| 1 | Providing 2 Nos. 8 Passenger Lift: |
| 2 | Supply, Installation, testing and commissioning of 1 No. Lift of 8 Passangers machine room less.Type and Capacity : Approximately 544 Kg 8 passenger Speed: 1.0 Meter per second Type of drive: AC Variable Voltage Variable Frequency with 16-Bit Microprocessor. Motor: Permanent Magnet Gearless Machine to be hoisted on the top of guide rail within the elevator hoist wayTravel: upto 16.45 Meter Serving: 7 Floors 7 Stops 7 Openings 7 Levels (All on the same side) Hoist way : 1680mm (Wide) x 1800mm (Deep) Clear dimensions Headroom Height (HR): upto 4500 mm beyond finished floor level of last landing Pit Depth : 1600mm below the finish floor level of first landing Car Size Area : Minimum 1.31 square meter amd Maximum 1.45 square meterCar Enclosure : Constructed out of stainless steel Scratch proof finish (Vandal Proof). |
| 3 | Car Entrance: Center Opening Automatic Doors (all landing doors must be fire-rated for a minimum of 120 minutes, classified as EI120 according to EN 81-58) of Stainless steel finish /Honey Comb / Hairline panel in Scratch Resistance/ Vandal proof with a clear opening of 800mm (wide) x 2000mm (high) Door operation:Automatic DC Door operation with adjustable door opening and closing timings Control: Simplex full selective collective control with and without attentdent.Operation: Automatic Power Supply: 415 Volts, 3- phase, 50Hz Alternating Current Flooring: Floor Skid-resistant as per standardFan: Blower Fan in Car for ventilation with Auto cut off Lighting: LED for Car Lighting Indicators: LED Dot matrix / Digital 3 segement direction and position indicators in the car and at all landings Hand Rail: Stainless Steel round Hand rail not less than 600mm long at 900mm above floor level (Side LH,Side RH & Rear)Call Button Height: Call button (Outside the lift) placed at a height between 800mm-1meter from the floor levelControl Panel Height: Control panel placed at a height between 800mm-1meter from the floor level.As per compliance of rights of Person with Disability act 2016 & Std. Govt. Features. |
| 4 | Other Features : 1. Battery operated emergency light with rechargeable battery 2. Battery operated emergency alarm with rechargeable battery 3. Adjustable Guide shoes 4. Micro movement LED based buttons 5. Door Open and Close buttons 6. Emergency Intercom provided inside the elevator 7. Emergency Intercom usable without the voice communication 8. Load weighing device with overload bypass feature and Overload function with Audio Visual Indication9. Steel items, door frames sill angle's, fascia plates, spring buffers 10. Automatic phase reversal device and Phase Failure protection 11. Call registration 12. Audio & Video System installted in the lift indicating arrival at a floor 13. Manual break lever14. Additional car gate lock15. Automatic break testing infrared safety curten 16. Braille Buttons (Inside and outside) with Braille instructions for the communication system17. Kick plate/Skirting |
| 5 | 18. Lift anoucement system to announce floor level's in english language only and indication of door for entrance / exit is either Open or Close.19. Car Operating Panel20. Car plateform constructed out of cold rolled grain oreinted formed sheets of steel 21. Phase two device fire man drive 22. Fire Man switch at main lobby23. Car false ceiling in stainless steel 24. Pit ladder 25. Anti Nuisance car call protection 26. Door Nudging27. Automated Resuce Device to bring the elevator to the nearest landing in case of power failure.28. The provision of a mirror on the wall of the lift car opposite the lift door should not extend below 900 mm from the lift door to avoid confusing people with impaired sight.29. The emergency communication system should be coupled with an induction loop system installed all around the lift. Telephone units, where provided, should have an inbuilt inductive coupler to assist persons using hearing aids30. The use of visually and acoustically reflective wall surfaces should be minimized within the lift car as visual reflections can cause discomfort and affect the visual acuity of people with impairments.31. The floor of the lift car should be slip resistant and have similar frictional qualities to the floor of the lift landing to decrease the risk of stumbling. |
