| 1 | Excavation in trenches in soft/loose soil not exceeding 1.5 mtr wide and not exceeding 1.5m depth, getting out the excavated earth, forming bottom surfaces to required gradient complete all as specified and directed by Engineer-in-Charge. |
| 2 | Removal of excavated material soils to a distance n exc 50 m and depositing where directed at a level not exceeding 1.5m above the startly point complete all as specified and directed. |
| 3 | Returning filling in, including spreading, levelling watering and well ramming in layers n exc 25 cm as in any type of soil complete all as specified and directed. |
| 4 | Material and labour for sand cushioning using dry and clean tibba sand in two layers, first layers of 80mm thick before laying of cable and second layer of 150mm thick after laying of cable in trenches/ducts including consolidation of each layers complete all as specified and directed. Note : Punned thickness shall be measured for payment. |
| 5 | Material and labour for un-reinforced pre-cast concrete cable covers, class LV type-1, flat size 250mm x 150mm x 40mm thick complete all as specified and directed. |
| 6 | Taking out defective cable XLPE/PVC sheathed 1100 volt grade heavy duty armoured with aluminum conductor 2 core, 6 Sqmm from trenches complete all as specified and directed.Note : Excavation and earth work shall be measured and paid for separately under relevant item |
| 7 | Taking out defective cable XLPE/PVC sheathed 1100 volt grade heavy duty armoured with aluminum conductor 2 core, 10 Sqmm from trenches complete all as specified and directed.Note : Excavation and earth work shall be measured and paid for separately under relevant item |
| 8 | Taking out defective cable XLPE/PVC sheathed 1100 volt grade heavy duty armoured with aluminum conductor 4 core, 16 Sqmm from trenches complete all as specified and directed.Note : Excavation and earth work shall be measured and paid for separately under relevant item |
| 9 | Taking out defective cable XLPE/PVC sheathed 1100 volt grade heavy duty armoured with aluminum conductor 3.5 core, 25 Sqmm from trenches complete all as specified and directed.Note : Excavation and earth work shall be measured and paid for separately under relevant item |
| 10 | Taking out defective cable XLPE/PVC sheathed 1100 volt grade heavy duty armoured with aluminum conductor 3.5 core, 35 Sqmm from trenches complete all as specified and directed.Note : Excavation and earth work shall be measured and paid for separately under relevant item |
| 11 | Taking out defective cable XLPE/PVC sheathed 1100 volt grade heavy duty armoured with aluminum conductor 3.5 core, 50 Sqmm from trenches complete all as specified and directed.Note : Excavation and earth work shall be measured and paid for separately under relevant item |
| 12 | Supplying, laying, jointing and testing of under ground cable XLPE insulated, 1100 volt grade heavy duty armoured with stranded aluminium conductor 2 core 6 Sqmm laid in trenches/duct/pipe including all electrical connection with required lugs and nuts, bolts complete all as specified and directed by Engineer-in-Charge |
| 13 | Supplying, laying, jointing and testing of under ground cable XLPE insulated, 1100 volt grade heavy duty armoured with stranded aluminium conductor 2 core 10 Sqmm laid in trenches/duct/pipe including all electrical connection with required lugs and nuts, bolts complete all as specified and directed by Engineer-in-Charge |
| 14 | Supplying, laying, jointing and testing of under ground cable XLPE insulated, 1100 volt grade heavy duty armoured with stranded aluminium conductor 4 core 16 Sqmmlaid in trenches/duct/pipe including all electrical connection with required lugs and nuts, bolts complete all as specified and directed by Engineer-in-Charge |
| 15 | Supplying, laying, jointing and testing of under ground cable XLPE insulated, 1100 volt grade heavy duty armoured with stranded aluminium conductor 3.5 core 25 Sqmm laid in trenches/duct/pipe including all electrical connection with required lugs and nuts, bolts complete all as specified and directed by Engineer-in-Charge |
| 16 | Supplying, laying, jointing and testing of under ground cable XLPE insulated, 1100 volt grade heavy duty armoured with stranded aluminium conductor 3.5 core 35 Sqmm laid in trenches/duct/pipe including all electrical connection with required lugs and nuts, bolts complete all as specified and directed by Engineer-in-Charge |
