| 1 | Supplying and fixing double door Horizontal TPN MCB Distribution board with IP-42/43 protection, concealed in wall after cutting the wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment [D-10/14] |
| 2 | a) 6 Way Enclosure [Make: Legrand Enclosure (607716) or equivalent model of Siemens/Crabtree/L&T as approved by E.I.C] |
| 3 | Supplying and fixing double-door SPN MCB Distribution Board with IP-42/43 protection, concealed in wall after cutting the wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment. |
| 4 | a) 2+14 way Enclosure [Make: Crabtree Enclosure (DCDKSHODCW16) or equivalent model of Legrand/Siemens/L&T as approved by E.I.C] [D-9, D-10/13] |
| 5 | b) 2+10 way Enclosure [Make: Crabtree Enclosure (DCDKSHODCW12) or equivalent model of Legrand/Siemens/L&T as approved by E.I.C] [D-9, D-10/13] |
| 6 | Supplying and fixing 240/415 V MCB Isolator on din rail of existing DBs and necessary connection. (Make: Legrand /Siemens/ Crabtree/L&T as approved by E.I.C) [D-5/6] |
| 7 | (a) 63Amp FP Isolator |
| 8 | (b) 40 Amp DP Isolator |
| 9 | Supplying and fixing 240/415 V MCB of Breaking capacity 10kA & C characteristics on din rail of existing DBs and necessary connection. (Make: Legrand /Siemens/ Crabtree/L&T as approved by E.I.C) [D-6/7] |
| 10 | (a) 6-32 Amps SP MCB [D-6/7] |
| 11 | Supplying and fixing double door sheet steel (16SWG), powder coated cable end box for TPN DB horizontal enclosure with IP-42/43 protection, on angle iron frame on wall & mending good the damages to original finish with nuts bolts etc incl. provision for earthing attachment [D-12/16] |
| 12 | a) 6 way [D-12/16] |
| 13 | Distribution wiring in 1.1 KV grade 2x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) partly in 20mm size PVC rigid conduit 'FR' (Precision make) [for horizontal run & above false ceiling portion only] and in 19mm bore, 3mm thick polythene pipe [for vertical run embedded in wall], with 1x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire for ECC, to light/fan/call bell points with Modular type switch (Legrand: Myrius/Arterior or equivalent model of Crabtree/ROMA as approved by E.I.C) fixed on Modular GI switch board complete with 2 no. suitable size “Ph & N” copper bar with top cover plate making earthing attachment fixed on wall incl. mending good damages to original finish. [PVC Rigid Conduit only for horizontal run & above false ceiling and vertical run concealed] [E-25/5] |
| 14 | a) Average run 10 mtr [E-25/5(g)] |
| 15 | b) On Board [E-24/3(a)] |
| 16 | Supplying and fixing PVC 25mm casing-capping [Precision Make] onwall or ceiling, incl. necy. PVC fittings etc. and mending good damages to building works[E-13/10)] 25x10mm size. |
| 17 | Cutting channel of 40 mm x 40 mm size on masonry wall incl. S&F heavy gauge polythene pipe dia as stated below, by means of iron hooks and supplying and drawing 18 SWG GI Wire as fish wire incl. mending good damages to building works |
| 18 | 19 mm dia 3 mm thick polythene pipe with 1x14 SWG GI earth continuity wire[E-2/3(b))] |
| 19 | Supplying and Drawing 1.1 KV single core stranded 'FR' PVC insulated & unsheathed single core stranded copper wire (Brand approved by EIC) of the following sizes in the prelaid polythene / PVC rigid pipe and by the prelaid GI fish wire and making necy. connection as required [E-9/1] |
| 20 | i) 3 x 22/0.3 (1.5 sqmm) [E-9/1(b)] |
| 21 | ii) 2 x 36/0.3 (2.5 sqmm) + 1 x 22/0.3 (1.5 sqmm) ECC [ E-9/1(s)] [Computer Point and Power Point] |
| 22 | iii) 2x56/0.3 (4 sqmm) + 1x36/0.3 (2.5 sqmm) as ECC [ E-9/1(v)] [1.5Tr. And 2 Tr. Ac point] |
| 23 | iv) 2x84/0.3 (6 sqmm) + 1x56/0.3 (4 sqmm) as ECC[E-9/1(y)] [PDB to SPN DB] |
| 24 | Supplying and fixing PVC Rigid Conduit 'FR' [Precision Make] of following sizes on wall, ceiling with saddles and other accessories as required and mending good damages to building works [E-16/7] |
| 25 | a) 20mm size [E-16/7(a)] |
| 26 | Finishing of the PVC insulated wire ends by socketting with pin/ ring type copper sockets and insulated tapes etc., including supplying sockets, tapes. [F-5/9] |