| 6 | COPPER EARTHING (8 SWG COPPER EARTHING): Earthing with 8 SWG (4mm dia.) electrolyticcopper wire thimbled (1No. copper thimble with suitable size steel bolt, washers & double nut) with 30cm x 60cm x 2mm thick copper plate (made cylindrical) burried below ground level in the hole of excavation having bore dia. 125mm and surrounded by salt & charcoal dust mixture (20 kg.) including fixing the copper wire run through 20mm dia. G.I. pipe (A-Class) recessed in wall and in floor etc., up to suitable Length in metre (including bore Length). G.I. pipe 20mm dia. (A-class) of suitable Length should be laid in the hole of excavation 1 feet below ground level and having GI Reducer 50mm x 20mm with PVC Cap (For pouring water) fixed on the top level of the pipe. 300mm x 300mm x 300mm deep haudi of First class bricks finished with 1:4 cement plaster and haudi covered with cast iron lid having size 300mm x 300mm (Heavy) around the hole of excavation:- |
| 7 | Earthing with 8 SWG (4mm dia.) copper wire thimbled with 30cm x 60cm x 2mm thick copper plate burried 10.50 metre (34.44 feet) below ground level (up to 14metre in Length) with G.I. pipe 20mm dia. (A-class), 9metre long |
| 8 | Additional Length copper wire 8 S.W.G. (4mm dia.) in 20mm dia. G.I. pipe (On Surface) |
| 9 | MCCB's (MOULDED CASE CIRCUIT BREAKER):Supply and erection of Moulded Case Circuit Breaker (Panel mounting Cubicle type) in the existing Cubical Panel (conforms to IEC:60947-11) having Ics=100% Icu, 100% neutral with spreader links and relevant PWD General Specifications (Electrical Works) complete with G.I. Bolts, Nuts & Connection on both sides of MCCB with sutiable size of Thimbles etc. |
| 10 | MCCB Four Pole 40amp., 415voIts, a25kA Fixed Magnetic and Adjustable Thermal Setting |
| 11 | SHEET METAL DOUBLE DOOR DISTRIBUTION BOARD FOR MCB/ RCBO/ RCCB's:Supply and erection of sheet metal Double Door Distribution Boards IP 43- IK09 metal door (dust protected) as per IS 8623-1&3, IEC 61439-1&3 suitable for flush mounting with fully insulated copper busbars, shrouded neutral bars, earth bars, cement spill protector, colorcoded interconnecting \vire set, cable ties, blanking plates and circuit identifications label and of required no. of ways for mounting miniature circuit breakers/ RCBO's/ RCCB's in the distribution board (For SP&N distribution board with provision DP MCB's/ RCCB's/ RCBO's as incomer and SP MCB's as outgoings and for TP&N horizontal distribution board with provision TPN/ FP MCB's/ RCCB's/ RCBO's as incomer and SP MCB's as outgoings) as per PWD General specifications including connections with suitable size of thimbles and bonding to existing earth etc:- |
| 12 | TP&N Horizontal Double Door Distribution Board 4 way each |
| 13 | Supply and erection of sheet metal Cable End Box (Make is same as MCB Distribution Board) mounting on the top or bottom of the MCB Distribution Board (Either Horizontal or Vertical) to keep loose \vires & cables as per PWD General specifications including petty materials etc as required:- |
| 14 | Cable End Box for TPN 4 Way |
| 15 | RCCB's: Supply and erection of RCCB (Residual Current Circuit Breaker) for Earth leakage protection suitable for 240/415 volts 50 cycles AC supply with breaking capacity of 10kA as per IEC 61008-1 in the existing MCB distribution board as per PWD General Specifications including connections with suitable size of thimbles/lugs:- |
| 16 | RCCB Double Pole 16/25amp., Sensitivity 30mA |
| 17 | RCCB Double Pole 32/40amp., Sensitivity 30mA |
| 18 | MINIATURE CIRCUIT BREAKERS:Supply and erection of Miniature Circuit Breaker MCB's for circuit protection against overload and short circuit current fault suitable for 240/ 415 volts 50cycles AC supply with breaking capacity of 10kA, Curve-C and low watt losses as per IS/IEC 60898-1, energy limitation class-3, true contact indication, label holder facility in the existing MCB distribution board as per PWD General Specifications including connections with suitable size of thimbIes/lugs:- |
| 19 | MCB Single Pole 6-32amp. (10kA, Curve-C) |
| 20 | MCB Triple Pole 50, 63amp. (10kA, Curve-C) |
| 21 | MCB Four Pole 50, 63amp. (10kA, Curve-C) |
| 22 | Providing Servo Stabilizer 300KVA |