| 17 | Supplying, laying, jointing and testing of under ground cable XLPE insulated, 1100 volt grade heavy duty armoured with stranded aluminium conductor 3.5 core 50 Sqmm laid in trenches/duct/pipe including all electrical connection with required lugs and nuts, bolts complete all as specified and directed by Engineer-in-Charge |
| 18 | Material and labour for earthing complete with galvanized steel earth plate electrode 60 cm x 60 cm x 6mm thick, buried directly in ground, vertically to a depth not less than 2.25 mtr deep below ground level with top edge of the earth plate at depth not less than 1.5 mtr below ground level earth plate surrounded by 40 cm thick and packed layers of charcoal, dust and common salt, earth GI strip of size 32x6mm by means of bolts, nuts, check-nuts and washers of galvanized iron and thimbles and of earth wire protected by galvanized iron pipe light grade 40mm bore and water pipe 40 mm bore GI medium grade with funnel and wire mesh complete including excavation and earth work, PCC chamber and cover in cement concrete 1:3:6 type C-1 using 20 mm graded stone aggregate in lieu of CI cover and frame etc all as specified and shown in electrical plate No. 3 of SSR-2009 (Part-I). |
| 19 | Repair/ maintenance and servicing of DG set capacity 400/320 KVA comprising diesel engine, AMF panel and micro processor based control panel and taking down the unserviceable spares / parts required for the periodical service / maintenance of 400/320 KVA DG Set 415 volts 3 phase 4 wire 50HZ. Draining out the old engine oil, filling of new engine oil, top up of coolant, changing of all filter elements, cleaning and washing the oil sump with kerosene oil to make it free from dust and unwanted particle. Cleaning of radiator thoroughly with soda ash powder, top up of coolant, greasing and lubricating all mobile parts and making it fully functional and testing the same on full load in the presence of Engineer -in-Charge. Note :(a) Spares parts required for replacement like Air filter, Oil filter, engine oil, coolant etc. shall be measured and paid separately under relevant item of schedule.(b) Contractor should attend breakdown of any type with in the period of contract inclusive of all Sundays and holidays.(c) Minor parts required over all cost upto Rs 1000) also included in the rate quoted excuting srl item No 20.01 to 20.12 here in below. |
| 20 | Supply only for 400/320 KVA DG Set 415 volts 3 phase 4 wire 50HZ the spares / parts followings:- |
| 21 | Air Filter Make : Bosch/fleetguard/Doossan |
| 22 | Oil filter Make : Bosch/fleetguard/Doossan |
| 23 | Fuel filter (Primary) Make :Bosch/fleetguard/Doossan |
| 24 | Fuel filter (Secondary) Make : Bosch/fleetguard/Doossan |
| 25 | Oil pressure pipe |
| 26 | Hose pipe (Water pump inlet/outlet) |
| 27 | Solenoid switch. |
| 28 | Automatic voltage regulator suitable for 320/400 KVA DG Set |
| 29 | Hose Pipe (Fuel / Radiator) |
| 30 | Relay card |
| 31 | V-Belt |
| 32 | Water pump |
| 33 | Repair and Maint of fuel injector pump of 320/400 KVA DG Set 415 volts 3 phase 4 wire 50HZ, by dismantling of fuel injector pump striping out of each of unserviceable parts, PT pumb repair kit, gear pump assembly replacement of unserviceable parts and reassembling the FIP including calibration and pressure testing computerize for each FIP from mico service station including replacement of the following items:-(i) PT Pump repair Kit(ii) Gear pump assembly |
| 34 | Dismantling of self starter 24 volts of 320 KVA/400 KVA DG Set 415 volts 3 phase 4 wire 50HZ opening and segregating cleaning the serviceable parts for re-use, self starter servicing and greasing, re-assembling the self starter and replacement of following parts :-(i) Carbon bush – 01 Set (ii) Brass plunger - 01 No(iii) Solenoid switch - 01 No (iv) Body Brass Nut – 04 Nos |
| 35 | Taking out unserviceable and supply & fixing new controller actuator (Governor control unit ) suitable for 320/400 KVA DG Set of existing make complete all as specified and directed. |
