| 1 | Taking down unserviceable copper/aluminium point wiring (light, fan, bell, socket or power) complete, including fixture and fittings(Modular / Non Modular) such as switches, ceiling roses, pendants, regulators, sockets, light fitting etc. removing materials to store for keeping in safe custody or for taking credit (credit for above items should be made as per conditions separately) and making good disturbed surfaces of walls, floors, etc complete all as specified and as directed. |
| 2 | Taking down unserviceable light fittings of any type any capacity complete all as specified and as directed. |
| 3 | Taking down unserviceable old aluminium sub main wiring of any size any type complete all as specified and as directed |
| 4 | Taking down unserviceable fuse Unit/DBs, 415 Volt/230 Volt of any type any size complete all as specified and as directed |
| 5 | Taking down old unserviceable MCB/MCCB of any capacity any type complete all as specified and as directed |
| 6 | Taking down unserviceable Earhting of any type complete all as specified and as directed |
| 7 | M & L for point wiring for one light/ fan point/exhaust fan point/ bell point controlled by one 5 Amp switch with 1100 volt grade PVC insulated-unsheathed 1.5 Sq mm multi stranded FRLSH copper conductor cable with continuous earth wire of 1.5 Sq mm multi stranded FRLSH copper conductor cable PVC insulated-unsheathed, drawn in & including PVC casing caping/ surface non metallic PVC conduit of size 20mm dia non metallic PVC medium grade with fittings (ISI marked) & sunken anodized pressed steel sheet boxes made out of not less than 1.6 mm thick sheet, covered with 2.8 mm thick laminated insulated cover make sheet for housing/fixing switches etc complete all as specified and directed. Note : Proper coding to be adopted. |
| 8 | All as per item No.07 here in before but one 3 pin 5 Amp switch socket outlet on independent board complete all as specified and as directed |
| 9 | All as per item No.07 here in before but one 3 pin 5 Amp switch socket outlet on same board with accessories complete all as specified and as directed |
| 10 | All as per item No.07 here-in-before but one 16A socket point controlled by one 16A switch on independent board with 2.5 sqmm wires complete all as specified and as directed |
| 11 | All as per item No. 7 here-in-before but one 16A socket/16 A earth plug point controlled by one 16A switch /20A MCB on independent board for ac with 4.0 sqmm wirescomplete all as specified and as directed |
| 12 | M&L Point wiring with 1.5 Sqmm (Nominal area) FRLSH PVC insulated and unsheathed single core cable 1100 volts grade with stranded copper conductor in existing conduit along with contineous earth wire 1.5 Sqmm FRLSH PVC insulated , unsheathed stranded copper conductor cable and connected to common earth dolly, with and including 1.6mm cadmium plated sunk MS pressed steel terminal boxes with 3.0 mm thick hylum sheet cover ISI marked fixed with brass screw complete with all accessories for one light/fan/bell point controlled by one 5 Amps single pole one way switch complete all as specified and as directed |
| 13 | All as per Item No.12 mentioned here-in-before but one 3 pin 5 Amps socket outlet on same board controlled by one, one way 5 Amps piano switch complete all as specified and as directed |
| 14 | All as per Item No.12 mentioned here-in-before but one outlet 5/3 pin 5 Amps socket outlet on independent board controlled by one, one way 5 Amps piano switch complete all as specified and as directed |
| 15 | All as per item No. 12 here-in-before but one 16A socket point controlled by one 16A switch on independent board with 2.5 sqmm wires complete all as specified and as directed |
| 16 | M & L for point wiring for one light/ fan point/call bell controlled by one switch with 1100 volt grade PVC insulated FRLSH 1.5 Sq mm multi stranded copper conductor cable with continuous earth wire of 1.5 Sq mm multi stranded copper conductor cable PVC insulated-unsheathed, drawn in & including concealed rigid non metallic PVC conduit medium grade with fittings (ISI marked) not less than 20 mm dia & sunken anodized pressed sunken boxes made out of not less than 1.6 mm thick sheet, covered with 2.8 mm thick laminated insulated cover make sheet for housing/fixing switches etc complete all as specified and directed. |
| 17 | All as per item No 16 above but 1.5 Sq mm for 5 Amp socket outlet on same board with 1.5 Sq mm earth wire complete all as specified and as directed |
| 18 | All as per item No 16 above but 1.5 Sq mm for 5 Amp switch socket on independent board with 1.5 Sq mm earth wire complete all as specified and as directed |
| 19 | All as per item No. 16 here-in-before but one 16A socket point controlled by one 16A switch on independent board with 2.5 sqmm wires complete all as specified and as directed |
| 20 | All as per item No. 16 here-in-before but one 16A socket/16 A earth plug point controlled by one 16A switch /20A MCB on independent board for ac with 4.0 sqmm wires complete all as specified and as directed |
