| 1 | Taking down copper/ aluminium point wiring of any type (ligh, fan, bell, socket or power etc.) complete with all accessories like switches, sockets, regulators, ceiling roses, light fittings any type,termilnal box etc. for taking credit and making good disturbed surfaces, applying distemper / Emulsions matching to the existing colour / quality of walls / floors / ceiling etc complete all as specified and directed. NOTE-Industrial bldg height approx 30 feets and all T & P arrangements will be done at contractor end. |
| 2 | Taking down carefully all type of sub main wiring any core including batten / conduit and making good to disturbed surface as matching to existing complete all as specified and directed. |
| 3 | M&L for concealed point wiring with 1.5 Sq.mm nominal cross sectional area, single core, 1100 Volts grade, multi stranded, FR-LSH, conforming to IS: 694-1990, PVC insulated, unsheathed copper conductor and including PVC concealed conduit of 20 mm dia or higher, medium grade complete with and including all PVC conduit accessories / fittings, brass screws, washers etc, sunk zinc coated pressed steel terminal box suitable for fixing moduler switches, sockets, regulator etc or with 3mm thick plastic laminated sheet top cover concealed in wall any height with and including continuous green earth wire of size 1.5 Sqmm nominal cross sectional area, single core, PVC insulated multi stranded, FRLS copper conductor cable, unsheathed and connected to common earth and earth dolly including cutting holes in or through the walls, making good to walls, ceiling etc including two coats of white / colour washing / distempering etc to the disturbed surfaces to match complete all as specified and directed for One light/fan/bell/security light/exhaust point wiring controlled by one, one way switch/bell push button. The point wiring shall include the wiring of light/ outlets of any length from the distribution board via switch to the point. |
| 4 | All as described ser item no 3.00 here-in-before but one out let socket point 3pin 5 amps on independent board. |
| 5 | All as described ser item no 3.00 here-in-before but on the same board with other switches |
| 6 | All as described ser item no 3.00 here-in-before but using 2.5 sqmm copper conductor with 2.5 sqmm earth wire for one 15 amps socket outlet on independent board all as directed. |
| 7 | All as described ser item no 3.00 here-in-before but using 4 sqmm copper conductor with 4 sqmm earth wire for one 20 amps socket outlet on independent board all as directed. |
| 8 | M&L for concealed point wiring with 1.5 Sq.mm nominal cross sectional area, single core, 1100 Volts grade, multi stranded, FR-LSH, conforming to IS: 694-1990 PVC insulated, unsheathed copper conductor and in existing PVC/MS concealed conduit or connecting through new caping casing of any size/ dia or higher, medium grade complete with and including all PVC conduit accessories / fittings, brass screws, washers etc, sunk zinc coated pressed steel terminal box 18G suitable for fixing moduler switches, sockets, regulator etc or with 3mm thick plastic laminated sheet top cover concealed in wall any height with and including continuous green earth wire of size 1.5 Sqmm nominal cross sectional area, single core, PVC insulated multi stranded, copper conductor cable, unsheathed and connected to common earth and earth dolly including cutting holes in or through the walls, making good to walls, ceiling etc including two coats of white / colour washing / distempering etc to the disturbed surfaces to match complete all as specified and directed for One light/fan/bell/security light/exhaust point wiring controlled by one, one way switch/bell push button. The point wiring shall include the wiring of light/ outlets of any length from the distribution board via switch to the point. |
| 9 | All as described ser item no 8.00 here-in-before but one out let socket point 3pin 6 amps on independent board. |
| 10 | All as described ser item no 8.00 here-in-before but on the same board with other switches |
| 11 | All as described ser item no 8.00 here-in-before but using 2.5 sqmm copper conductor with 2.5 sqmm earth wire for one 15 amps socket outlet on independent board all as directed. |