| 36 | Repair/ maintenance and servicing of DG set capacity 20/30/62.5/82.5/125 KVA comprising diesel engine , alternator, AMF panel and micro processor based control panel including taking down the unserviceable spares / parts required for the periodical service / maintenance of 20/30/62.5/82.5/125 KVA DG Set 415 volts 3 phase 4 wire 50HZ and draining out the old engine oil, filling of new engine oil, top up of coolant, changing of all filter elements, cleaning and washing the oil sump with kerosene oil to make it free from dust and unwanted particle. Cleaning of radiator thoroughly with soda ash powder, top up of coolant, greasing and lubricating all mobile parts and making it fully functional and testing the same on full load in the presence of Engineer- in- Charge. Note : (a) Spares parts required for replacement like Air filter, Oil filter, engine oil, coolant etc. shall be measured and paid separately under relevant item of schedule.(b) Contractor should attend breakdown of any type with in the period of contract inclusive of all sundays and holidays.(c) Minor parts (over all cost upto Rs 1000 ) required also included in the rate quoted excuting Srl item No 25.01 to 25.12 here in below. |
| 37 | Supply only for 20/30/62.5/82.5/125 KVA DG Set 415 volts 3 phase 4 wire 50HZ the spares / parts followings:- |
| 38 | Air Filter Make : Bosch /Mico/Leyparts |
| 39 | Oil filter Make : Bosch /Mico/Leyparts |
| 40 | Fuel filter Make : Bosch /Mico/Leyparts |
| 41 | Oil pressure pipe |
| 42 | Hose pipe (Water pump inlet/outlet) |
| 43 | Solenoid switch. |
| 44 | DG set auto battery charger, input voltage - 12 V. |
| 45 | Hose Pipe (Fuel / Radiator) |
| 46 | Relay card |
| 47 | V-Belt |
| 48 | water pump |
| 49 | Automatic voltage regulator suitable for 125/82.5/62.5/30/20 KVA DG Set |
| 50 | Repair and Maint of fuel injector pump of 20/30/62.5/82.5/125 KVA DG Set 415 volts 3 phase 4 wire 50HZ, by dismantling of fuel injector pump striping out of each of unserviceable parts, PT pump repair kit, gear pump assembly replacement of unserviceable parts and reassembling the FIP including calibration and pressure testing computerize for each FIP from mico service station including replacement of the following items:-(i) PT Pump repair – 01 No(ii) Gear pump assembly 01 No |
| 51 | Supply only followings items here in below :- |
| 52 | Distilled water |
| 53 | Battery Terminal |
| 54 | Coolant for Radiator of DG Sets |
| 55 | Engine oil 15 W 40 grade |
| 56 | S&F in repair unserviceable controller actuator (Governor control unit ) suitable for 125/82.5/62.5/30/20 KVA DG Set. INPUT- 24 V, as per existing model and make complete all as specified and as directed by Engineer-in-Charge |
| 57 | M&L for boring of road crossing of size 80mm dia using trenchless technology for laying of cables / pipe lines etc. complete all as directed. |
| 58 | Supply and fixing LED street light fitting 45 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 66 Protection complete all as specified and directed. |
| 59 | Supply and fixing LED street light fitting 60 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 66 Protection complete all as specified and directed. |
| 60 | Supply & Fixing in repairs GI brackets for mounting street light fittings made out of medium grade 32 mm dia , 1.5 m length GI pipe and have an angle of 120 degree including fixing arrangement i.e. clamps, nuts, bolts etc complete all as specified and directed. |
| 61 | Supply and fixing High light intensity empowered color changing & monochromatic 15W LED under water fountain light complete all as specified and as directed by Engineer-in-Charge. |
| 62 | Attending complaint of U/S street / road / security /Garden light/ high mast light of any capacity / type from poles / walls at height upto 10 m etc including removal of connection using labour / machinery equipments for the repair / maint or deposited to the store yard and refixing/fixing the light after necessary repair on its original position complete all as per the instruction of Engineer-in -Charge.Note: - (i) Cost of spares and accessories will be measured and paid separately under relevant items. (ii) Cost for taking down and re-fixing new parts shall be deemed to be included in the unit rate quoted.(iii) Contractor shall provide Technically qualified person for attending the complaint within 24 hrs from the time of complaint registered/conveyed otherwise, a penalty at the rate of Rs. 500/- per day shall be levied from contractor due payment. |
| 63 | S & F as in repair astronomical timer switch 110/240V, complete all as specified and as directed. |
| 64 | Supply only followings items here in below:- |
| 65 | Power Contactor 3 Pole 40Amps 415 Volts 50HZ |
| 66 | Power Contractor 3 Pole 70Amps 415 Volts 50HZ L&T/Legrand/Seimens. |
| 67 | LED Driver as per existing in site suitable for 60/70W street light LED fittings |
| 68 | LED Driver as per existing in site suitable for 35/45W street light LED fittings |
