| 1 | Distribution wiring in 1.1 KV grade 2x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) partly in 20mm size PVC rigid conduit 'FR' (Precision make) [for ceiling portion only] and in 19mm bore, 3mm thick polythene pipe [for horizontal & vertical run embedded in wall], with 1x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire for ECC, to light/fan/call bell points with Modular type switch (Brand approved by EIC) fixed on Modular GI switch board complete with 2 no. suitable size “Ph & N” copper bar with top cover plate making earthing attachment fixed on wall incl. mending good damages to original finish. [only PVC Rigid Conduit on ceiling and remaining portion concealed]8 Mtr [4(c)/ E-25 ] |
| 2 | Distn. wiring in 22/0.3 (1.5 sqmm) single core stranded 'FR'PVC insulated & unsheathed single core stranded copper wire (Brand approved by EIC) in 19 mm bore, 3 mm thick polythen pipe complete with all accessories embedded in wall to 240 V 6A 5 pin plug point incl. S&F 240 V 6A 3 pin Modular type plug socket & Modular type switch (Brand approved by EIC) incl. S&F earth continuity wire, fixed on 4 Module GI switch board with 3/4 Module top cover plate flushed in wall incl. mending good damages to original finish. 2x22/0.3 (Ph. & N) and 1x22/0.3 as ECCOn Board [ 3 (i) / E- 20 ] |
| 3 | SUB-HEAD 2-- POLYTHENE PIPE & WIRECutting Channel of required size on masonry wall by Electric operated cutting machine incl. supplying & fixing of heavy gauge Polythene pipe of following diameter as per GS.19 mm dia 3 mm thick [ 6 (a)/ E- 3 ] |
| 4 | 25mm dia 3 mm thick [ 7 (a)/ E- 3 ] |
| 5 | Supplying and fixing PVC Rigid Conduit 'FR' [Precision Make] of following sizes on wall, ceiling with saddles and other accessories as required and mending good damages to building works20 mm size [ 7(a)/ E- 16 ] |
| 6 | 25 mm size [ 7(b)/ E- 16 ] |
| 7 | Supplying and Drawing 1.1 KV single core stranded 'FR' PVC insulated & unsheathed single core stranded copper wire(Brand approved by E.I.C) of the following sizes in the 19mm/25mm prelaid polythene pipe/PVC rigid conduit as per GS.3 x (1.5 sqmm) [1(b) / E- 9 ] For 2x6A Plug Point |
| 8 | 2x(2.5 sqmm) + 1x(1.5 sqmm) [ 1(s) / E-9 ] For Computer Boards and 16 A Plug Point |
| 9 | 2x(4 sqmm)+1x (2.5 sqmm) [ 1(v) / E- 9 ] For Gyser Point |
| 10 | 2x (6 sqmm) + 1x (4 sqmm) [ 1(y) / E- 9 ] for SPNDBs |
| 11 | S & F solderless Copper socket by crimping of Copper wires.2.5 sq mm [9(i) / F-5] |
| 12 | 4 sq mm [9(ii) / F-5] |
| 13 | 6 sq mm [9(iii) / F-5] |
| 14 | Supplying & Fixing sheet metal inspection box (16 SWG) of the following sizes(in mm ) flushed in wall & 3 mm thick bakellite cover as per GS175 x 100 x 65 [11(c)/E-4 ,13(c)/E-5] |
| 15 | SUB-HEAD 3- PLUGS & SOCKETS etc.Supplying & Fixing GI Modular Switch Board of the following sizes complete with three no. suitable size Copper bar with holes (for Ph, N & E) fixed on bakelite/Hard Rubber insulator over the MS welded chairs incl. top cover flushed in wall for housing the board after cutting the brick wall incl. making earthing attachment, painting and mending good damages to building works.2 Row 12 Module 1(e)/E-17] |
| 16 | 6 module 1(b)/E-17] |
| 17 | 4 module 1(a)/E-17] |
| 18 | Supplying & Fixing modular type socket /switch (Brand approved by EIC) on existing GI Modular type switch board having top cover plate and making necessary connections as required. 6 A 5-pin modular type three pin socket [4(a)/E-17] |
| 19 | 6 A modular type switch [3(a)/E-17] |
| 20 | 16/20A 5-pin modular type three pin socket [4(b)/E-17] |
| 21 | 16/20 A modular type switch [3(b)/E-17] |