| 12 | All as described ser item no 8.00 here-in-before but using 4 sqmm copper conductor and with 4 sqmm earth wire for one 20 Amps socket outlet on independent board all as directed. |
| 13 | M&L for each additional light point with 1.5 sqmm copper conductor on the same switch circuit |
| 14 | M & L for submain wiring with two single core 6 sq mm nominal area with 1100 volt grade confirming to IS 694 (2010) PVC insulated unsheathed FR-LSHcopper conductor with one run of 6 sq mm multi stranded copper conductor cable (FR-LSH) ISI marked for continuous green earth wire drawn in exisitng PVC conduit with all fitting marked including cutting, chasing for conduit and making good to walls, ceiling etc including two coats of white / colour washing / distempering etc to the disturbed surfaces to match complete all as directed.Note:- Two runs of 6 Sqmm Cable and one run of 6 Sqmm cable together in & including PVC conduit shall be measured as one RM. |
| 15 | All as described ser item no 14.00 here-in-before but using two single core 4 sqmm copper conductor and with one single core 4 sqmm earth wire for one 20 Amps socket outlet on independent board all as directed. Note:- Two runs of 4 Sqmm Cable and one run of 4 Sqmm cable together in & including PVC conduit shall be measured as one RM. |
| 16 | M & L for submain wiring with four single core 10 sq mm FR-LSH nominal area for 3 phase & neutral with 1100 volt grade confirming to IS 694 (2010) PVC insulated unsheathed with one run of 10 sq mm multi stranded copper conductor cable (FR-LSH) ISI marked for continuous green earth wire drawn in and in existing PVC conduit (ISI mark) of size 32 mm dia medium grade with all fitting marked including cutting, chasing for conduit and making good to walls, ceiling etc including two coats of white / colour washing / distempering etc to the disturbed surfaces to match complete all as specified and directed.Note:- Four runs of 10 Sqmm Cable and one run of 10 Sqmm cable together in & including PVC conduit shall be measured as one RM. |
| 17 | S&F Modular Switch, 1 module, 10A, AC, 240V, one way ISI Marked complete all as specified and directed.. |
| 18 | S&F Modular Socket, 2 module, 10A, 3 pin combined, AC, 240V, ISI Marked complete all as specified and directed.. |
| 19 | S&F Modular Socket, 2 module, 10A / 16A, 3/5 pin combined, AC, 240V, ISI Marked complete all as specified and directed.. |
| 20 | S&F Modular Switch, 1 module, 16A, AC, 240V, one way ISI Marked complete all as specified and directed.. |
| 21 | S&F Modular Switch, 1 module, 10A, AC, 240V, two way ISI Marked complete all as specified and directed.. |
| 22 | S&F Modular Switch, 1 module, bell switch, AC, 240V, two way ISI Marked complete all as specified and directed.. |
| 23 | S&F Modular Fan Regulator, 1/2 module, 120W, AC, 240V, ISI Marked complete all as specified and directed. |
| 24 | S&F Modular MCB, 1 module, 6-20A, AC, 240V, one way ISI Marked complete all as specified and directed. |
| 25 | S&F 1 module modular blank plate complete all as specified and directed. |
| 26 | S&F modular white/cloured outer plate with inner frame 1/2/3 module suitable for modular switch & board complete incl screw washer etc all as specified and directed. |
| 27 | All as described ser item no 26.00 here-in-before but 4/6 module |
| 28 | All as described ser item no 26.00 here-in-before but 8 module |
| 29 | All as described ser item no 26.00 here-in-before but 12 module |
| 30 | All as described ser item no 26.00 here-in-before but 18 module |
| 31 | S&F in repairs anodised rust proof, 18 SWG, GI box ,flush type of 1/2 module sizes suitable for modular switches and sockets or for piano switch/ sockets etc fixed in wall including taking down existing u/s flush box making good disturbed surfaces, applying distemper / Emulsions matching to the existing colour / quality of walls / floors / ceiling etc complete all as specified & as directed :- |
| 32 | All as described ser item no 31.00 here-in-before but 3 module/4''x4'' |
| 33 | All as described ser item no 31.00 here-in-before but 4 module |
| 34 | All as described ser item no 31.00 here-in-before but 6 module//7''x4'' |
| 35 | All as described ser item no 31.00 here-in-before but 8 module/8''x6'' |
| 36 | All as described ser item no 31.00 here-in-before but 12 module/8''x10'' |
| 37 | All as described ser item no 31.00 here-in-before but 18 module |