| 21 | S&F in repair switch piano Flush type, single pole, one way 6 amp 240 volts, complete all as specified and as directed. |
| 22 | S&F switch piano Flush type, single pole16 amp 240 volts, complete all as specified and as directed. |
| 23 | S&F Socket outlet 2 in 1, 3 pin, 5 Amps, flush type complete all as specified and as directed. |
| 24 | S&F Socket outlet 2 in 1, 3 pin, 15/16 Amps, flush type complete all as specified and as directed. |
| 25 | S&F Switch socket combination 2 in1, 3 pin,5 Amps flush type,universsal complete all as specified and as directed. |
| 26 | S&F Switch socket combination 2 in1, 3 pin,15/16 Amp flush type,universsal complete all as specified and as directed. |
| 27 | S&F switch modular single pole one way 6 amp 240 volts,1 Module complete all as specified and as directed |
| 28 | S&F switch modular single pole one way 16 amp 240 volts,1 Module complete all as specified and as directed |
| 29 | S&F Modular socket 6A - 2/3 pin combined 2 module, complete all as specified and as directed |
| 30 | S&F Modular socket 16A- 2/3 pin combined 2 module, complete all as specified and as directed |
| 31 | S&F Modular Bell Push 6 Amp , One module complete all as specified and as directed. |
| 32 | S&F bell push flush type 5 amp AC 230 volts, single pole complete all as specified and as directed |
| 33 | S&F Bell electric, Ding Dong AC 230 Volts, single pole complete all as specified and as directed. |
| 34 | S&F five stepped type modular fan regulator ,120 W, 1/2 module complete all as specified and as directed |
| 35 | S&F Stepped type electronic fan regulator flush type on the existing phenolic laminated sheet complete all as specified and as directed. |
| 36 | S&F ceiling rose 3 terminal / PVC/ Polycarbonate, isolated body complete all as specified and as directed |
| 37 | S&F Plug top 15A 240V complete all as specified and directed complete all as specified and as directed |
| 38 | Supply and fixing building security lights with new generation energy saving & environment friendly long life versatile pressure die-cast aluminium IP65/66 roadway luminaries with high power LEDs as light source & exclusively designed polycarbonate cover alongwith electronic driver type street light fitting 35 watt capacity LED and including all accessories duly pre-wired, fixing on existing bracket with nut, bolts & washers as required at site for fixing of street light on wall complete including taking old building security lights fitting any type and description complete all as specified and directed. |
| 39 | S&F in repair of bracket made of GI light grade pipe 1.2 Mtr long of size 40 mm bore bend to shape as per site requirement fixed to pole/wall with 40 x 5 MM -02Nos, size clamps bolts, Nuts, washers including painting two coats of aluminium paint over a coat of primer on exposed surface of mild steel surface all as specified and directed by Engr in Charge. |
| 40 | S&F in repair decorative wall light LED 15 watt globe (conical shape) made up of high grade unbreakable polycarbon material specified and directed. |
| 41 | S & F in repair Single pole and neutral enclosure with a two pin and earth plug and socket complete with one single pole MCB 20 Amp complete all as specified and as directed. |
| 42 | S&F in replacement of old unserviceable twin core of flexible wire of size 23/0.0076 with PVC medium grade pipe 20mm dia for connection of post top lantern fitting from one junction box to other junction box complete all as specified and directed at site. |
| 43 | S&F in replacement of double door SPN DBs sheet steel, powder coated DBs suitable for MCBs fitted with bus bar, neutral link earth bar and din rail Single phase and neutral confirms to IS : 13032-1991DB, 240 Volts suitable amps rated busbar 4 way complete all as specified and directed by Engr-in-charge. |
| 44 | S&F in replacement of double door SPN DBs sheet steel, powder coated DBs suitable for MCBs fitted with bus bar, neutral link earth bar and din rail Single phase and neutral confirms to IS : 13032-1991DB, 240 Volts suitable amps rated busbar 8 way complete all as specified and directed by Engr-in-charge. |
| 45 | S&F in replacement of double door SPN DBs sheet steel, powder coated DBs suitable for MCBs fitted with bus bar, neutral link earth bar and din rail Single phase and neutral confirms to IS : 13032-1991DB, 240 Volts suitable amps rated busbar 12 way complete all as specified and directed by Engr-in-charge. |
| 46 | S&F in repair 240V, 10KA 'B' curve miniature circuit breaker (MCB) of single poles and neutral (SPN) and current carrying capacity 32 Amp in the MCB DB with connection testing and commissioning complete all as specified and as directed. |
| 47 | S&F in repair 240V, 10KA 'B' curve miniature circuit breaker (MCB) of single poles (SP) and current carrying capacity 6 to 32 Amp in the MCB DB with connection testing and commissioning complete all as specified and as directed. |
| 48 | S & F in repair MCCB, 4 pole, 415 V, fixed type, 63 to 125 Amps with breaking capacity 16 kA, duly ISI marked, complete all as specified and as directed. |
