G.O.Switch, Transformer, Lightening Arrestor , Erection of Jumpers, Erection of L.T.Cable Complete in all respect as directed by the Engineer-In-Charge including all types of risk & incedental at site. |
| 4 | Transportation Charges with loading & unloading of DTR with allied material at Divisional store & site of work |
| 5 | Distribution Transformer 100 to 250KVA (Material Part):- Prov.Panel (Distribution box L.T) With CoppPer thimbles of 200 Amp, Insulating sleeves etc. MCCB 400 amp 3P 50kA -1 No. ICS 100 % ICU & MCCB 250 Amp 36 kA =3 nos Make L&T , Schenider and ABB or its equavalent only complete in all respects as per direction of Engineer-In Charge. |
| 6 | Providing,Testing & Commissioning of LT Trivector meter 400/5Amps suitable for 250 KVA Transformer/Sub Station , Make HE , L&T and Secure or its equavalent only, complete in all respects as per direction of Engineer-In Charge. |
| 7 | Prov. alluminium thimble 300 Sq. mm. |
| 8 | Prov. copper thimble 400 Sq. mm. |
| 9 | Prov. alluminium cable (3.5 core) 300 mm² Incoming( 1 Ckt.). |
| 10 | Prov. alluminium cable (3.5 core) 185 mm² Incoming ( 2 Ckt.). |
| 11 | Abstract of cost of const. of plinth 11/0.4 KV, 250 KVA DTR. :-Earth work in excavation by mechanical means (Hydraulic excavator) / manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m. All kinds of soil. |
| 12 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level. 1:3:6 (1 Cement : 3 coarse sand): 6 graded stone aggregate 40 mm nominal size) |
| 13 | Centering and shuttering including strutting, propping etc. and removal of form for:(a) Foundations, footings, bases of columns, etc. for mass concrete. |
| 14 | (b) Walls (any thickness) including attached pilasters, butteresses, plinth and string courses etc. |
| 15 | Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level 1:1.5:3 (1 cement : 1.5 coarse sand): 3 graded stone aggregate 20 mm nominal size) |
| 16 | Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete upto plinth level Thermo-Mechanically Treated bars of grade Fe-500D or more. |
| 17 | Chain Link Fencing(For 1no. 250KVA Transformers):-Earth work in excavation by mechanical means (Hydraulic excavator) / manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m. All kinds of soil. |
| 18 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level : 1:4:8 (1 Cement : 4 coarse sand) : 8 graded stone aggregate 40 mm nominal size) |
| 19 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level : 1:1½:3 (1 Cement: 1½ coarse sand) : 3 graded stone aggregate 20 mm nominal size) |
| 20 | Steel work welded in built up sections/ framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required. In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works |
| 21 | Providing and fixing G.I. chain link fabric fencing of required width in mesh size 50x50 mm including strengthening with 2 mm dia wire or nuts, bolts and washers as required complete as per the direction of Engineer-in-charge. Made of G.I. wire of dia 4 mm |
| 22 | Providing and fixing ISI marked M.S. pressed butt hinges bright finished with necessary screws etc. complete :100x58x1.90 mm |
| 23 | Providing and fixing ISI marked oxidised M.S. sliding door bolts with nuts and screws etc. complete :250x16 mm |
| 24 | Distribution Transformer Aug. 25 to 63 KVA (Erection) :- Dismantlement & Safe unloading of 25 KVA,11/0.4 KV Transformer, Trivector meter & LT cable from transformer Str. to Ground & loading of 25 KVA,11/0.4 KV DTR through Mechanical as well as mannual mode complete in all respects as per direction of Engineer-In Charge i/c all kinds of lead lifts and other incidentals. |
| 25 | Erection of 63 KVA, 11/0.4 KV Transformer on existing transformer plateform through Mechanical as well as mannual mode, Erection of Switch L.T.Box, Energy Meter , Providing earthing to G.O.Switch, Transformer Lightening Arrestor , Erection of Jumpers, Erection of L.T.Cable Complete in all respect as directed by the Engineer-In-Charge including all types of risk & incedental at site. |
| 26 | Transportation Charges with loading & unloading of DTR with allied material at Divisional store & site of work |
| 27 | Distribution Transformer Aug. 25 to 63 KVA (Supply):- Prov.Panel(Distribution box LT) with MCCB (100 A, 3 P 35 KA, 100 A) , complete in all respects as per direction of Engineer-In Charge. |
| 28 | Prov.Alluminium Thimble |
| 29 | Prov. Copper Thimble 95 mm2 |
| 30 | Prov.3.5 Core Alluminium Cable 120 mm² Incoming Please Enable Macros to View BoQ information |