| 38 | S&F in repairs 3mm thick mica sheet slotted for mounting piano switch sockets etc including screw ,wahers etc of 5''x5'' size complete all as specified & as directed :- |
| 39 | All as described ser item no 38.00 here-in-before but 8''x5'' |
| 40 | All as described ser item no 38.00 here-in-before but 9''x7'' |
| 41 | All as described ser item no 38.00 here-in-before but 9''x11'' |
| 42 | S&F switch piano flush type,PC, 5A, AC, 240V, one way ISI Marked complete all as specified and directed. |
| 43 | S&F switch piano flush type,PC,15A, AC, 240V, one way ISI Marked complete all as specified and directed. |
| 44 | S&F Bell Push, Flush type, PC,5A, AC, 240V, ISI Marked complete all as specified and directed. |
| 45 | S&F socket outlet flush type, PC, 5A, 3pin, AC, 240V ISI Marked complete all as specified and directed. |
| 46 | S&F socket outlet flush type, 15A,PC 6pin, AC, 240V ISI Marked complete all as specified and directed. |
| 47 | S&F Steped Fan Regulator, PC,2 module, 100W, AC, 240V, ISI Marked complete all as specified and directed. |
| 48 | S&F combination box, 15A,PC, 6pin, AC, 240V complete all as specified and directed. |
| 49 | S&F in repairs lamp holder, angular/ straight ,PVC / Polycarbonate type with batten back plate, AC, 240V, Pin type, ISI marked complete all as specified and directed.. |
| 50 | S&F in repairs modular Power Unit 32 A, 3pin, AC, 240V ISI Marked incl PVC Box complete all as specified and directed.. |
| 51 | S&F in repairs Ceiling rose surface Bakelite 65x50mm, 3 terminals, AC, 240V, ISI Marked complete all as specified and directed. |
| 52 | S&F in repairs Call Bell, AC, 240V, SP, ISI Marked complete all as specified and directed. |
| 53 | S&F 20/25 mm rigid non-metallic PVC conduit inclusive of junction, tees, bends, elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hooks etc concealed in wall,lay in ground complete all as specified and directed. |
| 54 | S & F in repair 36W LED recessed mounted 2'X2' panel light having CRCA sheet housing, PC diffuser, luminous efficacy of 100 lumen/W, CRI > 80, PF ≥ 0.9, CCT 6500K/3000K, independent isolated SMPS based constant current electronic LED driver with THD < 20%,built-in surge voltage protection min 4kV and other safety tests as per IS 15885 (Part-2/Sec-13): 2012, IP 20 protection, input voltage range 140- 270V , input frequency 50- 60 Hz, including electrical connection with 3 core flexible Cu conductor cable of appropriate size from ceiling rose to the fixture complete all as specified and directed . |
| 55 | S & F 20 W surface / wall mounted, 4 feet LED T-5 industrial batten having PC diffuser, luminous efficacy of ≥100 lumen/W, CRI > 80, PF > 0.9, CCT 6500K/3000k, independent isolated SMPS based constant current electronic LED driver with THD < 20%, surge voltage protection 4kA, input voltage range 140- 270 V, input frequency 50- 60 Hz, including electrical connection with flexible Cu conductor cable of appropriate size from ceiling rose to the fixture complete all as specified and directed |
| 56 | S&F in repairs Retrofit polycarbonate diffuser type 20 watt retrofit LED tube rod 4 feet,100Lm/Watt,CRI >80, PF >0.90, operating volatage 140- 240V complete all as specified and directed. |
| 57 | S&F in repairs, Wall mounting focus light with polycarbonate diffuser prewired incl 12/15 Watts LED lamp complete all as specified and directed. |
| 58 | S&F in repairs, Wall mounting fancy / round light fitting with polycarbonate/glass diffuser prewired suitbale for B22 incl 9 Watts LED bulb complete all as specified and directed. |
| 59 | S&F 10/12W LED bulkhead light outdoor IP65 fitting with polycarbonate diffuser complete all as specified and directed. |
| 60 | S&F in repairs, LED 3-in-1 colour temprature decorative mirror light with polycarbonate diffuser 9/12 Watts chrome painted/matt painted body complete all as specified and directed. |
| 61 | S&F in repairs, LED decorative bed light with polycarbonate diffuser 3/5 Watts chrome painted/matt painted metal body,spring type flexible arm, built in on/off switch complete all as specified and directed. |
| 62 | S&F in repairs pressure die-cast alluminium housing 18 Watt LED flush / surface/reccesd mounting down light luminaire powder coated finish in round or square shape with integral electronic driver THD<10% complete all as specified and directed.. |
