| 1 | Taking down carefully aluminum/ copper point wiring (light, fan, socket or power) complete (excluding sunken box) including fittings such as switches, ceiling roses, pendants, regulators, sockets, light fittings etc and segregating serviceable fittings & set aside for reuse in the work and making good to disturbed surfaces of walls, floors, ceilings etc. complete all as specified and as directed. |
| 2 | Taking down unserviceable sub main wiring of any type and any size including wooden batten, PVC conduit or casing caping complete all as specified and as directed. |
| 3 | Material & Labour for point wiring complete with cable PVC insulated, unsheathed, 1100V grade conforming to IS for one way SP, 5A with 1.5 Sqmm of cable of nominal area multistranded copper conductor drawn through and including 20mm PVC casing capping including accessories on wall/floor/ceiling ( on surface) etc with 16G MS pressed steel terminal box with 2.8 mm thick laminated sheet cover for mounting switch, socket outlet etc complete with all accessories/fittings including PVC insulated continuous muli standred copper earth wire (1.5 Sqmm) and connected to common earth dolly complete for the following :-(a) One light /fan point/ bell point controlled by one way one switch. Complete all as specified and as directed. |
| 4 | All as per Item No 3.00 above but one 3 Pin 5/6 Amp socket outlet on independent board. Complete all as specified and as directed. |
| 5 | All as per Item No 3.00 above but one 3 Pin 5/6 Amp socket outlet on same board with other switches. Complete all as specified and as directed. |
| 6 | Material & Labour for point wiring complete with cable PVC insulated, unsheathed, 1100V grade conforming to IS for one way SP, 5A with 1.5 Sqmm of cable of nominal area multistranded copper conductor drawn through and including 20mm PVC conduit including accessories on wall/floor/ceiling ( on surface) etc with 16G MS pressed steel terminal box with 2.8 mm thick laminated sheet cover for mounting switch, socket outlet etc complete with all accessories/fittings including PVC insulated continuous muli standred copper earth wire (1.5 Sqmm) and connected to common earth dolly complete for the following :-(a) One light /fan point/ bell point controlled by one way one switch. Complete all as specified and as directed. |
| 7 | All as per Item No.6.00 above but one 3 Pin 5/6 Amp socket outlet on independent board. Complete all as specified and as directed. |
| 8 | All as per item No 6.00 above but point wiring with 2.5 Sqmm stranded PVC unsheathed copper conductor for one 3 Pin 15/16 amps socket outlet on independent board including continuour earth wire with 2.5 Sqmm stranded PVC unsheathed copper conductor and connected to common earth dolly. Complete all as specified and as directed. |
| 9 | Material and Labour for sub main wiring using two single core PVC insulated, stranded copper conductor (FRLS) cable of size 4 Sq mm unsheathed drawn in and including PVC caping casing including accessories in surface to wall/floor/ceiling etc and 1x4 Sq mm PVC insulated unsheathed copper conductor as continuous earth continuity conductor drawn in complete all as directed and specified. |
| 10 | Material and Labour for sub main wiring using two single core PVC insulated, stranded copper conductor (FRLS) cable of size 6 Sq mm unsheathed drawn in and including PVC rigid conduit including accessories in surface to wall/floor/ceiling etc and 1x6 Sq mm PVC insulated unsheathed copper conductor as continuous earth continuity conductor drawn in complete all as directed and specified. |
| 11 | Supply & fix switch piano flush type 5/6 Amps single pole one way. Complete all as specified and as directed. |
| 12 | Supply & fix Switch socket combination, 3/5 pin, 5/6 Amp flush type. Complete all as specified and as directed. |
| 13 | Supply & fix Switch socket combination 2 in 1, 3 Pin, 5/6 Amp and 15/16 Amp flush type universal. Complete all as specified and as directed. |
| 14 | Supply & fix stepped type electronics fan regulator on the existing phenolic laminated sheet etc. Complete all as specified and as directed. |
| 15 | Supply & fix Ceiling rose 3 Terminal/PVC/ Polycarbonate, isolated body. Complete all as specified and as directed. |
| 16 | Material and Labour for Bell push flush type 5 Amps complete all as specified and directed. Complete all as specified and as directed. |
| 17 | Supply and fixing Buzzer, Ding Dong AC 230 volts, single pole complete all as specified and as directed. |
| 18 | Supply and fixing school Gong Bell 15 inch, AC 230 volts, single phase complete all as specified and as directed. |
| 19 | Supply and fixing school Auto Bell multipurpose timer, AC 230 volts, single phase complete all as specified and as directed. |