| 23 | Supplying, Installation, Testing and Commissioning of Indoor application & floor Mount oil cooled Voltage Servo Stabilizer of 300/315 KVA Capacity Digital (MCU based design) Suitable for 3 phase unbalanced load having input range of 300-400 volts and output range 400V/415 AC+/-1% volts along frequency 50 Hertz with Protection required: low voltage, high voltage, low Current, high current, overload protection, phase reversal protection, phase missing protection with LED Indication & LCD Display for Metering & with input MCB/MCCB’s & by pass arrangements and with 1 year OEM Warranty. Special Feature required:• Winding Copper• Type of control : Digital (MCU based design)• Cooling : Oil Cooled type.• GENERATOR COMPATIBLE• Efficiency upto 97%• Standard & certification: Conform to IS 9815 & IS 2026 latest certified OEM.• Power factor : Suitable for all power factors• Response Time: Instantaneous (Mili Sec)• IP30 protection• Insulation: Class-A, Greater than 6M ohms• Speed of correction: upto 50 V/sec (as required)• Ambient temperature : 0 to 45 deg C• Relative Humidity : upto 95% RH• With LED Indication & LCD Display for Metering – Alpha Numerical LCD Display.• Wheel facility with lock.•Laminations: Imported High Grade Graphite complete in all respect as desired by engineer at site |
| 24 | Providing 82.5KVA Silent Diesel Generating Set: |
| 25 | Supply, Erection, Testing and Commissioning of Silent (Sound Proof} Diesel Generator Set 82.5 KVA /66KW with Manual Control Panel .It should be air cooled/water cooled naturally aspirated/ turbo charged/ turbo charged after cool (As per manufacturer standard).ENGINE: The Diesel engine developing minimum 101.3 BHP (Approx.) for giving a power rating as per ISO 8528- Pan-1 ( With CPCB-IV+ Norms as amended upto date) in KVA at the load terminals of alternator at 1500 rpm at actual site conditions. The engine shall confirm to IS 10000/ ISO 3046/ BS: 649/ BS 5514 amended up to date have dynamically balanced Fly wheel, air cleaner (dry/ oil bath type) as per manufacturer standard. A mechanical/ electronic governor of TYPE A1 AND A2 to maintain engine speed at all conditions of load, daily fuel service tank of minimum 8 hours running capacity as per manufacturer standard, Dry exhaust manifold with suitable exhaust residential grade silencer to reduce the noise level.suitable self-starter for 12 V/ 24 V DC ,battery charging alternator unit and voltage regulator, Lubrication oil cooIer,Lubrication oil filters with replaceable elements.ENGINE CONTROL PANEL: Engine control panel fitted and having digital display i.e Start/stop key switch/push button, Battery charging indication,Engine Hours indications, Over speed indication, High water temperature indication, Lubricant oil pressure indication,) RPM indication and MCCB (Fixed Thermal and Adjustable Thermal protection) of suitable rating for outgoing supply.ALTERNATOR: The alternator should be designed as per (IS4722 and IEC:34 ) standard. Rated Power Factor : 0.8 (lag), Rated voltage : 230/415 volt, SPDP (Screen Protected Drip Proof), Degree of protection: IP-23, Ventilation : Self ventilated air cooled Alternator should have 40 degree maximum class H insulation, Automatic voltage regulator unit should be provided as per standard practice of manufacturer. Its voltage dip shall not exceed more than 20% of the rated voltage at any step load or transient load as per ISO 8528 (Part-1). Its efficiency at full load 0.8 power factor, 10% overload one hour in every 12 hrs of continuous use. |
| 26 | ACOUSTIC ENCLOSURE: The enclosure shall be fabricated out the CRCA sheet of thickness not less than 1.6 mm on the outside cover with inside cover having nd less than 0.6 mm thick perforated powder coated CRCA sheet. It should be IP54 Suitable for outdoor installation exposed to weather conditions, noise level up to 75 dB (A). All sheet metal pans should be processed through 7-tank pre treatment process and batteries accommodated in the battery rack .The acoustic lining should be made up of high quality insulation material i.e. Rockwool / glass/ mineral wool / PU foam of appropriate thickness & density for sound absorption.The inside of enclosure should be provided with at least one no. 28 W-T5 fluorescent tube light/ LED 10Watt luminaries controlled by a 5A switch for adequate lighting during servicing etc.with 2 year