| 27 | i) 1.5 sqmm |
| 28 | ii) 2.5sqmm [F-5/9(i)] |
| 29 | iii) 4 sqmm [F-5/9(ii)] |
| 30 | iv) 6 sqmm [F-5/9(iii)] |
| 31 | Supplying & Fixing GI Modular Switch Board of the following sizes complete with three no. suitable size Copper bar with holes (for Ph, N & E) fixed on bakelite/Hard Rubber insulator over the MS welded chairs incl. top cover flushed in wall for housing the board after cutting the brick wall incl. making earthing attachment, painting and mending good damages to building works. [E-17/1] |
| 32 | i) 2 Row 18 Module [E-17/1(f)] |
| 33 | ii) 4 Module [E-17/1(a)] |
| 34 | iii) 6 Module [E-17/1(b)] |
| 35 | Supply & Fixing 240 V 6 A Modular type switch (Legrand: Myrius/Arterior or equivalent model of Crabtree/ROMA approved by EIC) on existing GI Modular type switch board having top cover plate and making necessaryconnections as required. [E-17/3(a)] |
| 36 | Supply & Fixing 240 V 16 A Modular type switch (Legrand: Myrius/Arterior or equivalent model of Crabtree/ROMA approved by EIC) on GI Modular type switch board having top cover plate and making necessary connections as required [E-17/3(b)] |
| 37 | Supply & Fixing 240 V, 6A, 5 pin Modular type plug socket (Legrand: Myrius/Arterior or equivalent model of Crabtree/ROMA approved by EIC), without switch & plug top, on existing GI Modular type switch board with top cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc. [E-17/4(a)] |
| 38 | Supply & Fixing 240 V, 6/16 A, 5 pin Modular type plug socket (Legrand: Myrius/Arterior or equivalent model of Crabtree/ROMA approved by EIC), without plug top and switch, on existing GI Modular type switch board with top cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc. [E-17/4(b)] |
| 39 | Supply & Fixing 240 V, 25 A, Modular type starter (Brand approved by EIC) with 25A Modular switch type DP MCB (CCurve) and 4 Module GI Modular type switch board with 4 Module top cover plate flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc. [E-19/17] |
| 40 | Supply & Fixing 240 V, 25A Modular switch type SP MCB (C-Curve) (Brand approved by EIC) on existing GI Modular type switch board with top cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc.(E-19/19(a)) |
| 41 | Supply & Fixing 240 V, 16 A, 3 pin Modular type plug socket with 16A Modular type switch of grey/brown/other colour as approved by the authority/E.I.C (Legrand: Myrius/Arterior or equivalent model of Crabtree/ROMA approved by EIC), without plug top on 4 Module GI Modular type switch board with top cover plate flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc. [E-18/9(b)] |
| 42 | Supplying & Fixing 240 V AC/DC superior type Ding-Dong Call Bell (Anchor) on HW board incl. S&F HW board [D-13/20(a)] |
| 43 | Fixing only louver shutter/cowl on wall with necy. bolts & nuts (6 mm dia x 62 mm long) [C-4/30b] |
| 44 | a) 23 cm (12\\") [C-4/30(b)] |
| 45 | Supply & fixing of Indicator for existing modular box |
| 46 | Supply & fixing of Blank Plate for existing modular box |
| 47 | Supplying, installation, Testing & Commissioning of LED Recessed/ surface Down lighter (Round/ square/ Rectangular) SMD with powder-coated pressure Die-cast Aluminium with high-transmission opal PMMA/ polycarbonate/ prismatic diffuser having uniform light distribution and construction as per IS : 10322. The driver rated output wattage should be 10% to 15% higher than lamp rating and efficiency Driver >80%, Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range 00 to 400 C, internal surge protection of 2.5 KV with Short & Open circuit protection, THD < 10% , PF ≥0.9, IP20, CRI >80, life time (LED, Driver & electrical circuitary), of minimum 50000 . Burning Hours (Life projection shall be calculated as per TM-21 methodology) and 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K / 6000°K / 6500°K, |