| 69 | LED Driver as per existing in site suitable for 20/25W security light LED fittings |
| 70 | LED Driver as per existing in site suitable for 200W flood light LED fittings |
| 71 | LED Driver as per existing in site suitable for 100W flood light LED fittings |
| 72 | S&F in repair battery of 12 V 90 AH complete with copper lead and terminal for connection all as specified and directed. |
| 73 | S&F in repairs battery of 12 V 180 AH complete with copper lead and terminal for connection complete all as specified and as directed. |
| 74 | Supply and fixing in repairs cylindrical shape, Pressure die cast powder coated housing with PC diffuser, efficient high output COB LED for Garden, Pathway etc lighting IP-66 protection of capacity 10W complete with electrical connections with new 3 core wire complete all as specified and as directed. |
| 75 | Supply and fixing in repairs, LED Bollard with robust design and efficient light distribution with IP65 rated, complete all as specified and directed. |
| 76 | S&F as in repairs IP 65 rated LED Post top ideal to lit up parks, garden ways, efficient light distribution 20W capacity, incl electrical connection using 3 core wire complete all as specified and as directed |
| 77 | Supply & Fixing in repair LED Driver suitable for garden light of existing make all as specified and directed by Engineer-in-Charge |
| 78 | Supply & Fixing in repair LED Driver suitable for garden light of existing make all as specified and directed by Engineer-in-Charge |
| 79 | Supply & Fixing in repair LED Driver suitable for garden light of existing make complete all as specified and directed by Engineer-in-Charge |
| 80 | Supply and Fixing in repair LED flood light IP 65 PDC aesthetically designed with better thermal management of capacity 100W with complete accessories and duly prewired by using new 3 core 1.5 sqmm cable incl testing complete all as specified and as directed.Note :- The fitting will be fitted after executing the following jobs :-(a) Lowering the existing high mast lights ring with existing handle or by using motor.(b) Disconnecting all the electric connections of existing unserviceable sodium high mast lights.(c) Fixing the new LED floodlights, fitting by using nuts & bolts on high mast rings.(d) Testing the all LED fittings and uppering the high mast ring by using existing handle or by using motor. |
| 81 | Supply and Fixing in repair LED flood light IP 66 PDC housing heat resistant tempered glass for protection with 5KV surge protection of capacity 200W with complete accessories and duly prewired by using new 3 core 2.5 sqmm cable from junction box to LED fitting incl testing complete all as specified and as directed.Note :- The fitting will be fitted after executing the following jobs :-(a) Disconnecting the electric connections and Lowering the existing unserviceable Watch Tower lights or any other location and at any height by using machinery equipments.(b) Fixing the new LED floodlight fitting of 200W by using nuts & bolts on watch tower poles or any other location as per existing . |
| 82 | S&F in repair new generation, 35W post-top, energy saving, environmental friendly, long life aesthetically designed with symmetrical light distribution, spun aluminum landscape luminaire with high power LEDs as light source complete all as specified and as directed |
| 83 | Supplying and laying in repairs GI tubing light grade incl all accessories for encasing cables for mechanical protection, laid under Plinth / Floors/ Paths Culverts or fixed on wall or concealed in wall/floor or along poles or as street light poles or as street light mounting bracket with complete accessories such as bends/sockets/reducers/saddles incl necessary threading/drilling workscomplete all as specified and as directed of follwing sizes.Note :- MS works will be measured under separate item in Schedule. |
| 84 | 80 mm bore |
| 85 | 50 mm bore |
| 86 | 40mm bore |
| 87 | S&F in repair LT Cable joining kit straight through heat shrinkable type complete with joining materials suitable for LT Armoured cables of size upto 50 Sqmm 3.5 core complete all as specified and as directed. |
| 88 | S&F in repair LT Cable joining kit straight through heat shrinkable type complete with joining materials suitable for LT Armoured cables of size 70-120 Sqmm 3.5 core complete all as specified and as directed |
| 89 | S&F in repair LT Cable joining kit outdoor end termination heat shrinkable type joint complete with jointing material and accessories suitable for LT Armoured cables of size up to 95 Sqmm 3.5 core complete all as specified and as directed |