| 22 | SUB-HEAD 4--BDB,PDB,VTPN ETCSupplying and fixing double door Vertical TPN MCB Distribution board for MCCB incomer with IP-42/43 protection, on angle iron frame on wall as per GS as per direction of EIC. 4 Way ( Up to 160 A ) Make - Legrand /Siemens /L&T as approved E.I.C as approved by E.I.C ] [15 / D- 11 ] |
| 23 | Supplying and fixing double door Horizontal TPN MCB Distribution board with IP-42/43 protection, concealed in wall as per GS.( Make - Legrand/Siemens/L&T as approved by E.I.C. )4 Way (Make - Make - Legrand/Siemens/L&T as approved by E.I.C] [ 14 / D- 10 ] . |
| 24 | 6 Way (Make - Make - Legrand/Siemens/L&T as approved by E.I.C] [ 14 / D- 10 ] . |
| 25 | Supplying and fixing double-door SPN MCB Distribution Board with IP-42/43 protection, concealed in wall as per GS.2+8 Way [ Make - Legrand/Siemens/L&T as approved by E.I.C).[ 13 / D- 9 ] |
| 26 | Supplying and fixing MCB SS enclosure with IP-20/30 protection, powder coated provision for two/four pole MCB, concealed in wall after cutting the wall & mending good the damages to original finish incl. painting, connection & provision for earthing attachment2 way [11/D-9] |
| 27 | Supplying and fixing 240/415 V MCB Isolator on din rail of existing DBs and necessary connection as per GS [Make-Legrand/ Schneider/Siemens/ Crabtree/ L&T) as per direction of EIC. ]40 A DP [ 6 / D- 5 ] |
| 28 | 63 A FP [ 6 / D- 5 ] |
| 29 | Supplying and fixing 240/415 V MCB of Breaking capacity 10kA & C characteristics on din rail of existing DBs and necessary connectionas per GS [Make-Legrand/ Schneider/Siemens/Crabtree/L&T) as per direction of EIC. ]6-32 SP [ 7 / D- 6] |
| 30 | 32 A TP [ 7 / D- 6 ] |
| 31 | 63 A TP [ 7 / D- 6 ] |
| 32 | Supplying and fixing 415 V Four Pole MCCB of Breaking capacity 25kA/35kA in existing Vertical DBs including necessary connection as per GS [ Make - Legrand /L&T/Siemens as per direction of EIC.].100 A [10/ D- 8 ] |
| 33 | SUB-HEAD 5-- CABLE & CABLE LAYING Supplying and delivery of following size Armoured cables XLPE/PVC insulated are designed for 1.1 kV Stranded Aluminium conductor, high tensile galvanized steel wire/strip armour for mechanical protection, and PVC/FR PVC outer sheathing power cable of following size. (IS 7098 Part - 1/2011 with Up To Date Amendments.2 Core 6 Sq. mm |
| 34 | 4 Core 16 Sq. mm |
| 35 | 4 Core 50 Sqmm |
| 36 | Laying of cable upto 2 core 25 sqmm on wall/surface incl. S & F MS saddles with earthing attachment in 10 SWG GI (Hot Dip) Wire, making holes etc. as necy. mending good damages and painting [ 2(a)/ F- 1 ] |
| 37 | Laying of cable upto 3/4 core 25 sqmm on wall/surface incl. S & F MS saddles with earthing attachment in 10 SWG GI (Hot Dip) Wire, making holes etc. as necy. mending good damages and painting [ 2(b)/ F- 1 ] |
| 38 | Laying of cable above 3½ core 50 sqmm and upto 3½ core 90 sqmm on wall/surface including S & F MS clams with earthing attachment in 2 x 10 SWG GI (Hot Dip) Wire, making hole etc. as necy., mending good damages and painting [ 2(d)/ F- 1 ] |
| 39 | Laying of one No. cable above 35 sqmm and upto 185 sqmm in underground trench 460mm wide x 760mm average depth, with brick protection on the top of the cable with 8 (eight) Nos. bricks per Mtr. including filling the space between the bricks and cable and also the trenchwith shifted soil, leveling up and restoring surface duly rammed |
| 40 | Supplying and fixing compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry of XLPE/PVC armoured cables as below :2 Core 6 Sq. mm [7(a)/F4 ] |
| 41 | 4Core 16 Sq. mm [7(c)/F4 ] |