| 20 | Material and Labour sheet metal enclosure for double door DBs using MCB with 200 Amps rated bus/link bar of 4 way 240V including taking down unserviceable one. Complete all as specified and as directed. |
| 21 | Material and Labour sheet metal enclosure for double door DBs using MCB with 200 Amps rated bus/link bar of 8 way 240V including taking down unserviceable one. Complete all as specified and as directed. |
| 22 | Material and Labour for wall mounted Busbar chamber TPN (4 bar) 100 Amp rated, 415 volt, 8 way complete all as specified and as directed. Make - Havells, Cat No.IHBC010008 or equivalent make of L&T/Legrand/ABB/Schneider. |
| 23 | Material and Labour for wall mounted Busbar chamber TPN (4 bar) 200 Amp rated, 415 volt, 4 way complete all as specified and as directed. Make - Havells, Cat No.IHBC020004 or equivalent make of L&T/Legrand/ABB/Schneider. |
| 24 | Material and Labour for Switch Disconnector fuse unit (SDFU) with sheet steel enclosure 200 Amp rated, 415 volt complete all as specified and as directed. Make - Havells, Cat No.IHFSFW4200 or equivalent make of L&T/Legrand/ABB/Schneider. |
| 25 | Supply & fixing MCB SPN 40 Amps 230 Volt 'C' Curve, 10 KA.complete all as directed and specified. |
| 26 | Supply & fixing MCB SP 6 to 32 Amps 230 Volt 'B' Curve, 10 KA.complete all as directed and specified. |
| 27 | Material and Labour single pole and Neutral enclosure with a two pin and earth plug and socket 15 Amp complete with one single pole MCB 20 Amps including taking down old one complete all as directed and specified. |
| 28 | Taking up old unsv LT UG cable of any size from trenches/road /floor/poles & wall complete all as specified and directed. |
| 29 | Supply, laying, commissioning and testing of UG cable XLPE insulated screened PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) 1100 volts grade with stranded aluminium conductor of size 10 sq mm 4 core laid in trenches or fixed to walls including end termination fixing with lugs and nut bolts complete all as specified and directed. |
| 30 | Supply, laying, commissioning and testing of UG cable XLPE insulated screened PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) 1100 volts grade with stranded aluminium conductor of size 35 sq mm 3.5 core laid in trenches or fixed to walls including end termination fixing with lugs and nut bolts complete all as specified and directed. |
| 31 | Supply, laying, commissioning and testing of UG cable XLPE insulated screened PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) 1100 volts grade with stranded aluminium conductor of size 70 sq mm 3.5 core laid in trenches or fixed to walls including end termination fixing with lugs and nut bolts complete all as specified and directed. |
| 32 | S&F LED 20 Watt tube light fitting intregated type,operational voltage of 170 volts to 270 volts, frequency of 50 Hz, lumen efficacy of minimum 100 lumens per watt, integrated electronic driver with output short circuit protection and surge protection upto 2.5 KV, protection grade IP 20, CCT of 6500K, extruded PVC battens complete fitting including connecting with PVC insulated multistranded copper flexible cable 1.0 sqmm three core, and PVC round/ square box white colour x 2 Nos for mounting of fitting including taking down old unserviceable complete all as specified & directed. (Make :Havells,Cat part No LHEXAXPNIN1W020 or equivalent of Philips/Bajaj/CG/Wipro/Century |
| 33 | S & F Energy saving new generation environmental friendly long life versatile presure die cast aluminium IP 66 security light fitting luminaire with high power LEDs as light source and electronic driver of capacity 35 watts with pre wired and necessary mounting arrangements, provision of new 3 core multistranded copper conductor of size 23/0.193 from ceiling rose to fitting and GI pipe bracket made out of GI pipe medium grade 32 mm dia 1.5 mtr long bend to required shape complete incl removal of old unsv fitting all as directed by Engineer-in-Charge. |
| 34 | Supply, installation and commissioning of MCCB controlled, Double door type LT distribution Panel boards, indoor type, factory made, powder coated, G frame panel board, Outgoing TP,3 pole, MCCB, 12 Ways, 415 volts, 50 Hz AC Supply with 02 Nos cable Alley double door type and pre-wired meter module double door with digital Voltmeter, Ammeter, selector switch, CT,s control fuse and indicating lights with the following accessories including PCC foundation all round approximate1.0 Mtr wide and 0.45 Mtr height from ground level housed in complete all as specified and as directed.of Make : Havells, Cat No. IHLG04001200 for enclosure , cat No. ISSBOU0700 for 12 way Cable Ally & cat No.- ISSBOU0707 for digital meter module (to be installed in Sample Preparation Room) Or equivalent make of Standard/L&T/Legrand/ABB/Schneider. |