warranty from the date of installation. complete in all respect as desired by engineer at site:-The Generator set should be instaaled at site on the suitable size existing plinth of RCC as per specifacation DG set as per satisfacation of the Engineer- in-Charge at site. The model of engine will be decided by the Engineer in Charge.MANUAL CONTROL PANEL: Manual control panel shall be fabricated out of 1.6 mm sheet steel, totally enclosed, dust, damp and vermin proof wall mounted/ free standing floor mounted type with IP-53 degree of protection & front operated, composite meter for digital display, HRC fuses of suitable rating. MCCB (Fixed Thermal and Adjustable Thermal protection)/ ACB (Over cuurent/ overload, shorcircuit, instantenous, earth fault protection) should be used.Battery charger complete with voltage regulator, Voltmeter and Ammeter for charging the battery from external mains. This will be in addition to the battery charging alternator or dynamo fitted on the engine.All the components in the control panel shall be properly mounted, duly wired and labeled. Suitable terminals are to be provided for panel incoming and outgoing connections. System opeartion facility provided shall afford the following operational requirements. Necessary instruments and accessories such as voltmeter, power factor meter, KW meter, KWH meter, Ammeter, Frequency meter,battery charger complete in all respect as desired by engineer at site:- |
| 27 | COPPER EARTHING |
| 28 | COPPER EARTHING (Upto 8 metre in Length):-Earthing with electrolytic Copper Tape rivetted (with 5Nos. copper rivets)/Steel Nut & bolts (with 4Nos. 32mm long, 8mm thick with washer and double nut) to 30cm x 120cm x 2mm thick copper plate (made cylindrical) burried 4.50 metre (14.76 feet) below ground level in the hole of excavation having bore dia. 125mm and surrounded by salt & charcoal dust mixture (20 kg.) including fixing the Copper Tape recessed in wall and in floor etc., up to 8metre in Length (including bore Length). G.I. pipe 20mm dia. (A-class), 3metre long should be laid in the hole of excavation 1 feet below ground level and having GI Reducer 50mm x 20mm with PVC Cap (For pouring water) fixed on the top level of the pipe. 300mm x 300mm x 300mm deep haudi of First class bricks finished with 1:4 cement plaster and haudi covered with cast iron lid having size 300mm x 300mm (Heavy) around the hole of excavation:- |
| 29 | Earthing with 25mm x 3mm Copper Tape (upto 8Metre in Length) |
| 30 | Additional Length 25mm x 3mm thick Copper Tape |
| 31 | Providing 11 KV, 315VA Sub Station: |
| 32 | Supply, Erection, Testing and Commisioning of HT 11kV Package Substations is completely self-contained Solution for power distribution that includes Pre fabricated indoor enclosure, high voltage switchgear, distribution transformer, low voltage panel and accessories such as power factor improvement equipment, control and protection equipments, all providing a cost effective. The complete unit shall be installed on a substation plint (base) as indoor substation. Package substation shall have the following equipments: 11kV Switchgear: 11 kV, 3 Phase, SF6 compact switchgear panel with 11kV Load break switches controls incoming-outgoing feeder cables of 11kV ring main distribution system and Vacuum circuit breaker (VCB) as protection to the transformer.The Load break switch, Vacuum circuit breaker, Bus bars should be mounted inside a sealed robotically welded stainless steel tank enclosure. The operating mechanism of switches and breakers shall be outside the SF6 tank and accesible from front. The tank should be filled with SF6 gas at an adequate pressure. The degree of protection for gas tank should be IP67. |
| 33 | There shall be provision for filling the SF6 gas at site. Stainless steel gas tank shall confirm to the sealed pressure system and ensure the gas leakage to 0.1% per year as per IEC 60298. The Panels shall be tested for IAC level of min. 21kA Sec. No. of operations of Vacuum interrupter bottles for better performance (i) At rated current: 10,000 operation (ii) No. of short circuit dead operation at rated short circuit current: 40 opeartion. Load break switch parameters are as below:(a). 11kV, 3Phase HT manually operated Load break switches 630Amp., copper busbars with integral earth switch having ON/OFF/EARTHED indiaction, live cable indiaction cable termination bushing suitable for 300sq mm XLPE cable.(b). Type: Load breaking and fault making in SF6 tank(c). Fault making capacity : 52.5kAp(d). Operating Mechanism: Operating handle with ON, OFF, Earth positions with arrangement for padlocking in each position |