| 42 | 4Core 50 Sq. mm [7(c)/F4 ] |
| 43 | Finishing of the XLPE/PVC insulated armoured cable ends by soldering with cable sockets and insulated tapes etc., including supplying sockets, soldering materials, tapes etc. and making connection to switch, BDB and BBC etc.2Core 6 Sq. mm [ 8(b-iii) /F5] |
| 44 | 4Core 16 Sq. mm [ 8(b-xii) /F5] |
| 45 | 4Core 50 Sq. mm [ 8(xvi) /F5] |
| 46 | SUB-HEAD 6 - SUPPLY OF LIGHT FITTINGSLED Industrial Batten light Supplying and delivery of LED Industrial Batten light made of CRCA Sheet Body (Thickness ≥ 0.50 mm) and construction as per relevant IS, along with LED lamp (Opal finish polycarbonate housing withAluminium end-cap) voltage AC 140-270 Volt, freq 50/60 hz,Operating temp range 0o to 40o C, internal surge protection of 2.5 KV(internal) with Short & Open circuit protection , THD < 10% , P. F.≥0.9, IP20, CRI >80, and minimum 40000 Burning Hours (Life projection shall be calculated as per TM-21 methodology), CCT 5700°K /6500°K, and Fixture shall be of relevant BIS standard and trade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing, with Minimum 5 year OEM warranty. All test report except L80 should be from 3rd party NABL accredited Lab as per BIS shall be submitted. (System lumen efficacy ≥115 lm/WattSingle fittings along with S/F of 1 no. 18-20 W LED lamp as per specification |
| 47 | Twin fittings along with S/F of 2 no. 18-20 W LED lamps as per specification |
| 48 | LED Down lighter (COB Type)Supplying, installation, Testing & Commissioning of LED Recessed/ surface Down lighter (Round/ square/ Rectangular) COB with powder-coated pressure Die-cast Aluminium with high-transmission opal PMMA/ polycarbonate/ prismatic diffuser having uniform light distribution and construction as per IS : 10322. The driver rated output wattage should be 10% to 15% higher than lamp rating andefficiency Driver >80%, Operating voltage AC 140-270 Volt,frequency 50/60 hz, Operating temp range 00 to 400 C, internal surge protection of 2.5 KV with Short & Open circuit protection, THD <10% , PF ≥0.9, IP20, CRI >80, life time (LED, Driver & electrical circuitary), of minimum 50000 Burning Hours (Life projection shallbe calculated as per TM-21 methodology) and 70% of initial Lumen maintained till life ends , CCT 3000°K / 4000°K / 5700°K / 6000°K/6500°K, Maximum power consumption should not more than the specified rating and Fixture shall be confirming to relevant BIS standards and trade mark certificate (T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing Complete in all respect and LED Chips of SMD Low to mid-power, as per requirement (LM-80 tested) and necessary inter-connections with 1.5 sq mm FR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM comprehensiveon-site warranty against manufacturing defects including driver and LED module. All test report except L80 should be from 3rd party NABL accredited Lab as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. System lumen efficacy shall be as below System lumen efficacy ≥ 110 lm/Watt 8 - 10 Watt |
| 49 | Supply & Fixing angular batten holder (Anchor) on 75mm dia PVCround block / round bakelite on wall/ceiling as per GS [ 22/D-13 ] |
| 50 | Supply of 14 W LED bulb(Bajaj/CG/Philips/wipro) on existing batten holder. [NS] |
| 51 | SUB-HEAD 7 -FIXING OF LIGHT FITTINGSFixing only single/twin fluorescent light fitting suspended 25 cm bellow the ceiling with 2 No. 20 mm dia EI conduit (14 SWG) supports fixed with “L” type MS clamp whose one side fixed on ceiling with sutable size 4 nos. fastener and other side connected with the conduit with suitable size of bolts and nuts incl. S&F EI conduit, “L” type (125mmx125mm) 6mm thick and 25mm with MSclamps and connecting the length of PVC insulated wire and mending good damages to original finish and painting etc. by 2x24/0.20 mm (1.5sqmm.) flexible copper wire of 1.10 mt. length. [ 17/C-2 ] |