| 63 | S&F in repairs pressure die-cast alluminium housing 12 Watt LED flush / surface/reccesd mounting down light luminaire powder coated finish in round or square shape with integral electronic driver THD<10% complete all as specified and directed.. |
| 64 | S&F in repairs 45 Watt pressure die cast housing LED bldg security light luminaire IP 66 ingress protection ,Efficacy 100 lm/watt ,built-in surge protection,electronic driver incl suitable OD GI pipe bracket, mounting clamps with nuts, bolts and washers, electrical connection with 3 core flexible Cu conductor cable of appropriate size from ceiling rose/junction box to the fixture complete all as specified and directed . |
| 65 | S&F in repairs 100 Watt pressure die cast LED flood light luminaire IP 65 ,Efficacy 100lm/watt incl suitable OD GI pipe bracket, two nos mounting clamps with nuts, bolts and washers complete all as specified and directed. |
| 66 | S&F in repairs LED POST TOP LANTERN 40 W ,IP-65 including all accessories for fixing complete all as specified and directed |
| 67 | S&F Garden light aluminium casted body , thick acrylic sheet diffuser incl B22 ( warm light) ABS holder cast aluminum spiot in existing pole , 09 Watt B22 bulb and light will be fixed at existing pole complete all as specified and directed. |
| 68 | S&F bollard LED Garden light 10/12W metal powder coated body,upto 800mm,IP65 thick acrylic sheet molded body finished incl pcc foundation excavation etc complete all as specified and directed. |
| 69 | S&F 2-way PVC water proof electrical junction box 150X100X70mm suitable for mounting on garden pole all as specified and directed. |
| 70 | S&F in repairs LED Driver suitable for any make or model LED street light fitting 25 to 60 Watts, 240V complete all as specified and directed. |
| 71 | All as described ser item no 70.00 here-in-before but suitable for 2'x2' ceiling light 36/45 watts |
| 72 | All as described ser item no 70.00 here-in-before but suitable for 12/18 Watts down lighter |
| 73 | S&F 15 watt LED bulb 2 pin B22 base,100 Lumems per watt,PF≥0.9, 180° wide beam angle voltage surge protection 4kV ,6500K/3000K cool white,operating voltage 100-240V complete all specified and directed. |
| 74 | All as described ser item no 73.00 here-in-before but 20 Watts |
| 75 | All as described ser item no 73.00 here-in-before but 9 Watts |
| 76 | S&F sheet metal enclosure double door, single pole and neutral, AC, 240 volts, 4 way, with 200 Amps rated copper bus bar and IP - 43 ,IK08 protection with metal double door and flush to wall including all cutting / chases on wall and making good including two coats of white/colour washing/distempering etc to match the existing disturbed surfaces and taking down the old distribution board of any type complete all as specified and directed . |
| 77 | All as described ser item no 76.00 here-in-before but 06 way |
| 78 | All as described ser item no 76.00 here-in-before but 08 way |
| 79 | All as described ser item no 76.00 here-in-before but 10 way |
| 80 | All as described ser item no 76.00 here-in-before but 12 way |
| 81 | S&F sheet metal enclosure, Triple pole and neutral AC, 415 volts, 04 way, with 200 Amps rated copper bus bar and IP - 43 & IK 08 protection including provision for four pole isolator/MCB as incomer with metal double door and flush to wall including all cutting etc on wall and making good including two coats of white / colour washing / distempering etc to match the existing disturbed surfaces and taking down the old distribution board of any type complete all as specified and directed. |
| 82 | S&F Vertical Loadline sheet metal enclosure double door, Triple pole and neutral (TP&N vertical loadline) AC, 415 volts, 04 way, with 200 Amps rated copper bus bar and IP - 43 & IK 08 protection, including 1 No MCCB of capacity upto 125 Amp and provision for 12 Nos MCB'S inside of DB, with metal door and flush to wall including grouting and cutting in existing wall and making good disturbed surface with two coats of white / colour washing / distempering etc to match the existing one and taking down the old distribution board along with mcb,mccb & fixing back serviceable mcb in new DB of any type complete all as specified and directed. Note:- MCB's will be measured and paid separately as required. |
