| 1 | Supply & Installation of floor cum wall mounted cubicle type indoor compartmentalized panel size 9000mm(L) X 1200mm (H) X 350mm (D) or as per requirment , 415V., 50 Hz. dust & moisture proof LT Distribution panel board with following electrical accessories fabricated from 14 SWG CRCA sheet with MS angle frame as required. The base of panel should be made with MS channel & Angle. The panel should have adequate strength & space to accommodate the incoming & outgoing switches and with all interconnection in between the switches and changeover switch with copper flat / flexible wire of suitable capacity. The panel should be provided with cable alley for facilitating connection of all the incoming & outgoing XLPE Cables with termination arrangement by S&F copper terminal stud / bolt of required sizes. The panel with earthing attachment is to be painted with powder coated paint as per direction of EIC. The panel board should consist with the followings:- [ To be installed at New Fire Panel Room] |
| 2 | (A) INCOMER:-415V, 400A 4 pole 36 kA (Uimp=8KV), Ics= 100%Icu MCCB with microprocessor based release having adjustable O/L (0.4 to 1x In or better), Adjustable S/C (1/1.5 - 8/10 Ir), Inbuilt Instantenious protection, Adjustable E/F, Adjustable neutral protection at 50%, 100% , Both side spreader link, extended rotary handle etc. [L&T/Schneider/ABB/Legrand) - 2 Sets. |
| 3 | (B) OUTGOING:-415V, 400A 4 pole On load chanover Switch incl. extended Operating Handle Kit (handle + shaft + center bush + bush clip) etc. [L&T/HPL/C&S) - 1 Set. |
| 4 | (C) METERING:-Digital Multifunction Meter (class 0.5) capable of display of Current, Volt, KWH, PF, MD with date & time stamp etc. with RS-485 port for displaying alongwith 400/5A, max 15 VA,CL:0.5, tape wound CT's for metering with phase indication lamp RYB incl. control circuit MCB (Make- Kappa) for all three phases -- 1 set. |
| 5 | Supply of 3/4 Core XLPE Insulated & Sheathed Armoured stranded Aluminium Conductor cables for Working Voltage up to 1100 Volts of following sizes [Make Polycab / RR /KEI/ Havells/ Gloster as approved by E.I.C] |
| 6 | 4 Core 300 mm² XLPE Ar./ Al. Cable.[(From SS-II DG Panel to New Fire Panel ( 148 Mtrs single run approx.) & SS-OPD Raw Panel to New Fire Panel (262 mtrs single run approx.)] |
| 7 | 3 Core 10 mm² XLPE Ar./ Al. Cable. (From Main timer to compound light). |
| 8 | Laying of two cables above 185 sqmm in an underground trench in single tier formation (horizontal), the trench size : 680 mm x 760 mm average depth, with brick protection on the top of each cable 8 (eight) Nos. bricks per Mtr. and 4 (four) Nos. bricks per Mtr. as separator between the bricks and cables and also trench to be filled up with shifted soil, levelling up and restoring surface duly rammed. |
| 9 | 4 Core 300 mm² XLPE Ar./ Al. Cable. |
| 10 | Laying of one No. cable upto 35 sqmm in underground trench 460 mm wide x 760 mm average depth, with brick protection on the top of the cable with 8 (eight) Nos. bricks per metre, including filling the space between the brick & cable and also the trench with shifted soil, leveling up and restoring surface duly rammed |
| 11 | 4 Core 10 mm² XLPE Ar./ Al. Cable. |
| 12 | Laying of one cable above 150 sqmm and upto 300 sqmm through existing covered masonry trench incl. taking out RC covers, setting them in order, mending good the damages filling the trench with fine dry sand incl. supplying sand. |
| 13 | 4 Core 300 mm² XLPE Ar./ Al. Cable. |
| 14 | Laying of one no.Cable on wall by suitable MS clamp as to GS.. |
| 15 | 4 Core 300 mm² XLPE Ar./ Al. Cable. |
| 16 | 3 Core 10 mm² XLPE Ar./ Al. Cable. |
| 17 | Laying of one no. Cable on existing cable tray as to GS. |
| 18 | 4 Core 300 mm² XLPE Ar./ Al. Cable. |
| 19 | S&F compression type gland for XLPE/Ar cable complete with Brass Gland, Rubber Rings for dust & moistureproof entry of cables incl. finishing the ends by crimping method incl. S & Fixing (Make:Dowells) solderless socket, tapes and jointing materials as per direction of EIC. as per GS. |