| 35 | Item No 34.00 continued.............. INCOMING(a) MCCB TPN 4 pole, adjustable thermal and adjustable magnetic type, Ics = 100% of Icu, LE frame, 415 Volts, 400 Amps, 36 KA - 01 No. Make- Havells, Cat No. IHLLSEC40400OUTGOING(a) MCCB 4 pole, fixed thermal and fixed magnetic type, Ics = 100% of Icu, 'GS' frame, 415 Volts, 150 Amps, 25 KA - 04 Nos. Make- Havells, Cat No. IHLGST0150# (b) MCCB 4 pole, fixed thermal and fixed magnetic type, Ics = 100% of Icu, 'GS' frame, 415 Volts, 100 Amps, 25 KA - 06 Nos. Make- Havells, Cat No. IHLGST0100# (c) MCCB 4 pole, fixed thermal and fixed magnetic type, Ics = 100% of Icu, 'GS' frame, 415 Volts, 63 Amps, 16 KA - 02 Nos. Make- Havells, Cat No. IHLGST0063 (d) Digital Voltmeter 0-500 V with selector switch - 01 No.Make- Havells.(e) Digital Ammeter 0-200 Amps with CTs and selector switch - 01 No(f) Indicator lamp (RYB) (set of three) - 01 Set(g) Cable gland for incoming and outgoing. cable.complete all as specified and directed. |
| 36 | Material & Labour for earthing with galvanised steel earth plate electrode of size 60cmx60cmx6mm thick buried directly in ground (earth pit not less than 2.25m deep below the ground level) with top edge of the plate not less than 1.5m below normal ground level, connected to the galvanised earth lead by means of bolts, nuts check nuts and washers of galvanised iron strip of size 32 x 6 mm as earthing lead as shown in electrical plate No. 3 of SSR Part-I connected to earthing test point all as specified or indicated including testing on completion including necessary excavation and earth work in soft/loose soil, returning filling, disposal of surplus soil, earth pit in PCC 1:3:6 type C-1 using 20mm graded stone aggregate pit, funnel, 20mm dia GI medium grade watering pipe, 40mm dia GI medium grade earth lead protection pipe and pre-cast earth pit cover made of RCC (1:1.5:3) type A1 duly reinforced with 8mm dia TMT bar @150 c/c both ways, one lifting handle made of 10mm dia TMT bar embedded in cover slab and cover, wire, copper lugs etc mesh, chorcoal and common salt in alternate layer of 15cm thick complete all as specified and directed. |
| 37 | Material & Labour for earthing with galvanised steel earth plate electrode of size 60cmx60cmx6mm thick buried directly in ground (earth pit not less than 2.25m deep below the ground level) with top edge of the plate not less than 1.5m below normal ground level, connected to the galvanised earth lead by means of bolts, nuts check nuts and washers of galvanised iron wire of size 4 mm dia as earthing lead as shown in electrical plate No. 3 of SSR Part-I connected to earthing test point all as specified or indicated including testing on completion including necessary excavation and earth work in soft/loose soil, returning filling, disposal of surplus soil, earth pit in PCC 1:3:6 type C-1 using 20mm graded stone aggregate pit, funnel, 20mm dia GI medium grade watering pipe, 40mm dia GI medium grade earth lead protection pipe and pre-cast earth pit cover made of RCC (1:1.5:3) type A1 duly reinforced with 8mm dia TMT bar @150 c/c both ways, one lifting handle made of 10mm dia TMT bar embedded in cover slab and cover, wire, copper lugs etc mesh, chorcoal and common salt in alternate layer of 15cm thick complete all as specified and directed. |
| 38 | Supply & fix Earth continuity conductor or main earthing lead fixed to wall on batten or recess or burried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required 4 mm dia galvanized iron or steel wire complete all as specified and directed. |
| 39 | Taking down carefully old unserviceable Ceiling fan/Exhaust fan of any sizes from site for safe custody for refixing.complete all as directed and specified. |
| 40 | Hanging or Refixing of Ceiling Fan/Exhaust fan any size including provision of suitable flexible cable as required from ceiling rose or connector to fan complete all as specified and directed. |
| 41 | S&F heavy duty exhaust fan 300 mm sweep MS body with antidust painting, 4 blade with heavy duty motor and double ball bearing, 1320 RPM, single phase 230/240 volts copper wounds, Air delivery -1600 CMH complete with all accessories as bird guard/ louvers shutters etc incl making connections with 3 core flexible multistranded copper conductor of size 0.75 Sqmm run through flexible pipe all as specified and as directed including cutting holes and making good the disturbed surfaces of walls in CM(1:4) and finishing the surface as per existing color scheme complete all as specified and as drected. |
| 42 | Material & labour for 80mm bore galvanized tube (light grade) with all fittings (if required) laid in road crossing or along poles with clamps for protection of UG cable complete all as specified and directed. |
| 43 | Material & labour for 40mm bore galvanized tube (light grade) with all fittings (if required) laid in road crossing or along poles with clamps for protection of UG cable complete all as specified and directed. |