| 48 | Maximum power consumption should not more than the specified rating and Fixture shall be confirming to relevant BIS standards and trade mark certificate (T.C.) Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing Complete in all respect and LED Chips of SMD Low to mid-power, as per requirement (LM-80 tested) and necessary inter-connections with 1.5 sq mm FR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM comprehensive on-site warranty against manufacturing defects including driver and LED module. All test report except L80 should be from 3rd party NABL accredited Lab as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. System lumen efficacy shall be as below: System lumen efficacy ≥ 110 lm/Watt [Make:-Signify/Crompton/Wipro] |
| 49 | a) 18 - 20 Watt |
| 50 | Supplying, installation, Testing & Commissioning of LED Recessed/ surface Down lighter (Round/ square/ Rectangular) 2'x2' with powder-coated pressure Die-cast Aluminium/CRCA sheet body with high-transmission opal PMMA/ polycarbonate/ prismatic diffuser having uniform light distribution and construction as per IS : 10322. The driver rated output wattage should be 10% to 15% higher than lamp rating and efficiency Driver >80%, Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range 00 to 400 C, internal surge protection of 2.5 KV with Short & Open circuit protection, THD < 10% , PF ≥0.9, IP20, CRI >80, life time (LED, Driver & electrical circuitary), of minimum 50000 Burning Hours (Life projection shall be calculated as per TM-21 methodology) and 70% of initial Lumen maintained till life ends , CCT 3000°K / 4000°K/ 5700°K / 6000°K / 6500°K, Maximum power consumption should not more than the specified rating and Fixture shall be confirming to relevant BIS standards and trade mark certificate (T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing Complete in all respect and LED Chips of SMD Low to mid-power, as per requirement (LM-80 tested) and necessary inter-connections with 1.5 sq mm FR, |
| 51 | PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM comprehensive on-site warranty against manufacturing defects including driver and LED module. All test report except L80 should be from 3rd party NABL accredited Lab as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement.System lumen efficacy shall be as below:System lumen efficacy shall be as below: System lumen efficacy ≥ 135 lm/Watt [Make:-Signify/Crompton/Wipro] |
| 52 | a) 33 - 36 Watt |
| 53 | Supply& delivery of 230 V, 50 Hz, single phase, 48 watts, 12\\" (300 mm) Sweep, speed 900 rpm (minimum), A.C. Exhaust Fan and class of insulation: B, 4 nos. metal (Aluminium alloy) blades, copper winding, steel/Al body. Power Factor not less than 0.9 and minimum air delivery 1145 cmh (minimum) capacitor with safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable forcompliant to IS 374:2019andexternal connections with 1.5 sq.mm FR, PVC insulated copper conductor single corecable andearthingetc.asrequired. |
| 54 | Supply & Delivery of 230 V, 50 Hz, single phase, 85 watts, 18\\" (450mm), speed 1325 rpm (minimum), Bracket Fan and class of insulation: B, 4 nos. metal (Aluminium alloy) blades, copper winding, steel/Al body with metal back cover. Power Factor not less than 0.9 and minimum air delivery 110 cu.m/min (minimum), including capacitor with safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for compliant to IS 374:2019 and external connections with 1.5 sq.mm FR, PVC insulated copper conductor single core cable and earthing etc. as required. [Make:- Crompton Greaves/EPC/Orient/ USHA ] |
| 55 | Supplying and delivery of following size Un-Armoured cables XLPE insulated are designed for 1.1 kV Stranded copper conductor and PVC/FR PVC outer sheathing power cable of following size. (IS 7098 Part - 1/2011 with Up To Date Amendments.) [Make:-Gloster/Polycab/Havells/RR Kable]i) 3 core 4 sqmm(from OLP starter to single phase A.C outdoor Connection) |
| 56 | Disconnection & dismantling existing old Electrical installation, Switch-board, wiring, Electrical fitting/fixtures etc with owns tools & takles incl. mending good damages as per GS and clearing/removing from the site at HRBC Bhawan |
| 57 | Add. G.S.T.@ 18% on total of item |
| 58 | Add. LWC.@ 1% on total of item Please Enable Macros to View BoQ information |