| 49 | S&F in repair MCB DB TPN 4 way vertical type with suitable Amp rating 415 V rated copper busbar in sheet steel enclosure, double door type, complete all as specified and as directed. |
| 50 | Supply and fixing 415V 10KA 'B' curve TPN/FP 40 to 100 Amp capcity in the DB complete with connection testing and commissioning complete all as specified and as directed |
| 51 | S&F in repair LED bulb of capacity 10 watts lumen out put (950 lm) length 102 mm, dia 56 mm, base cap B22, (ISI marked) complete with all accessories (ISI marked) all as specified & directed |
| 52 | S&F Inveter LED bulb of capacity 12 watts lumen out put (1200) length 140 mm width 70 mm base cap B22 ,3 star, (ISI marked) complete with all accessories base (ISI marked) all as specified & directed. |
| 53 | S&F in repair Lamp holder, PVC/Polycarbonate type with back plate having matching colour to holder suitable for angle/batten fittings (ISI marked) complete all as specified and directed. |
| 54 | S&F in repair LED light fitting 1X10W bulkhead luminaires including LED light driver holder connecting up with three core flexible copper conductor cable of suitable size complete all as specified and as directed. |
| 55 | S&F in repair of LED tube lights fitting 1x 20W, 220V, LED warm tube light batten connecting up with three core flexible copper conductor cable of suitable size from ceiling rose complete all as specified and as directed by Engr in Charge. |
| 56 | S&F in repair of LED tube light fitting with high out put diffuser 2 feet, 10 watt 220 V AC decorative type with driver holder and LED lamp including connecting up with three core flexible copper conductor cable of suitable size complete all as specified and as directed by Engr in Charge. |
| 57 | S&F in repair round/square shape 15 watt 220 volts AC recessed type with high efficiency PMMA diffuser soft glare free light complete with drivers, holders, LED lamp suitable for roof ceiling including connecting up with three core flexible copper conductor cable of suitable size complete all as specified and as directed |
| 58 | S&F in repair LED luminaries 600 mm x 600mm, 35/36 watt, 220 V AC recessed type with high efficiency PMMA diffuser soft glare free light complete with driver, holders & LED lamp suitable for roof ceiling including connecting up with driver three core flexible copper conductor cases of suitable size complete all as specified and as directed |
| 59 | S&F in repair of LED tube wall light fitting with high out put diffuser warm white of size 35.5L x 7W x 13.5W Centimeter, 7 watt 220 V AC decorative type with driver holder polycarbonate silver color including connecting up with three core flexible copper conductor cable of suitable size complete all as specified and as directed by Engr in Charge. |
| 60 | M & L Sub main wiring two single core 6.0 Sqmm PVC insulated FRLSH multistanderd copper conductor cable and one run of 6.0 Sqmm PVC insulated unsheathed FRLSH multi stranded copper conductor cable for earth wire drawn in & including concealed rigid non metallic PVC conduit medium grade with fittings (ISI marked) not less than 20 mm dia, complete and making good disturbed surface wall taking down of existing submain wiring complete all as specified and as directed. Note : - Not : 2 runs of 6 Sqmm cable and 1 run of earth wire 6 sqmm and one run of PVC conduit shall be measured as one unit length. |
| 61 | M & L Sub main wiring two single core 6.0 Sqmm PVC insulated FRLSH multistanderd copper conductor cable and one run of 6.0 Sqmm PVC insulated unsheathed FRLSH multi stranded copper conductor cable for earth wire drawn in existing surface/recessed PVC conduit complete and making good disturbed surface wall taking down of existing submain wiring complete all as specified and as directed. Note : - Not : 2 runs of 6 Sqmm cable and 1 run of earth wire 6 sqmm shall be measured as one unit length. |
| 62 | M & L Sub main wiring four single core 6.0 Sqmm PVC insulated FRLSH multistanderd copper conductor cable and one run of 6.0 Sqmm PVC insulated unsheathed FRLSH multi stranded copper conductor cable for earth wire drawn in & including existing surface/recessed PVC conduit PVC conduit medium grade with fittings (ISI marked) not less than 20 mm dia, complete and making good disturbed surface wall taking down of existing submain wiring complete all as specified and as directed. Note : - Not : 4 runs of 6 Sqmm cable and 1 run of earth wire 6 sqmm and one run of PVC conduit shall be measured as one unit length. |
| 63 | S&F 1100 V grade heavy duty service cable with pvc insulated aluminium conductor served with an inner sheathing of pvc tape and overall pvc sheathed in service connection suspended by insulating hangers not more than 1mtr apart including 4mm suspension wire one twin core cable flat or circular of size 10 sqmm taking down of existing service cable all as specified and directed |