| 44 | M & L Painting of steel pole (swan neck type or straight type) up to 09 mtr height with cross arms, clamp of any length and shape for LT overhead line/ for street light with two coat of aluminium paint after scraching out old paint, cleaning and exiting surface rust free, preparation of the existing surface, including marking pole numbers in a 15 cm dia yellow circle with number writting with black syenthic paint/ Stricker, including painting strips in alternate from bottom to top with three strips of black syenthatic paint & two strips of Yellow/ Sky blue paint (as per existing pattern through out the circumference of pole, including removing extra wall papdi ,peel off wall papdi by sand paper and making good with putty as per existing thickness and applying one coat of white washing on PCC copping of pole and re-numbering of pole with approved size of letter ( Example - P- 001) with synthetic enamel paint of white colour background and black colour lettering complete all as specified and as directed. |
| 45 | Supply and fixing loop in- loop out junction box, with terminal, IP65 of dimention 182 x 180 x 111 mm made of thermoplastic, locking screw fitted with and including 4 way connectors for 3 phase and neutral incoming/outgoing , mounted in the box, fixing on street pole/rail poles including necessary aluminium clamps, suitable glands, lugs and GI nut and bolt including taking down old unserviceable junction box all as specified and directed. Make - Cape, Model -TK PS 1818-11 or equivalent make of Hansel/Sintex |
| 46 | Supply and fixing rusted/corroted security light bracket made out of GI pipe of light grade 1.6 RMx32mm dia for inserting of light fitting, properly shaped, bended, & fixed on the pole through MS flat by nut,bolt & washer of suitable sizes incl dismantling the old unsv existing one complete all as specified and directed. |
| 47 | Material & labour for Flexible PVC insulated multicore FR PVC sheathed multistranded copper conductor cable of 1.5 Sqmm x 3 core for voltage grade up to 1100 V conforming to IS 694 : 2010 for connection of light fitting from junction box or from over head conductors to fitting complete all as specified and as directed by Engineer-in-Charge. |
| 48 | Supply & fixing in repair LED flood light 100 watt 230 V AC outdoor type with thermal management in multiple optics and equipped with IP66 protection, with impact and corrosion resistant complete with driver and lamp including taking down old U/s light fitting with necessary electrical connections by PVC sheathed copper conductor wire of 3 core x 1.5 Sqmm all as directed and specified by Engr-in-Charge. |
| 49 | Supply and fixing of LED street light epoxy powder coated pressure die-cast aluminium housing with weatherproof gasket for LEDs with lens and control gear compartments, pressure die-cast aluminium frame with heat resistant toughened clear glass fixed with SS screws, input voltage 140-270 Volts, delivering lumen equal to/greater than 6000 lumen, system wattage 60 Watt, Ingress protection IP-66 with all acessories complete incl taking down old unsv street light any type from any hight complete all as specified and directed. (CAT No - ENDURASUDOWNSL60WLED765PASYBOTG OF Make - Havells or equivalent Make of Crompton / Bajaj / Phillips / Century / Wipro) |
| 50 | Excavation in trench n. exc 1.5 mtr wide and n.exc 1.5 mtr depth and getting out of soft/loose soil/brick all as specified |
| 51 | Removing of excavated surplus soil to a distance not exceeding 50 mtr and depositing/ spreading where directed at level of n.exc 1.5 mtr above the starting point.complete all as directed and specified. |
| 52 | Returning filling in spreading, leveling and well ramming in layers n.exc 25 cm thick above the ground level complete all as specified. |
| 53 | Material & labour for sand cushioning for cable protection with dry river sand and punning to provide required cushioning for UG cable all as specified and directed |
| 54 | Supply & fixing bricks well burnt sub class ‘B’ bricks in trenches on cable as cable protection across the length of the cable (width wise) complete all as specified and as directed. |
| 55 | Material and labour for PCC 1:4:8 type D-2 with 40 mm graded aggregate for foundation of pole, stay , panels etc all as specified and directed |
| 56 | Material & Labour for plain cement concrete (1:2:4) B1 type using 20 mm graded coarse stone aggregate for foundation/coping of poles complete all as specified and directed. |
| 57 | Material & Labour for supports, clamps and back plates fabricated from structural steel section, flat strips, etc including nuts and bolts with washers, welding bending cold or hot drilling holes for bolts of any size as indicated / directed and inclusive of preparation of surfaces for one finishing coat of synthetic enamelled paint over a coat of primer complete all as specified and directed . Please Enable Macros to View BoQ information |