| 1 | Excavation in trenches in soft/loose soil not exceeding 1.5 mtr deep and not exceeding 1.5 mtr wide for laying of cable complete all as speciied and directed. |
| 2 | Returning, filling in including spreading, leveling, watering and well ramming excavated soft/loose soil in layers , complete all as speciied and directed. |
| 3 | Removing excavated material surplus (soil ) to a distance not exceeding 50 mtr and depositing where directed at a level not exceeding 1.5m above the starting point complete all as speciied and directed. |
| 4 | M&L for sand cushioning to under ground cable using locally available fine clean dry river sand over,under ground UG cable laid in treches and gently punning to cushioning to cable complete all as speciied and directed. |
| 5 | Supplying and laying reinforced precast concrete cable cover Class LV, Type I, flat, size 250 mm x 150mm x 40mm complete all as specified and directed. |
| 6 | S&F in repair,given size bore tubing 50 mm bore 'light grade' in trenches/ on pole for protection of cables complete all as speciied and directed. |
| 7 | S&F in repair,given size bore tubing 32 mm bore 'light grade' in trenches/ on pole for protection of cables ccomplete all as speciied and directed. |
| 8 | S&F in repair,given size bore tubing 80 mm bore 'light grade' in trenches/ on pole for protection of cables complete all as speciied and directed. |
| 9 | Supply ,laying & testing in trenches / pole cable XLPE insulated screened PVC bedded galvanised steel strip or wire, armoured electric power cable (heavy duty) with stranded aluminium conductor 11000 volts earthed grade of cross sectioal area 185 Sqmm 3.5 Core wth all fitting accessories i.e Aluminium Lugs etc complete all as specified and directed. |
| 10 | All as per Ser Item No 9 above but for 120 Smm 3.5 Core complete all as specified and directed. |
| 11 | All as per Ser Item No 9 above but for 70 Sqm 3.5 Core complete all as specified and directed. |
| 12 | All as per Ser Item No 9 above but for 50 SQmm 3.5 Core complete all as specified and directed. |
| 13 | All as per Ser Item No 9 here-in-before but for 35 SQmm 3.5 Core complete all as specified and directed. |
| 14 | All as per Ser Item No 9 here-in-before but for 25 SQmm 3.5 Core complete all as specified and directed. |
| 15 | All as per Ser Item No 9 here-in-before but for 16 SQmm 4 Core complete all as specified and directed. |
| 16 | All as per Ser Item No 9 here-in-before but for 10 SQmm 4 Core complete all as specified and directed. |
| 17 | All as per Ser Item No 9 here-in-before but for 125 SQmm 2 Core complete all as specified and directed. |
| 18 | All as per Ser Item No 9 here-in-before but for 16 SQmm 2 Core complete all as specified and directed. |
| 19 | All as per Ser Item No 9 here-in-before but for 10 SQmm 2 Core complete all as specified and directed. |
| 20 | Dismantling of old/rusted aluminium conductor steel reinforced of any size and removing the same from site of work complete all as speciied and directed.. |
| 21 | Dismantling of old/rusted Cross arms,bracings, supports, clamps and back plates including nut bots etc any size and removing the same from site of work complete all as speciied and directed. |
| 22 | Material and Labour in repair, dismantling the all cable from panel, poles, MCB Main DBs taking out the cable loop stretching out the cable, carrying out end termination with new lugs, proper thimbling, fixing the joint kits connecting back to the new/existing panel board by means of nuts, bolts & washers of any size any type complete all as speciied and directed.. Note: (The work includes necessary excavation to take out the loop,and laying the cable, putting proper cable protection bricks using the old retrived bricks and refill the area properly and spreading any surplus soil (ii) The cost of Al lugs, joint kit shall be measured and paid separately under relevant items of schedule |
| 23 | Supply & fix for cable straight through joint for 1100 volt, out door type terminal heat shrinkable type joint complete with all jointing material and accessories suitable for 3.5/4 core 70-150sqmm, complete all as speciied and directed. |