| 20 | 4 Core 300 Sq mm |
| 21 | 3 Core 10 Sq mm |
| 22 | S&F Double Door 2+10-Way SPN MCBDB in S.S. enclosure with IP-42/43 protection flushed in wall consisting with 1 No., 63A. DP MCB Isolator, 10 nos., 6/16/32 A. SP MCB as outgoing, complete with DIN Channel, Neutral Bar, Earth Bar and other accessories & connection with suitable size of Cu. wire with proper socketing incl. necsy.earthing attachment.as per GS. (Make :- Legrand /Schneider/Seimens) |
| 23 | Distribution wiring in 2 x 22/0.3 (1.5 sqmm) single core stranded 'FRLSH' PVC insulated & unsheathed copper wire(Havells/Gloster/Polycab/KEI)in 20 mm size PVC rigid conduit 'FR' (Precision/Polycab make, HMS/MMS type), with 1x22/0.3 (1.5 sqmm) single core stranded 'FRLSH' PVC insulated & unsheathed copper wire for ECC, to light/fan/call bell points with Piano Key type switch fixed on MS CRC sheet metal (16 SWG) switch board cum JB (Make:Anchor)on wall complete with 2 no. suitable size “Ph & N” copper bar incl. bakelite/Perspex (wall matching color) top cover 3 mm thick and incl. 175mmx100mmx65mm inspection box, making earthing attachment, painting the MS box and mending good the damages to original finish (Avg Run - 8 Mtrs) |
| 24 | Supply & Fixing 240 V, 20A, plug socket with separate 20 A Piano key type switch (Brand approved by EIC) on sheet metal switch board embedded in wall incl. S & F 150x100x65mm MS (16SWG) switch board and bakelite/perspex top cover of 3mm thick by Brass screws after making housing for switch by cutting bakelite/perspex cover and making necessary connections as required.(Make:Anchor) |
| 25 | Distribution wiring in 1.1 KV single core stranded 'FRLSH' PVC insulated & unsheathed copper wire (Havells/Gloster/Polycab/KEI) in 20mm size PVC rigid conduit 'FR' (Precision/Polycab make, HMS/MMS type) incl. necy. fittings as required |
| 26 | 2 x 2.5 sq.mm.+ 1 x 1.5 sq.mm. (for Power Plug, Sw-soc boards). |
| 27 | Finishing of the PVC insulated wire ends by socketting with pin/ ring type copper sockets (Make : Dowels) and insulated tapes etc., including supplying sockets, tapes. |
| 28 | 2 x 2.5 sq.mm.+ 1 x 1.5 sq.mm. |
| 29 | Supplying & Fixing iron beam fan clamp of two piece type, as per approved specification, fabricated from 40 mm x 9 mm MS sheet flat suitable for beam having flange upto 150 mm wide – (As per Drawing no. 476 of PWD Specification Book – May 1991) |
| 30 | Supply and Delivery of 4 feet Industrial box type single LED tube fitting incl. Supply & Delivery of 1 no. 240V, 20 W LED Tube (Polycarbonate with heat sink)with glare free light distribution with CCT (5000K-6500K) having minimum luminous efficiency of 100 Lm/ Watt or better & 50,000 LED burning hours or more. [Make- Philips/ Wipro/Lighting Technology/ manufacturer with own NABL accredited lab with valid test certificate] [LED lamps & accessories shall have BEE certification] |
| 31 | Supply and Delivery of 4 feet Industrial box type twin LED tube fitting incl. Supply & Delivery of 2 no. 240V, 20 W LED Tube (Polycarbonate with heat sink) with glare free light distribution with CCT (5000K-6500K) having minimum luminous efficiency of 105 Lm/ Watt or better & 50,000 LED burning hours or more. [Make- Philips/ Wipro/Lighting Technology/ manufacturer with ownNABL accredited lab with valid test certificate] [LED lamps & accessories shall have BEE certification] |
| 32 | Supply & Delivery of 230V, 1-Ph, AC ceiling fan of follwing size incl. all accessories. (Make- Crompton / Usha / Orient) [BEE star rated] |
| 33 | Sweep Size- 1200 mm (48\\"), Wattage ≤ 55 Watt, R.PM ≤ 380, Air Delivery ≥ 210 C.M.M |
| 34 | Supply & Delivery of 220V, Single Phase, 50 Hz A.C heavy duty exhaust fan of following sizes having complete metal body. (Make- EPC/ USHA/Orient CROMTON) [ISI mark, IP55 rated] |