| 64 | S&F in repair Rigid non-metallic PVC conduit exclusive of boxes (junction/ terminal) but inclusive of all tees, bends, elbows, reducers, bell mouth tube ends and such as couplers, lock nuts, saddles, pipe hooks etc complete all as specified and as directed |
| 65 | S&F in repair of 3mm thick phenolic laminated hylam sheet of size 9\\" X 11\\" including necessary cutting, drilling holes for fixing of switches, sockets & fan regulators etc and fixing the hylam sheet on existing metal flush box with new brass/GI screws and washers complete all as specified and directed.Note: S&F of switches, sockets & regulators shall be measured and paid separately. |
| 66 | S&F in repair of 3mm thick phenolic laminated hylam sheet of size 8\\" X 5\\" including necessary cutting and drilling holes for fixing of switches, sockets & fan regulators etc as per site requirement and fixing the hylam sheet on existing metal flush box with new brass/GI screws and washers complete all as specified and directed. Note: S&F of switches, sockets & regulators shall be measured and paid separately. |
| 67 | S&F in repair of 3mm thick phenolic laminated hylam sheet of size 5\\" X 5\\" including necessary cutting and drilling holes for fixing of switches, sockets & fan regulators etc as per site requirement and fixing the hylam sheet on existing metal flush box with new brass/GI screws and washers complete all as specified and directed Note: S&F of switches, sockets & regulators shall be measured and paid separately. |
| 68 | S & F of Starter switch of capacity 25 amps, working on 240 volts AC supply, suitable for air conditioner complete all as specified and directed |
| 69 | M&L in repairs for Earthing complete with galvanized steel earth plate electrode 600mm x 600mm x 6 mm thick buried directly in ground (earth pit not less than 2.25 m deep below normal ground level) with top edge of the plate not less than 1.5 m below normal ground level connected to galvanized earth wire of 4 mm dia (up to 7.5 m in length from earth plate ) by means of bolts and nuts check nuts and washers of galvanized iron or steel all as specified and shown in electrical plate no.3 of SSR part I including necessary excavation and earth work in any type of soil PCC 1:3:6 type C1 chamber with RCC 1:2:4 type B1 40 mm thick cover with MS rod 8mm dia at 150mm c/c in both ways as reinforcement, watering funnel, 20 mm dia light grade for protection of earth electrode, 20 mm dia GI pipe light grade for watering complete all as specified and as directed by Engineer in charge and tested on completion. Note : The rate is inclusive of necessary earth work, returning, filling in and removal etc all as specified and directed. |
| 70 | M&L in repairs for Earthing complete with galvanized steel earth plate electrode 600mm x 600mm x 6 mm thick buried directly in ground (earth pit not less than 2.25 m deep below normal ground level) with top edge of the plate not less than 1.5 m below normal ground level connected to galvanized earth wire of 32x6 mm dia (up to 7.5 m in length from earth plate ) by means of bolts and nuts check nuts and washers of galvanized iron or steel all as specified and shown in electrical plate no.3 of SSR part I including necessary excavation and earth work in any type of soil PCC 1:3:6 type C1 chamber with RCC 1:2:4 type B1 40 mm thick cover with MS rod 8mm dia at 150mm c/c in both ways as reinforcement, watering funnel, 20 mm dia light grade for protection of earth electrode, 20 mm dia GI pipe light grade for watering complete all as specified and as directed by Engineer in charge and tested on completion. Note : The rate is inclusive of necessary earth work, returning, filling in and removal etc all as specified and directed. |
| 71 | Disconnection/taking down aluminium strip any size complete all as specified and as directed. |
| 72 | Re-fixing in repair for aluminium strip 25 X 3.15 mm with saddles, DNB insulator and fixing screws washer etc for roof conductors and down conductors above ground complete all as specified and as directed. |
| 73 | S&F aluminium strip 25 X 3.15 mm with saddles, DNB insulator and fixing screws washer etc for roof conductors and down conductors above ground complete all as specified and as directed. |
| 74 | S&F in repair for Test point terminal block of size 175 mm x 120 mm x 80 mm made out of 2.0 mm thick hot dip galvanisied sheet drilled and screwed including 4 Nos 125 mm long hexagonal head screwed with test point terminal block made of gun metal or phosphorus bronze size 75x75x25mm drilled and screwed including 3 nos. 8mm dia 25mm long hex. head screw complete all as specified and as directed. |
| 75 | Disconnection/taking down Air termination any size complete all as specified and as directed. |
| 76 | S&F Air termination, single pointed aluminium rod 12mm dia and 300mm long with DNB insulators complete all as specified and as directed. |
| 77 | S&F Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required 25 x 4 mm dia galvanised iron strip including necessary clamps, nuts, bolts, DNB insulators & hylem sheet block complete all as specified and as directed. Please Enable Macros to View BoQ information |