| 83 | S&F Vertical Loadline sheet metal enclosure double door, Triple pole and neutral (TP&N vertical loadline) AC, 415 volts, 04 way, with 200 Amps rated copper bus bar and IP - 43 & IK 08 protection, including 1 No MCCB of capacity upto 200 Amp and provision for 12 Nos MCB'S inside of DB, with metal door and flush to wall including grouting and cutting in existing wall and making good disturbed surface with two coats of white / colour washing / distempering etc to match the existing one and taking down the old distribution board along with mcb,mccb & fixing back serviceable mcb in new DB of any type complete all as directed.Note:- MCB's will be measured and paid separately as required. |
| 84 | S&F in repairs MCB SP 6 to 32 A, AC, 240V, 10KA, ISI Marked 'B' curve incl thimble complete all as specified and directed. |
| 85 | S&F in repairs MCB SPN 40 to 63 A, AC, 240V, 10KA, ISI Marked 'C' curve incl thimble etc complete all as specified and directed. |
| 86 | S&F in repairs Isolator DP, 40A, AC, 240V, conforming to IEC 60947-3,biconnect terminals thibles etc complete all as specified and directed. |
| 87 | All as described ser item no 86.00 here-in-before but 63A |
| 88 | S&F in repairs Isolator 4P, 63A, AC, 415V, complete all as specified and directed. |
| 89 | All as described ser item no 88.00 here-in-before but 100A |
| 90 | S&F in repairs 1 module SPN metallic enclosure with a two pin and earth plug and socket with one MCB SP 20 Amps complete all as specified and directed. |
| 91 | S&F in repairs, 4 Pole MCCB 63 Amp, 50 Hz, 415 V with rupturing capacity 16KA with Ics=100%Icu,adjustable overload setting incl lugs,nut bolt etc all as per existing make DB complete all as specified and directed. |
| 92 | All as described ser item no 91.00 here-in-before but 100Amps |
| 93 | All as described ser item no 91.00 here-in-before but 125Amps |
| 94 | All as described ser item no 91.00 here-in-before but 160Amps |
| 95 | All as described ser item no 91.00 here-in-before but 200Amps |
| 96 | S&F in repairs PVC sheathed flexible 3 core with multistranded copper conductor of size 2.5 Sqmm, complete all as specified and directed |
| 97 | S&F in repairs copper cable 1.5 Sqmm copper multistandard PVC insulated FR, 1100V grade complete all as specified and directed |
| 98 | S&F in repairs copper cable 2.5 Sqmm copper multistandard PVC insulated FR, 1100V grade complete all as specified and directed |
| 99 | S&F in repairs copper cable 4 Sqmm copper multistandard PVC insulated FR, 1100V grade complete all as specified and directed |
| 100 | S&F in repairs copper cable 6 Sqmm copper multistandard PVC insulated FR, 1100V grade complete all as specified and directed. |
| 101 | S&F 23/76 twin core twisted multistranded copper wire |
| 102 | S&F in repairs, 1100 volts grade heavy duty PVC sheathed stranded Aluminium conductor twin core cable flat or circular of size 06 Sqmm. |
| 103 | S&F in repairs, 1100 volts grade heavy duty PVC sheathed stranded Aluminium conductor twin core cable flat or circular of size 10 Sqmm. |
| 104 | S&F in repairs, incl clamping and fixed to wall / pole / channels/in ground or air XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables with stranded aluminium conductor, 1100 volts grade, 6 Sqmm 2 core incl lugs,thimbles complete all as specified and directed. |
| 105 | All as described Srl item No 104.00 here-in-befor but 10 Sqmm 2 core |
| 106 | All as described Srl item No 104.00 here-in-before but 16 Sqmm 4 core |
| 107 | All as described Srl item No 104.00 here-in-before but 25 Sqmm 3.5 core |
| 108 | All as described Srl item No 104.00 as above here-in-before but 35 Sqmm 3.5 core |
| 109 | Excavation in trenches not exceeding 1.5 m wide and not exceeding 1.5 M depth in soft / loose soil and geting out complete all as specified and directed. |
| 110 | M&L for sand cushioning with dry fine sand including filling, spreading, levelling in layers in cable trench with approved quality of sand for protection of under ground cable complete all as specified and directed. |
| 111 | Supply / laying/ fixing/cutting 40 mm bore galvanised steel tubes with all fittings, light grade, laid in trenches for cable protection,garden light pole by making hole for wire to pass complete all as specified and directed. |