| 34 | Transformer:11/0.433 kV Dyn11 Connected CAST RESIN Transformer, Core type double wound with copper conductor cnforming to IS:2026, IS:11171 & IEC:76, LOSSES AS PER ECBC 2017, LATEST AMENDMENT, AS PER IS-11171., IS2026 Part-11 with all latest amendments, vector group Dyn11 suitable for packaged substation housed in a enclosure with corrugated tank arrangement hermeatically sealed. Transformer parameters are as follows:(a). Off Circuit Tap changer: +5% to -5% @ 2.5%(b). Permissible Temp. Rise of Winding 90°C(c). Magnetic Core: Prime grade of M4 or better (d). System Highest Voltage :- 12kV at the HV side (e). Terminations: Cable Box on HV & LV Side(f). Insulation Level: F● H.V. Power Frequency (KV rms) : 28 kV ● H.V. Impulse withstand voltage (KV peak): 75 kVp● Air cooled/ Naturally cooled |
| 35 | Enclosure for PSS:Indoor type enclousre shall be made of 2mm thickness of galvanised sheet steel tropicalised to meet indian weather conditions including all the partition sheets and doors. The enclosure shall be corrugated type wall design for better heat dissipation, provinding robust construction and enclousre should have IP54 degree of protection for HT & LT switchgear compartment & IP 23 protection for transformer compartment. the base of the enclosure shall be of 4mm thickness hot dip galavanized sheet steel to ensure rigidity for easy transport & installation. The entire package substation shall be factory assemble & factory fitted. Each compartment should be provided with the door and pad locking arrangement. The unit shall be tested for internal arc fault test to the tune atlest 21kA for 1 second as per latest IEC 62271-202.Interconnection & Earthing:Interconnection between HT switchgear & transformer using screened covered aluminium XLPE single core cable & interconnection between transformer & LT switchgear using aluminium busbars with copper flexibles. Internal earthing connections by 50x 6mm G.I strips. |
| 36 | LT switchgear: The LV compartment with Degree of protection-IP54 designed for a 50 degree C ambient temperature. The panel is modular, dead front, freestanding, floor mounted and comprises the following equipment(a). LT switchgear with 433V 800Amp (4Phase) rating Aluminium busbars with 100% neutral(b). 1 No. MCCB/ ACB FP microprocessor based for O/C, S/C & Integrated E/F release type for incomer according to the KVA rating of the transformerMetering compartment:(a). 1 No.Digital multi functional meter class1.0APFC Panel:APFC PANEL OF 100 KVAR ( 25 KVAR 3 NOS. + 15 KVAR 1 NOS AND 10 KVAR 1 NOS FEEDERS complete in all respect.)(a). Capacitor Banks shall be suitable for operation at 440V Three phases with 400Amp (4 Pole) rating Almunium busbar with 100% Neutral. The type of capacitor banks shall be self healing MPP type Heavy duty as per IS: 13340-1993 and shall be housed in sheet steel container to ensure the explosion free design. The external discharge resistors shall also be provided. Capacitor Banks shall be suitable for Overloading as 115% for Over Current and 110% for Over Voltage. The Watt Loss shall not be less than 0.5w/kVAr. The Relay shall be of 12 stages to improve the power factor at least 0.98. The relay shall be microprocessor based with self diagnostic and setting including C/K ratio. |
| 37 | Package Substation 11kV HT Switchgear with 2 way RMU (RRL), consisting of 2 Nos. manually operated Load Break Switch 630 Amp., 1 No. manually operated VCB 630 Amp., 11KV/433V, 315kVA air cooled type transformerLT PANEL: Air Circuit Breaker Four Pole, 800amp., 415volts (Electrical Draw-Out Type) of suitable ampere rating at 415V, 50Hz, 4 Pole Electrical draw-out type with inbuilt microprocessor based trip sytem with thermal memory, zone selective interlocking, pre trip alarm, individual fault indicating LED, O/C, S/C, Instantaneous & E/F internal protection, Impulse withstand voltage 12kV, rated insulation voltage 1000V, rated operational voltage 690V, fully rated neutral, protection against overload & shortcircuit with setting at 50%-100%-OFF, suitability for isolation as per IEC 60947-2. The ACB should be capable for recording 20 fault history, LCD Display of current & voltage, Icu = Ics = Icw (1 Sec.) = 50kA with no derating upto 50 degree celcius on the existing industrial panel (With terminal adapter on load and line side of breaker)PANEL: 1 No. ACB FP Pole 800A = 50kA MDO Microprocessor with out goings 2 no. MCCB 400Amp FP 36kA. |