| 52 | Fixing only single/twin LED Batten light fitting complete with all accessories Directly on wall/ceiling as per GS.[ 14d/C-2 ] |
| 53 | Extra for suspension exceeding 25 cm with S&F additional 2 no. 20 mm dia EI conduit (14 SWG) supports & necy. PVC insulated wire and painting etc. as required by 2x24/0.20 mm (1.5sqmm.) flexible copper wire of 1.10 mt. length. [16/C-2] |
| 54 | Fixing only lamp[ 11/C-2 ] |
| 55 | SUB-HEAD 8 -- SUPPLY OF FANSSupply & delivery of 230 V, 50 Hz, single phase, 52 watts, 48\\" (1200 mm)Sweep, speed 320 rpm (minimum), A.C. Ceiling Fan and class of insulation: B, 3 nos. metal (Aluminium alloy) blades, 30 cm long down rod (14 SWG & higher thickness), 2 nos. canopies, safety rope, copper winding, steel/Al body. Power Factor not less than 0.9 and minimum air delivery 210 cu.m/min (minimum), without Regulator including capacitor with safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for compliant to IS 374:2019 and external connections with 1.5 sq.mm FR, PVC insulated copper conductor single core cable and earthing etc. as required. |
| 56 | EXHAUST FANSupply & delivery of 230 V, 50 Hz, single phase, 40 watts , 9\\" (230 mm)Sweep, speed 1350 rpm (minimum), A.C. Exhaust Fan and class of insulation: B, 3 nos. metal (Aluminium alloy) blades, copper winding, steel/Al body. Power Factor not less than 0.9 and minimum air delivery 650 cmh (minimum) including capacitor with safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for compliant to IS 374:2019 and external connections with 1.5 sq.mm FR, PVC insulated copper conductor single core cable and earthing etc. as required |
| 57 | Supply & delivery of 230 V, 50 Hz, single phase, 48 watts, 12\\" (300 mm)Sweep, speed 900 rpm (minimum), A.C. Exhaust Fan and class of insulation: B, 4 nos. metal (Aluminium alloy) blades, copper winding, steel/Al body. Power Factor not less than 0.9 and minimum air delivery 1145 cmh (minimum) capacitor with safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for compliant to IS 374:2019 and external connections with 1.5 sq.mm FR, PVC insulated copper conductor single core cable and earthing etc. as required. |
| 58 | SUB-HEAD 9 -- FIXING OF FANSFixing only ceiling fan complete with blades, canopy, fork, rubber bush etc as per GS [ 21 (a) / C-3 ] |
| 59 | Supplying & Fixing MS fan clamp of two piece type for RCC as per approved specification as per GS. [ 29/D-14 ] |
| 60 | Supply & Fixing 240V, Modular Socket (2 Module) type fan regulator (Step type) ([Legrand-Model Arteror/Myrius or equivalent model of Crabtree/Equivalent make as per direction of E.I.) on existing Modular GI switch board with top cover plate incl. making necy. connections etc. [10/E18] [For Celling Fan] |
| 61 | Fixing only exhaust fan after making hole in wall and making gooddamages and smooth cement finish etc. as practicable as possible and providing necy. length of PVC insulated wire and making connection for exhaust of following diameter:23 cm (9\\") [28(a)/C-4] |
| 62 | 30 cm (12\\") [28(b)/C4] |
| 63 | Supply & Fixing louver shutter on wall with necy. bolts & nuts (6 mmdia x 62 mm long) For GI9 \\" [32(b)/D-14] |
| 64 | 12\\" [32(b)/D-14] |
| 65 | SUB-HEAD 10 --MISCELLANEOUSDismantling the existing damaged defective unuseable electrical Installation materials.(Deployment of 4 nos.Skilled and 4 nos.unskilled man power). |