| 112 | Returning, filling in, including spreading, leveling, watering and well ramming in layers n. exc. 25 cm thick in soft / loose soil complete all as specified and directed. |
| 113 | Removing surplus excavated materials n.exc. 50 Mtr and depositing where directed at a level n. exc. 1.5 Mtr above the starting point complete all as specified and directed. |
| 114 | M&L Cement concrete in foundations, filling and mass concrete PCC 1:4:8 D2 type for foundation incl taking down existing one all as specified and directed. |
| 115 | S&F in repairs, connect, tamper proof Electronic KWH meter with LCD display, 1 phase, 5 - 30 A including taking down old unserviceable one and depositing to MES complete all as specified and directed. |
| 116 | S&F in repairs, connect, tamper proof Electronic KWh meter with LCD display, 3 phase, 10 - 60 A including taking down old unserviceable one and depositing to MES complete all as specified and directed. |
| 117 | M&L for earthing complete with galvanised mild steel earth plate electrode 60cmx60cmx6mm thick buried directly in ground (earth pit not less than 2.25mtr deep below ground level) with top edge of the plate not less than 1.5mtr below normal ground level steel earth plate connected with GI wire 04mm dia by means of lug, bolts, nuts, check nuts, washers of galvanised iron or steel GI protection pipe 15mm bore light grade all as shown in elect plate No.3 of SSR part I connecting to main switch board / Main DB’s including excavation, earth work, salt and charcoal dust mixed and packed 150mm thick around GI earth plate, GI pipe medium grade 20mm nominal bore watering pipe GI sheet funnel wire mesh, concrete pit, RCC cover in PCC 1:2:4 type B1 duly reinforced with MS Bars 6mm dia at the rate of 150mm center to centre both way with suitable lifting handle and pit / chamber in PCC 1:3:6 type C1 , for pit cover including testing on completion complete all as specified and directed |
| 118 | S&F in repair BLDC ceiling fan 1200mm sweep 220CMM air delivery,with remote ,BEE 5 star energy rated minimum service value≥6,copper winded motor ,anti rust powder coated aluminium blade,double ball bearing, dynamically balanced including canopy,down rod,shackel assembly,safety pin,nut bolt etc electrical connection with flexible Cu conductor cable of appropriate size from ceiling rose/junction box to the fixture complete incl taking down old u/s one and depositing to MES Storeyard complete all as specified and directed. |
| 119 | S & F, Condensor / Capacitor, 240V, AC, suitable for fans 2.5 mfd complete all as specified and directed |
| 120 | S&F in repair PVC exhaust fan, 250mm sweep with lovers, AC, 230V incl 1200rpm complete all as specified and directed. |
| 121 | S&F in repair PVC exhaust fan, 200mm sweep with lovers, AC, 230V incl 1200rpm all as specified and directed. |
| 122 | S&F in repair metal exhaust fan, 300mm sweep with lovers, AC, 230V incl taking down complete all as specified and directed |
| 123 | S&F in repairs, mosaic style antique wall mounted lamp with glass shade contemporary accent light for indoor spaces , including E27 bulb complete all as specified and directed. |
| 124 | Carrying out electrical maint work of day to day internal electrical complaints such as repairs/rectrification/replacement of defective items ,no light / supply disruption complaints , fault findings etc as per complaints recived in complaint cell register as per ground requirements by providing one skilled electrician for Md accn under GE (N) Meerut AOR complete all as specified and directed. NOTE FOR ITEM No. 122:- (a) Flxtures/fittings shall be paid under relevant item. (b) Materials for repair works as directed by engineer -in-charge shall be supplied by the contractor and adequate stock shall be held all the time by contractor .(c) Contractor shall be penalised @ Rs 200/- per complaint per day, if he fails to attend the complaint within 12 hours. (d) All T&P, safety gears & transportation shall be provided by contractor(e) Rep of the contrractor shall receive complaints in morning 9000 hr on all working day and give feedback on daily basis to concern JE E/M(f) Payment to contractor released after submission of these compaints duly rectified. Please Enable Macros to View BoQ information |