| 1 | Supply and fix in repairs Network card (Cat No 795-004-001) for Fire Alarm control panel/Active repeater panel of make-Honeywell, fault tolerance the network operates as a true peer to peer system and allow information from any input or output device to be passed over the network and displayed on any axis EN control panel or remote terminal as required complete all as specified and as directed. |
| 2 | Servicing and repairs to intelligent triple IR quad band with visual technology flame detector complete all as specified and as directed. Note : (i) Servicing and cleaning of the item complete. (ii) Checking of all internal components/accessories for their serviceability. |
| 3 | Supply, installation, testing and commissioning in repairs Addressable control module complete all as specified and as directed. Make : Morley IAS- Honeywell/Seimens/Noifier/Bajaj Securiton, UL/FM/CE/LPCB certified |
| 4 | Servicing and repairs to motorised siren \\"Dual Tone\\" of range 2 KM with driving unit installed at technical hangars complete all as specified and as directed. Note : (i) Servicing and cleaning of the item complete. (ii) Checking of all internal components/accessories for their serviceability. |
| 5 | Supply and refilling of NOVEC-1230 fluid in cylinders of fire suppression system installed at various technical buildings complete all as specified and as directed. |
| 6 | Supply and refilling of FM-200 fluid in cylinders of fire suppression system installed at various technical buildings complete all as specified and as directed. |
| 7 | Maintenance and repairs of fire alarm panels Qty 13 Nos installed at various technical buildings once in a quarter complete all as specified and as directed.Note : (i) The work includes 01 service per quarter and all the break down during the contract period to be rectified by the contractor. (ii) Servicing and cleaning of complete fire alarm panels. (iii) Checking of complete internal wiring and carrying out necessary repairs/soldering/lugs etc. (iv) Checking of all internal components/accessories for their serviceability. |
| 8 | Supply only Addressable single loop card for connecting inside panel complete all as specified and as directed. Make : Morley IAS- Honeywell/Seimens/Noifier/Bajaj Securiton |
| 9 | Supply only 12V, 7AH Lead acid battery for connecting inside Panel complete all as specified and as directed. Make : Morley IAS- Honeywell/Seimens/Noifier/Bajaj Securiton |
| 10 | Supply, installation, testing and commissioning in repairs Micro processor based loop driven Intelligent addressable sounders cum strobe inbuilt. The addressable sounder cum strobe shall form part of loop device such that, no additional separate wiring is required. The sounder shall have audible range of 75 dB when heard at a distance of 1 Mtr. The sounder shall be suitable for wall/ceiling mounting shall operate on 24 Volt DC each sounder shall meet the specifications complete all as specified and as directed.Make : Morley IAS- Honeywell/Seimens/Noifier/Bajaj Securiton, UL/FM/CE/LPCB certified |
| 11 | Supply and fix in repairs Addressable manual call point with built in addressable monitor module, restorable type which is suitable for external mounting on polycarbonate box or concealed in metallic box with suitable covering plate . The manual call point will be of 'Pull down' type complete all as specified and as directed.Make : Morley IAS- Honeywell/Seimens/Noifier/Bajaj Securiton, UL/FM/CE/LPCB certified |
| 12 | Supply, installation, testing and commissioning in repairs Intelligent addressable Short Circuit Isolator (Fault Isolation Module) shall be suitable for DIN rail mounting and mounted external device shall display status of Tri colour with Open, short circuit LED status indication for normal, The Device shall be suitable for Loop connectivity. (The FIM shall be considered for every 20/22 devices as the site condition) complete all as specified and as directed.Make : Morley IAS- Honeywell/Seimens/Noifier/Bajaj Securiton, UL/FM/CE/LPCB certified |
| 13 | Supply, installation, testing and commissioning in repairs Response Indicator for multisensor type heat and smoke detector with LED indication enclosed in sturdy box and inscribed as \\"FIRE\\" complete all as specified and as directed.Make : Morley IAS- Honeywell/Seimens/Noifier/Bajaj Securiton, UL/FM/CE/LPCB certified |