| 66 | Supplying and fixing of digital time switch (Mk- L&T, 67DDT0) in existing 2 way SS encloser as per direction of EIC. |
| 67 | Supplying and fixing 240V,16A Sheetsteel DPMainSwitches with fuse (Make Havells/Standard/HPL)on flat iron frame on wall etc.[1(a)/D-1] |
| 68 | Supplying and fixing 415V, 32A,TPN SFU (Make-L&T/Havells)with sheet steel enclosure on flat iron/angle iron frame on wall with nuts bolts etc incl. S & F 3 nos. DIN type HRC fuse as per rating.[4(a)/D-3] |
| 69 | Supplying and fixing 415V, 100A,TPN SFU (Make-L&T/Havells)with sheet steel enclosure on flat iron/angle iron frame on wall with nuts bolts etc incl. S & F 3 nos. DIN type HRC fuse as per rating.[4(a)/D-3] |
| 70 | Supplying & fixing medium gauge GI Pipe ( ISI-Medium) Protection with necessary fittings and jointing metarials as required as following size as per GS.50 mm dia [11(d)/F-6] |
| 71 | SUB-HEAD 11- COMPOUND LIGHTLED Street Light fixture, Supplying, installation, Testing & Commissioning of Street light LED fixture powder coated pressure die cast aluminum body finish with corrosion resistance fasteners (SS hardware) & silicon gasket for proper sealing with driver as per the requirement with Driver efficiency >80%, Input voltage: 140-270 Volt AC, freq 50/60 hz, Operating temp range 0o to 50o C and working RH 10%- 90%, internal surge protection of 5 KV internal and external SPD min. 10 KV, L,N,E as per IEC 61000-4-5. The driver rated output wattage should be 10% to 15% higher than lamp rating and at least 2 driver for 200W & above and Driver efficiency >85%, THD < 10% as per IEC 61000-3-2 , P. F.≥0.9, IP- 66, IK-08 specified below, CRI >70, under voltage and over voltage protection, high efficiency lens with type II/III distribution as required with UV stabilized optical lens, life time (LED,Driver & electrical circuitry) of minimum 50000 Burning Hours (Life projection shall be calculated as per TM-21 methodology) and 70% of initial Lumen maintained till life ends. CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect and LED Chips of SMD mid to high-power (2.5 to 4 watt for 200 watt and above, as per required (LM 80 tested) and necessary inter-connections with 1.5 sq mm FR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM comprehensive on-site warranty against manufacturing defects including driver and LED module. All test report except L80 should be from 3rd party NABL accredited Lab as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement.System lumen efficacy shall be as below System lumen efficacy ≥135 lm/Watt 45 Watt |
| 72 | 100 Watt |
| 73 | LED Flood Light fixtureSupplying, installation, Testing & Commissioning of Flood light LED fixture powder coated pressure die cast aluminum body finish with corrosion resistance fasteners (SS hardware) & silicon gasket for proper sealing with driver as per the requirement with Driver efficiency >80%, Input voltage: 140-270 Volt AC, freq 50/60 hz,Operating temp range 0o to 50o C and working RH 10%- 90%, internal surge protection of 5 KV internal and external SPD min. 10 KV, L,N,E as per IEC 61000-4-5. The driver rated output wattage should be 10% to 15% higher than lamp rating and at least 2 driver for 200W & above and Driver efficiency >85%, THD < 10% as per IEC 61000-3-2 , P. F.