| 24 | Supply & fix for cable straight through joint for 1100 volt, out door type terminal heat shrinkable type joint complete with all jointing material and accessories suitable for 2/3.5/4 core 25-50sqmm, complete all as speciied and directed. |
| 25 | Supply & fix for cable straight through joint for 1100 volt, out door type terminal heat shrinkable type joint complete with all jointing material and accessories suitable for 2 core 10-25sqmm, complete all as speciied and directed. |
| 26 | S&F new PVC cable Junction Box IP66 \\"halogen free and weather proof\\" for out door installation size not less than 200 x 150 x 100 mm suitable for street light incoming and outgoing cables up to 10 to 25 sqmm 4 core (with terminal) & inclusive of MCB SP 10 Amp, 60A 04 strip aluminium Bus Bar, including nuts,bolts,cable glands & MS clamps fixed to pole complete all as speciied and directed. |
| 27 | Supply, laying & testing PVC insulated, PVC sheathed cable galvanized steel strip or wire unarmoured, electric control cables (Heavy duty) with stranded copper conductor of size 1.5 sq mm ,2 core, 1100 Volts grade passed through and including PVC conduit medium grade of size Min 20mm bore complete all as specified and directed. |
| 28 | M&L Earthing complete with Galvanised steel earth plate 60cmx60cmx6mm thick electrode, buried directly in ground (earth pit not less than 2.25 mtrs deep below ground level) with top edge of the plate not less than 1.5 m below ground level , connected to GI earth strip 25 X 4mm up to test point by means of bolts ,nuts , check nuts and washers of GI including excavation and earth work, PCC 1:3:6 type C-1 pit, 20mm dia GI pipe medium grade, watering pipe and 20 mm bore GI pipe, light grade for protection of earth strip, MS angle iron frame 40x40x3mm, 10mm thick RCC 1:2:4 type B-1 cover reinforced with 6mm dia MS bars @ 75mm C/C both ways and with MS handle made out of 12mm dia bars, PGI Funnel, wire mesh etc complete all as shown in electrical Plate No 03 of SSR Part-I and connected to earthing test point all as specified or indicated including testing on completion complete and including taking down old u/s complete all as speciied and directed. |
| 29 | Supply, install, testing and commissioning outdoor type LT panel of size 1.2m x 1.2m x 0.6m , with latest IP factory made totally enclosed dust and vermin proof , double steef shutter in front and single leaf shutter in rear side made of 3.15 mm thick CRCA sheet, duly fabricated and having proper locking arrangement in both ront and rear door painted with powder coated paint and aluminium bus bar 600 amps suitable for 500 volts, 50 Hz , 3 phase 4 wire system and comprising with and including following accesories and mounted on PCC platform all around the panel board complete with the following items complete all as speciied and directed.:- (FP-II ) Note : Foundation to be included in the quoted priceIncoming :-(a) MCCB, 4 Pole, 200 A, 415 V, 25 kA. (I/C). Thermal Magnetic release(b) 3 Phase LED Voltmeter Cl-1(c) Phase indicator lamps (RYB) -set of 3(d) aluminium bus bar 4 strip - 400 amps (length should not be less than 0.7(e) Internal connection by aluminium strip from mcb/mccb to busbar and busbar to mccb/mcb etcOutgoing :-(a) MCCB, 4 Pole, 100 A, 415 V 25 kA - 02 nos(b) MCCB, 4 Pole, 63 A, 415 V 25 kA - 02 nos(c) MCCB, 4 Pole, 63A, 415 V 25 kA - 02 nos(d) MCB, TPN, 32 A, 240 V, 18 kA - 04 No. |
| 30 | Supply, install, testing and commissioning outdoor type LT panel of size 1.2m x 1.2m x 0.6m , with latest IP factory made totally enclosed dust and vermin proof , double steef shutter in front and single leaf shutter in rear side made of 3.15 mm thick CRCA sheet, duly fabricated and having proper locking arrangement in both ront and rear door painted with powder coated paint and aluminium bus bar 600 amps suitable for 500 volts, 50 Hz , 3 phase 4 wire system and comprising with and including following accesories and mounted on PCC platform all around the panel board complete with the following items complete all as speciied and directed.:- (FP-I & FP-V ) Note : Foundation to be included in the quoted priceIncoming :-(a) MCCB, 4 Pole, 160 A, 415 V, 25 kA. (I/C). Thermal Magnetic release(b) 3 Phase LED Voltmeter Cl-1(c) Phase indicator lamps (RYB) -set of 3(d) aluminium bus bar 4 strip - 600 amps (length should not be less than 0.7 m)(e) Internal connection by aluminium strip from mcb/mccb to busbar and busbar to mccb/mcb etcOutgoing :-(a) MCCB, 4 Pole, 100 A, 415 V 25 kA - 01 nos(b) MCCB, 4 Pole, 63 A, 415 V 25 kA - 03 nos(c) MCB, TPN, 32 A, 240 V, 18 kA - 04 No. |