| 14 | Supply, installation, testing and commissioning in repairs Microprocessor based Intelligent Addressable multisensor type Heat & Smoke detectors (Combination of Photo electric & thermal sensor) with bases.including fixed on metal junction of size 75x75x50 mm with metal glands and gasket. The detector shall sense fire / smoke and generate alarm if any Fire / smoke occurred in the building. The detectors shall have Two built in LEDs for 360 degree viewing complete all as specified and as directed.Make : Morley IAS- Honeywell/Seimens/Noifier/Bajaj Securiton, UL/FM/CE/LPCB certified |
| 15 | Supply and fix in repair two core PVC cable, FRLS with copper conductor round cable 1.5 Sqmm for including 25mm dia metallic conduit FRLS/FR including all fittings and accessories complete all as specified and as directed. |
| 16 | All same as per item No 15 but size 2.5 sqmm, 4 Core complete all as specified and as directed. |
| 17 | Supply and fix in repair manual call point breakable glass complete all as specified and as directed. |
| 18 | Supply and fix in repairs of Active repeater panel of DIMENSIONS [MM] (H X W X D) 165 x 254 x 50,OPERATING TEMPERATURE +5°C to +45°C,RELATIVE HUMIDITY 5% - 95% non-condensing,Compatible with all Morley-IAS intelligent multiprotocol fire alarm control panels• Connects to RS485 peripheral bus• Active or Passive options• Backlit adjustable alphanumeric display• General status LEDs• Controls for system reset, accept, mute, silencealarms, and self test (active repeater only)• “Access Enable” key-switch on active repeaterMake : Morley-IAS-Honeywell/Seimens/Notifier |
| 19 | Supply and fix in repairs of Duct detector Photoelectric, integrated low-flow technology having Air velocity rating from1.5m/s to 20.3m/sec, Versatile mounting options, square or rectangular configuration, Broad ranges for operating temperature −20°C to 70°C and humidity,0% to 95% complete all as specified and directed. Make : Morley IAS- Honeywell/Seimens/Noifier |
| 20 | Supply laying & testing PVC insulated, PVC sheathed cable galvanized steel strip or wire armoured, electric control cables (Heavy duty) with stranded copper conductor of size 2.5 Sqmm, 4 core, 1100 Volts grade fixed on wall or laid in trenches complete all as specified and directed. |
| 21 | Supply laying & testing PVC insulated, PVC sheathed cable galvanized steel strip or wire armoured, electric control cables (Heavy duty) with stranded copper conductor of size 1.5 Sqmm, 4 core, 1100 Volts grade fixed on wall or laid in trenches complete all as specified and directed. |
| 22 | Supply and fixing cable route indictor made out of 3 mm thick MS Sheet of size 20cm x 15cm duly painted with two coats black paint over a coat of red oxide primer and writing HT/LT cable, direction & size of cable with white paint, mounted on angle iron 40x40x3 mm, angle of height 45cm, (30cm below ground level) duly grouted in PCC block of size 20cmx20cmx15cm including necessary earth works and complete all as specified and directed. |
| 23 | Excavation in trenches not exceeding 1.5 m wide and not exceeding 1.5 m deep for laying of cables, pipes, foundation for poles etc., and getting out in hard/dense soil complete all as specified and directed. |
| 24 | Returning filling in excavated soil upto a depth of 30 cm after riddling of excavated soil (in lieu of sand) for cushioning of cable and refilling of trenches with left over normal excavated soil including spreading, levelling, watering and well ramming in layers complete all as specified and directed. |
| 25 | Removing surplus soil to a distance not exceeding 50 m and depositing where directed at a level not exceeding 1.5 m above the starting point complete all as specified and directed. |
| 26 | Supplying and laying un-reinforced precast concrete cable cover, class LV, Type 1 with peak, size250 mm x 150mm x 40mm complete all as specified and directed. |
| 27 | M & L for boring of holes under roof, pavement, hardstanding by trenchless technology and necessary machine including GI pipe of 50/80/100mm dia suitable for 0.4mpa working pressure complete all as specified and directed. |
| 28 | Supply and laying GI tubing light grade 50mm dia in trenches/fixing on pole /wall/crossing in drain etc.for protection of UG cable complete all as specified and directed. Please Enable Macros to View BoQ information |