| 38 | HT CABLE, END TERMINATION KITS & CONTROL CABLE FOR TRANSFOMER: |
| 39 | XLPE INSULATED HT ARMOURED CABLES (UNDERGROUND):Supply & laying of Circular Aluminium Conductor screened with extruded semiconducting compound, XLPE insulated, insulation screened with extruded semiconducting combination in combination with copper tape (0.3KA for 1sec.) cores laid up, FR PVC inner sheathed, galvanized steel strip armoured and overall FR PVC sheathed cable confirming to IS:7098 (Part-2), 2011 working voltage 11KV(E) grade to be laid 1.50 meter below ground level including excavation, sand cushioning, covering with sand & First class bricks and back filling the trench etc., of the required size:- |
| 40 | HT Cable Overall size 50sq.mm (3Core) From PSPCL Meter to Substation |
| 41 | CABLE TRAY:Supply and erection of MS perforated cable tray (MS Sheet thickness 2mm) with DA gray paint on the existing surface with the help of MS angle iron support (to be painted with approved paint) of size 50mm x 50mm x 6mm thick to be fixed with fastners/ nut & bolts etc., complete in all respect as desired by the Engineer-in-charge and as per PWD General Specifications:- |
| 42 | Cable Tray Size 300mm x 50mm x 50mm (2mm thick) |
| 43 | S/E of LT Cast Resin type/ Heat Shrinkable Termination Kit for Outdoor/ Indoor supply of 1.1 KV grade PVC/XLPE cable as desired by the Engineer in charge of the site:- |
| 44 | Heat Shrinkable Outdoor/ Indoor End Termination Kit for Cable Size 3½/4 Core 400-630sq.mm |
| 45 | COPPER EARTHING |
| 46 | COPPER EARTHING (Upto 14 metre in Length):-iii- Earthing with electrolytic Copper Tape rivetted (with 5Nos. copper rivets)/Steel Nut & bolts (with 4Nos. 32mm long, 8mm thick with washer and double nut) to 30cm x 120cm x 2mm thick copper plate (made cylindrical) burried 10.50 metre (34.44 feet) below ground level in the hole of excavation having bore dia. 125mm and surrounded by salt & charcoal dust mixture (20 kg.) including fixing the Copper Tape recessed in wall and in floor etc., up to 14metre in Length (including bore Length). G.I. pipe 20mm dia. (A-class), 9metre long should be laid in the hole of excavation 1 feet below ground level and having GI Reducer 50mm x 20mm with PVC Cap (For pouring water) fixed on the top level of the pipe. 300mm x 300mm x 300mm deep haudi of First class bricks finished with 1:4 cement plaster and haudi covered with cast iron lid having size 300mm x 300mm (Heavy) around the hole of excavation:- |
| 47 | Earthing with 25mm x 3mm Copper Tape (upto 14Metre in Length) |
| 48 | Additional Length 25mm x 3mm thick Copper Tape |
| 49 | SUB STATION SAFETY EQUIPMENTS: |
| 50 | Supply of Rubber hand gloves suitable for 11KV. |
| 51 | Supply & fixing of shock treatment chart both in Hindi & English for treating person suffering due to electric shock mounted on wall hooks. |
| 52 | Providing and fixing H.T. danger notice plate of 250 mm x 200mm, made of mild steel at least 2mm thick and vitreous enamelled white on both sides and with inscription in single red colour on front side as required. |
| 53 | Providing and fixing M.V. danger notice plate of 200 mm x 150mm, made of mild steel at least 2mm thick and vitreous enamelled white on both sides and with inscription in single red colour on front side as required. |
| 54 | Providing of set of 4 Nos. 9.5 Litre capacity GI bucket painted in post office red colour with prior coat of red - oxide paint and written with white paint 'Fire' and mounted on MS angle iron frame with bracket of appropriate size and capacity including filling sand etc. |
| 55 | Supply of First Aid box as approved by St. John Ambulance Brigade / Indian red Cross conforming to IS 2217 -1963. |