| 31 | Supply, install, testing and commissioning outdoor type LT panel of size 1.2m x 1.2m x 0.6m , with latest IP factory made totally enclosed dust and vermin proof , double steef shutter in front and single leaf shutter in rear side made of 3.15 mm thick CRCA sheet, duly fabricated and having proper locking arrangement in both ront and rear door painted with powder coated paint and aluminium bus bar 600 amps suitable for 500 volts, 50 Hz , 3 phase 4 wire system and comprising with and including following accesories and mounted on PCC platform all around the panel board complete with the following items complete all as speciied and directed.:- (FP- III ) Note : Foundation to be included in the quoted priceIncoming :-(a) MCCB, 4 Pole, 320 A, 415 V, 25 kA. (I/C). Thermal Magnetic release(b) 3 Phase LED Voltmeter Cl-1(c) Phase indicator lamps (RYB) -set of 3(d) aluminium bus bar 4 strip - 600 amps (e) Internal connection by aluminium strip from mcb/mccb to busbar and busbar to mccb/mcb etcOutgoing :-(a) MCCB, 4 Pole, 200 A, 415 V 25 kA - 02 nos (W+S)(b) MCCB, 4 Pole, 100 A, 415 V 25 kA - 01 nos(c) MCCB, 4 Pole, 63 A, 415 V 25 kA - 02 nos(d) MCB, TPN, 32 A, 240 V, 18 kA - 04 No. |
| 32 | Supply, install, testing and commissioning outdoor type LT panel of size 1.2m x 1.2m x 0.6m , with latest IP factory made totally enclosed dust and vermin proof , double steef shutter in front and single leaf shutter in rear side made of 3.15 mm thick CRCA sheet, duly fabricated and having proper locking arrangement in both ront and rear door painted with powder coated paint and aluminium bus bar 400 amps suitable for 500 volts, 50 Hz , 3 phase 4 wire system and comprising with and including following accesories and mounted on PCC platform all around the panel board complete with the following items complete all as speciied and directed.:- (FP-IV ) Note : Foundation to be included in the quoted priceIncoming :-(a) MCCB, 4 Pole, 200 A, 415 V, 25 kA. (I/C). Thermal Magnetic release(b) 3 Phase LED Voltmeter Cl-1(c) Phase indicator lamps (RYB) -set of 3(d) aluminium bus bar 4 strip - 400 amps (length should not be less than 0.7(e) Internal connection by aluminium strip from mcb/mccb to busbar and busbar to mccb/mcb etcOutgoing :-(a) MCCB, 4 Pole, 100 A, 415 V 25 kA - 02 nos(b) MCCB, 4 Pole, 63 A, 415 V 25 kA - 02 nos(c) MCB, TPN, 32 A, 240 V, 18 kA - 04 No. |
| 33 | Supply, install, testing and commissioning outdoor type LT panel of size 0.6m x 0.6m x 0.5m , with latest IP factory made totally enclosed dust and vermin proof , double steef shutter in front and single leaf shutter in rear side made of 3.15 mm thick CRCA sheet, duly fabricated and having proper locking arrangement in both front and rear door painted with powder coated paint and aluminium bus bar 100 amps suitable for 500 volts, 50 Hz , 3 phase 4 wire system and comprising with and including following accesories and mounted on PCC platform all around the panel board complete with the following items complete all as speciied and directed.:- (Bus Bar Panel- II & III) Note : Foundation to be included in the quoted price(a) aluminium bus bar 4 strip of 100 Amps having hole drilled on Bus Bar for fixing of cables.(b) MCCB, 4 Pole, 100 A, 415 V 25 kA - 01 nos |
| 34 | Materials and labour for PCC ( 1:4:8) type D-2 Using 40 mm graded stone aggregate as in foundation of stay assembly , poles struts etc. complete all as specified and as directed . |
| 35 | Dismantling insulators any type, any size complete all as speciied and directed. |
| 36 | Dismantling of GI Earth wire 40mm or any size complete all as speciied and directed. Please Enable Macros to View BoQ information |
| 37 | Dismantling of GI Earth wire 40mm or any size complete all as speciied and directed. Please Enable Macros to View BoQ information |