| 35 | 300 mm (12\\"), 4 Blade, RPM ≤ 1420 , Wattage ≤ 90 Watt, Sound level ≤ 56 dB, Air Displacement (In CMH) ≥ 1120 |
| 36 | Supply & Delivery of 230V, 50Hz, 450 mm sweep heavy duty full metal body wall bracket fan having wattage ≤ 90 Watt, RPM ≤ 1350, Air Displacement (In CMM) ≥ 100 complete with all accessories. (Make - Orient/Crompton/ EPC) [BEE star rated] |
| 37 | Supply & Delivery of 240V, LED street lights with optic lens and polycarbonatediffuser having following wattage, in white powder coated pressure die cast aluminium housing with IP 66 protection & incl. 10 kV SPD, with glare free uniform illumination with CCT (5700K-6500K) having minimum luminous efficiency of 110 Lm/ Watt or better & 50,000 LED burning hours or more. [Make- Philips/ Wipro/Lighting Technology/ manufacturer with own NABL accredited lab with valid test certificate] [LED lamps & accessories shall have BEE certification] |
| 38 | Fixing only ceiling fan complete with blades, canopy, fork, rubber bush etc. incl. S&F connecting wire for down rod upto 30 cm incl. painting the rod with approved paint and making necessary connection as required by 2x1.5 sqmm flexible copper wire. |
| 39 | Fixing only single/twin fluorescent light fitting complete with all accessories directly on wall/ceiling by screws etc. |
| 40 | Fixing only exhaust fan after making hole in wall and making good damages and smooth cement finish etc. as practicable as possible and providing necy. length of PVC insulated wire and making connection for exhaust of following diameter |
| 41 | 300 mm (12\\") |
| 42 | Supply & Fixing GI sheet (20SWG) metal Cowl with MS flat iron frame & GI wire mesh on wall with necy. bolts & nuts (6 mm dia x 62 mm long) |
| 43 | 300 mm (12\\") |
| 44 | Fixing outdoor type fluorescent/SV/MV light fitting on pole including S&F 40 mm dia x 1.68 mts. long GI Pipe (ISI-Medium)bracket with 40 mmx10 mm thick, MS clamp etc. and providing wiring with 2x1/1.40 PVC insulated & sheathed wire (single core) partly in GI conduit & partly through above bracket from OH line to the fitting, without control switch, incl. making connections and painting |
| 45 | Supplying & Fixing GI waterproof type looping cable box size 200x150x100 mm deep having 4 mm thick comprising of one 250 V 15 A kit-kat fuse unit, one NL on porcelain insulator, one compression type brass cable gland for upto 2- core 16 sqmm PVC/A cable and having lined with rubber gasketted GI top cover with brass machine screws etc., earthing terminal with lug, on steel tubular pole near base, including S&F 40x6 mm thick, MS clamps with bolts, nuts etc. including painting with anticorrosive paint(Make:Sintex) |
| 46 | Earthing with 65 mm dia GI pipe (TATA-Medium)x 3.0 Mts. long and 1 No. 50 mm x 6 mm galvanized (Hot Dip) steel strip (4 Mts. long), 20 mm dia x 125 mm long galvanized bolt, double nuts, double washers including finishing both ends by making holes etc. and S & F 65 mm dia GI pipe (ISI-Medium) protection (3 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level to an average depth of 3.65 Mts . |
| 47 | Extra for providing masonery enclosure on the top of the earth electrode of overall size 86.36 cm x 86.36 cm x 46 cm deep (below Ground level) complete with cemented brick work(1:6) of 25 cm width duly plastered with cement morter (inside) CI hinged inspection cover of size 36.56 cm x 35.56 cm with locking rrangement, GI reducer including drilling of 46 nos. 12 mm dia holes on the GI pipe. |
| 48 | Extra for treatment of soil by using salt & charcoal or coke for plate electrode. |
| 49 | Connecting the equipments body to earth busbar incl. S & F 50 mm x 6 mm Galvanized (Hot Dip) MS flat on wall/floor with GI saddle as required and connection to equipments with incl. drilling holes, bolts, nuts,washers etc. |
| 50 | Defect Liability Period - 1 One) year after completion of work |
| 51 | Make & model of each and every material to be approved by EIC Please Enable Macros to View BoQ information |