| 1 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. Group C |
| 2 | Wiring for twin control light point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed PVC conduit, 2 way modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FR PVC insulated copper conductor single core cable etc as required. |
| 3 | Wiring for light/ power plug with 2X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed steel conduit alongwith 1 No. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required. |
| 4 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
| 5 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. 2 X 6 sq. mm + 1 X 6 sq. mm earth wire |
| 6 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. 4 X 10 sq. mm + 2 X 6 sq. mm earth wire |
| 7 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 Amp modular socket outlet and 5/6 A modular switch, connections etc. as required. |
| 8 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required. |
| 9 | Supply, Installation, Testing and Commissioning of 9 W Bulk head Light. |
| 10 | Supply, Installation, Testing and Commissioning of 10W Mirror Light. |
| 11 | Supply, Installation, Testing and Commissioning of 18W Surface/Recessed Mounted LED circular Downlighter. |
| 12 | Supply, Installation, Testing and Commissioning of 36W (Nominal) 2x2 ft Recess Mounted LED Luminaire. |
| 13 | Installation, testing and commissioning of ceiling fan, including wiring the down rods of standard length (upto 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable, including providing and fixing phenolic laminated sheet cover on the fan box etc. as required. |
| 14 | Supplying of 1200 mm sweep Power Saver A.C. electric Ceiling fans, capacitor type with double ball bearing complete with 300 mm down rod, canopies, shackles, blades, but without regulator suitable for operation on 230 / 240 Volts, 50 Hz, single phase, A.C. supply etc. as reqd. |
| 15 | Supply, Installation, Testing and Commissioning of 250 mm dia Domestic Exhaust Fan |
| 16 | Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer) as required . (Note :Vertical type MCB TPDB is normally used where 3 phase outlets are required.)4 way (4 + 12), Double door |
| 17 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single Pole |
| 18 | Supplying and fixing following rating, four pole, 415 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 A |
| 19 | Supplying, installing, testing & commissioning of surface / wall mounted type compartmentalised cubicle board made from 2mm thick CRCA sheet dust & vermin proof duly phosphatized & painted inclusive of 125 Amp 4 strip Al. Busbar complete with interconnection pdg. Lugs, inter-earthing, painting etc. i/c pdg. & fixing below noted accessories.INCOMING :200 Amp 415 V FP MCCB having braking capacity - 50 KA, with Ics=Icu= 50 KA, with potary Handle operating Mechanism - 1 No. (0-100 A) Ammeter with selector switch & 100/S C.T.'s (Digital type) 1 Set, (0-500 R/Y/B with backup fuses - Set of ThreeOUTGOING :63 Amp 415 V TP MCCB having breaking capacity - 25 KA, with Ics=Icu=25 KA, with Rotary Handle operating Mechanism - 4 Nos., 32 Amp TPN MCB - 10 KA - 6 Nos. |
| 20 | Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 21 | Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut,bolt, spring, washer excavation and re-filling etc. as required. |
| 22 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required. |
| 23 | Supplying and fixing extra down rod of 10 cm length G.I. pipe,15 mm dia, heavy gauge including painting etc. as required. (Note: More than 5 cm length shall be rounded to the nearest 10 cm and 5 cm or less shall be ignored) |
| 24 | Providing & Fixing 20 Watt LED Batten on Ceiling and Wall as required. |
| 25 | Supplying and fixing of 32 mm dia X 2.00 meter long G.I. pipe (medium class) bracket for mounting of fluorescent / HPMV /HPSV street light fitting on pole including bending the pipe to the required shape, 2 Nos. 40 mm X 3 mm flat iron clamps with nuts, bolts and washer, painting the flat iron with primer and finish paint etc. as required. |
| 26 | Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 27 | Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in foundation and plinth in: Cement mortar 1:6 (1 cement : 6 coarse sand) |
| 28 | 12 mm cement plaster of mix : 1:6 (1 cement : 6 Fine sand) |
| 29 | 15 mm cement plaster on the rough side of single or half brick wall of mix : 1:6 (1 cement : 6 Fine sand) |
| 30 | Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete. |
| 31 | Providing and supplying aluminium extruded tubular and other aluminium sections as per the architectural drawings and approved shop drawings , the aluminium quality as per grade 6063 T5 or T6 as per BS 1474,including super durable powder coating of 60-80 microns conforming to AAMA 2604 of required colour and shade as approved by the Engineer-in-Charge. (The item includes cost of material such as cleats, sleeves, screws etc. necessary for fabrication of extruded aluminium frame work. Nothing extra shall be paid on this account) |
| 32 | Providing and fixing stainless steel ( Grade 304) railing made of Hollow tubes, channels, plates etc., including welding, grinding, buffing, polishing and making curvature (wherever required) and fitting the same with necessary stainless steel nuts and bolts complete, i/c fixing the railing with necessary accessories & stainless steel dash fasteners , stainless steel bolts etc., of required size, on the top of the floor or the side of waist slab with suitable arrangement as per approval of Engineer-incharge, (for payment purpose only weight of stainless steel members shall be considered excluding fixing accessories such as nuts, bolts, fasteners etc.). |
| 33 | Providing and fixing 1mm thick M.S. sheet door with frame of 40x40x6mm angle iron and 3 mm M.S. gusset plates at the junctions and corners,all necessary fittings complete, including applying a priming coat of approved steel primer. Using flats 30x6mm for diagonal braces and central cross piece Please Enable Macros to View BoQ information |