| 1 | Servicing &Mtc. of Fire Alarm detection system . Honeywell- Esser make (FACP) fire alarm control panel with notifier make PA system alongwith cable/ wires network in Punjab and Haryana High Court Sector-1, Chandigarh. The details of fire alarm system is as under:- |
| 2 | Main FACP Microprocessor based with minimum 10 loop capacity with 20% spare capacity, having 100% Hot Redundant Intelligent Addressable Fire alarm Panel (In case panel do not have redundancy, vendor needs to supply 100% spare programmed mother board, spare loop cards and network cards for every panel. If vendor is providing more than one panels, than all panel shall be networked peer to peer),with minimum 200 character LCD display & onboard TCP/IP port/External I.P port to access panel on client existing LAN/WAN. Each loop may have a capacity of minimum 125 detectors & devices in one loop, 240 volts AC power supply. (Make:- Honeywell Esser) = 1 no. |
| 3 | Supply, installation, testing and commissioning of Repeater Panel with 160 and above character display (Make:- Honeywell Esser) = 14 nos. |
| 4 | Intelligent Multisensor Detector with integrated fault isolator/ isolator Base. (Make:- Honeywell – Esser) = 1556 Nos. |
| 5 | intelligent analog addressable Heat Sensor/ detector (Including Rate of Rise Temp) with integrated fault isolator/ fault isolator base (Make: Honeywell) = 69 Nos. |
| 6 | addressable manual call point break glass unit with integrated fault isolator. (Makes: Honeywell – Esser) = 151 nos. |
| 7 | Analog Addressable Control modules with integrated fault isolator (Makes:- Honeywell- Esser)= 151 nos. |
| 8 | Addressable Loop Powered multi tone sounder of 80-90 db, with integrated short circuit isolator (Makes:- Honeywell- Esser)= 151 Nos. |
| 9 | Linear Beam Smoke Detector with addressable module having monitoring length 5 to 100m, IP42 protection (Makes:- Honeywell) = 28 Nos. |
| 10 | Response indicator (Makes:- Honeywell – Esser) = 602 Nos. |
| 11 | virtual map software/ Remote Access Software/Web server with license. Make :- Honeywell Flexes Gourd= 1 no. |
| 12 | 2KVA Online UPS, double conversion IGBT based with Dual microprocessor controlled, Static Bypass. = 1 No. |
| 13 | Intel Core i7 PC with original window , 4 GB RAM, 2 TB HDD, Microsoft windows & latest MS office license, 22” LED monitor. (makeHP PRODESK 400 G2). = 1 no. |
| 14 | Digital Audio Amplifier suitable for required no. of speakers for PA system. ( Makes:- Notifier DVC).= 1 No. |
| 15 | fire panel supervised 70 db to 84 db and above wall mounted/ceiling mounted speaker ( Makes:- Notifire).= 342 nos. |
| 16 | 2 way communication fire fighters telephone jack Makes: Notifier FTM-1 = 69 nos. |
| 17 | DSR 28.2.3Supplying, installation, testing & commissioning of repeater panel with 320 character/ Touch screen LCD display with inbuilt reset, acknowledge and silence switches complete as required. |
| 18 | DSR 28.2.4Supplying, installation, testing & commissioning of intelligent analog addressable photothermal detector complete with mounting base complete as required |
| 19 | DSR 28.2.14Supplying, installation, testing & commissioning of addressable manual call point complete as required. |
| 20 | DSR 28.3.7 Supplying, installation, testing & commissioning of digital audio amplifier 75 Watt, 25V rms operating at 240 Volt AC Supply complete as required. |
| 21 | DSR 28.3.4 Supplying, installation, testing & commissioning of ceiling/wall mounted loud speaker, 3/1.5 Watt in ABS enclosure complete as required. Please Enable Macros to View BoQ information |