≥0.9, IP- 66, IK-08 specified below, CRI >70, under voltage and over voltage protection, high efficiency lens with type II/III distribution as required with UV stabilized optical lens, life time (LED,Driver & electrical circuitry) of minimum 50000 Burning Hours(Life projection shall be calculated as per TM-21 methodology) and 70% of initial Lumen maintained till life ends. CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect and LED Chips of SMD mid to high-power (2.5 to 4 watt for 200 watt and above, as per required (LM 80 tested) and necessary inter-connections with 1.5 sq mm FR, PVCinsulated copper conductor single core cable and earthing etc. asrequired with Minimum 5 year OEM comprehensive on-site warrantyagainst manufacturing defects including driver and LED module. All test report except L80 should be from 3rd party NABL accredited Lab as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement.System lumen efficacy shall be as below: System lumen efficacy ≥135 <135 lm/Watt150 watt |
| 74 | Supplying & Fixing GI waterproof type looping cable box size 200x150x100 mm deep having 4 mm thick comprising of one 250 V 15 A kit-kat fuse unit, one NL on porcelain insulator, one compression type brass cable gland for upto 2- core 16 sqmm PVC/A cable and having lined with rubber gasketted GI top cover with brass machine screws etc., earthing terminal with lug, on steel tubular pole near base, including S&F 40x6 mm thick, MS clamps with bolts, nuts etc. including painting with anticorrosive paint[5/H-5] |
| 75 | S & D 1 phase 230V,MF-1 Starter with over load relay for compound light(Make: L & T , MF-1 cat No :SS97227OOCO or equivalent as approved by EIC) [NS] |
| 76 | Fixing only starters (for motor control) on flat iron frame for Direct on Line starter for motor (upto 5 HP) [7(a)/C-1] |
| 77 | Fixing only outdoor / street light type fluorescent light fitting complete with all accessories to be fixed/projected from the wall of the building incl. making holes to building, S&F 40 mm dia GI pipe (ISI-Medium) 1.50 mts. average length, with GI socket at one end and thread at the other end & suitable bend to house the fitting & making necy. connections with S&F necy. length of 1.5 sqmm PVC insulated single core stranded annealed copper wire and making connections as required and mending good damages to wall and paintin (19/C-3) |
| 78 | SUB-HEAD 12 -- EARTHINGEarthing with 50 mm dia GI pipe 3.64 mm thick x 3.04 Mts. long and 1 x 4 SWG GI (Hot Dip) wire (4 Mts. long), 13 mm dia x 80 mm long GI bolts, double nuts, double washers incl. S & F 15 mm dia GI pipe protection (1 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level driven to an average depth of 3.65 Mts. below the ground level [ By TATA-Medium GI pipe] [2(a)/G-1]. |
| 79 | Excavation of soil for installation of Earth Electrode and filling & ramming. (For Soft Soil) [1(a)/G-1] |
| 80 | Extra for providing masonery enclosure on the top of the earth electrode of overall size 86.36 cm x 86.36 cm x 46 cm deep (below ground level) complete with cemented brick work(1:6) of 25 cm width duly plastered with cement mortar (inside) Cl hinged inspection cover of size 36.56 cm x 35.56 cm with locking arrangement, GI reducer including drilling of 46 nos. 12 mm dia holes on the GI pipe. [3(a)/G-2] |
| 81 | Connecting the equipments to earth busbar including S & F Solid GI (Hot Dip) wire of size as below as per GS No.-4 SWG [5(a)(i)/G-2] |
| 82 | No.-10 SWG [5(a)(iv)/G-2] |
| 83 | Supplying & fixing earth busbar of galvanized (Hot Dip) MS flat 25 mm x 6 mm on wall having clearance of 6 mm from wall including providing drilled holes on the busbar complete with GI bolts, nuts, washers, spacing insulators etc. as required [4(a)/G-2] |
| 84 | Add GST @18%:- Rs |
| 85 | Add LWC @1% Rs. Please Enable Macros to View BoQ information |