| 56 | Supply & fixing of fire retardant/ extinguishing Electrical insulated synthatic mat 1Mt. x 2Mt. of 2.0 mm thick +/- 10% confirming to BIS: DOC NO. ET-02 (5440) meeting requirments of IS: 15652 :2006 (with upto date amendment), suitable for all voltages not exceeding 3.3 KV and having minimum width of 1000 mm +/- 20mm and including supply of required quantity of adhensive/ compound and fixing the same at size as per site requirments. |
| 57 | Supply & fixing of fire retardant/ extinguishing Electrical insulated synthatic mat 1Mt. x 2Mt. of minimum 3.0 mm thick +/- 10% confirming to BIS: DOC NO. ET-02 (5440) meeting requirments of IS: 15652 :2006 (with upto date amendment),, suitable for all voltages not exceeding 33 KV and having minimum width of 1000 mm +/- 20mm and including supply of required quantity of adhensive/ compound and fixing the same at size as per site requirments. |
| 58 | Providing EV Charging System: |
| 59 | Supply, Installation, testing and Commissioning of 7.4Kw AC wallbox type 2, cable attached 5 metres min, Single Phase, 230 Vac, 50 Hz with RFID, Mobile app, Bluetooth, ethernet, WIFI connectivity, Network Interface: Ethernet, Wi-Fi, Communication Protocol: Modbus RS-485 (For Energy Metre connection), Modbus TCP/IP, GSM (4G), OCPP 1.6 compliant, Protection: IP66, IK10, Protection: Overcurrent, overvoltage, undervoltage, ground fault including DC leakage protection, integrated surge protection, Overvoltage category : III, Available configurable contacts: 1 input, 1 output, Connectivity : Wifi, Ethernet (RJ45), Bluetooth, RS485, 4G / 3G, NEMA enclosure type: NEMA 4 and 4X,IP.65 or IP 66 Operating altitude : 3000 m, Operating temperature range : -5°C to 55°C (minimum) (derating may apply), Storage temperature range : -35...+50 °C (derating may apply), Mounting: Wall or floor using a pedestal, Safety standards : IEC/EN 61851-1, IS 17017 (ARAI) . complete in all respects as approved and desired by the Engineer-in-charge at site. |
| 60 | Providing Solar Power Generation System: |
| 61 | Grid interactive PV System Solar Power Plant of KWp: |
| 62 | Supply, Installation, testing & Commissioing of Grid interactive PV System Solar Power Plant (i.e connected to utility grid) of Minimum capacity of 5Kwp including required quantities of SPV modules (High power density Monocrytalline based single module of capacity +500 watt) formed into arrays, their mounting arrangement, Power conditioning units (i.e String Solar Inverter with 2Nos. GI Chemical earthing with suitable size GI strip upto string inverter and AC & DC distribution panel), required DC & AC distribution panels with surge protection units, cabling from terrace to main distribution board through Cable tray, Bi Directional Energy Meter, Provision of Lightening Arrestor & 2 Nos. GI chemical earthing with suitable size GI strip upto Lightning arrestor, Hot dip galvanized MS Mounting Structures (1No. GI Chemical earthing with suitable size GI strip upto mounting structure) should be designed to withstand the speed for the wind Zone of the location (150 Km/hr-170 Km/hr) Complete in all respect with transportaion, fabrication, labour & Civil Work etc. Features :- 1. Solar PV Module warranty 25 Years & certified under IS/IEC 61730 I & II IS/IEC 61701 & IS/EC 142862. Power Conditioning unit (string solar inverter) & certified under IEC/EN 62109-1, IEC/EN 62109-2, EN 61000-6-2, EN 61000-6-3, IEC 61683, EN 50530, IEC 60068-2-1, 2, 14, 30, EN 605293. Structure 25 Years service life with AMC & certified under IS 2062 20114. Complete Plant insurance for the period of 5 Years (Excluding Theft of the Material)5. Annual Maintenance contract for the period of 10 YearsConditions:# The Plant will be installed as per MNRE and GOI guidelines and specifications. (Detail of material as per Annexure-I attached)#The work will got done from approved MNRE (Misitry of New and Renewable Energy)/ PEDA (Punjab Energy Development Agency) contractor/PWD enlisted contractor subject to condition that PWD enlisted contractor will get work done from MNRE/PEDA approved Contractor.#The capacity of solar power plant my increase or decrees as availability of site it can also be totally removed from executive endThe Rate are inclusive of Bidirectional Meter testing Charges. PSPCL Connection Charge.Unidirectional Meter Cost and all type of Taxes including GST. Please Enable Macros to View BoQ information |