| 90 | M&L for heavy duty double break fuse switch HBC/HRC fuse type TPN 415 Volts 200 amps capacity with 03 Nos HRC fuse link including taking down old HRC fuse complete all as specified and as directed. |
| 91 | Dismantling of damaged steel tubular/PCC pole of size 9 mtr for disposal complete all as specified and as directedNote :Unit rate of this item includes the cost of dismantling of PCC and excavation and earthwork complete as directed. |
| 92 | Supply, installation and erection steel tubular swaged welded poles 9 m,in true vertical position complete with MS base plate of 6 mm thick of size 300mm x 300mm, finial taper plug, pole cap, bolts, nuts and washers and screwed, pole made out of ERW MS tubing conforming to IS-2713 ( Part II),1980 type 410-SP-31, 9 meters long L.T pole including drilling of holes of required size and Nos for fixing of cross arms, painting with one coat of red oxide primer and two coats of aluminum paint for exposed surfaces and two coats of black bituminous paint for portion embedded in concrete, painting with two coats of aluminum paint over a coat of primer incl excavation incl PCC complete in post hole in any type of strata, PCC 1:2:4 foundation, filling, in post holes with PCC 1:3:6 and cylindrical coping with PCC 1:2:4 of size .45x.3 complete all as specified and directed.Note : Unit rates of this item includes the cost of PCC in foundation, PCC coping and excavation and earthwork. |
| 93 | Material and Labour for earthing complete with copper plate electrode 60 cm x 60 cm x 3.15 mm thick, buried directly in ground, vertically to a depth not less than 2.25 meter deep below ground level with top edge of the earth plate at depth not less than 1.5 meter below ground level earth plate surrounded by 15 cm thick and packed layers of charcoal, dust and common salt, earth lead copper strip 20 mm x 3 mm by means of bolts, nuts, check-nuts and washers of galvanised iron and then brazing the copper strip joints and thimbles of earth wire and water pipe 40 mm bore GI medium grade with funnel and wire mesh complete including excavation and earth work, PCC chamber and cover in cement concrete 1:3:6 type C-1 using 20 mm graded stone aggregate in lieu of CI cover and frame etc all as specified and shown in electrical plate No. 3 of SSR-2009 (Part-I) and colour coding the earthing including taking out the old unserviceable earth plate complete all as specified and as directed.Note : (i) Copper strip fixed more than 2 meters will measured and paid separately. |
| 94 | Material and Labour for copper strip of size 20 mm x 3 mm complete including taking out the old unserviceable strip of any type, complete all as specified and as directed. |
| 95 | Supply and fix OFF LOAD change over switch 415V ,50 Hz 4 pole of capacity 200 Amps incl enclosure and taking out the old unserviceable change over switch, complete all as specified and as directed. |
| 96 | Supply and fix OFF LOAD change over switch 415V ,50 Hz 4 pole of capacity 125 Amps incl enclosure and taking out the old unserviceable change over switch, complete all as specified and as directed. |
| 97 | Supply,fixing and testing in repair outdoor type dust & vermin proof type AMF Panel for DG Set of Capacity 30 KVA with two number MCCB 4 pole 63 Amp 25 KA , double contactors and accessories, battery charger 12V DC, timer, coil with all control circuit for auto ON/OFF etc housed in a outdoor type panel cabinet made of 3 mm CRCA sheet duly powder coated of size to accommodate the above mentioned MCCBs, relays, contractors,timers,busbars with properly insulated aluminum bus bar of size as required, prewired complete and fixed on an angle iron of size 50x50x6mm thick 600mm long to be fixed on ground with proper PCC for foundation and coping including necessary wiring required complete all as specified and directed. |
| 98 | Supply, install, testing and commissioning as in replacement outdoor type factory made, made out of 3.00mm thick CRCA Sheet CPRI test certified, platform mounted LT panel board to accommodate the following items and built upon angle iron frame suitable size compartmentalized design work, duly powder coated with gray paint and suitable size of cable glands chromium plated and aluminum busbars TPN, 400 Amps,415 V,50 Hz complete as following :- (i) Changeover switch 250A, 4 Poles - 01 No(ii) MCCB 200 Amps, 4 Poles, 25 KA rupturing capacity - 01 No (incoming) (iii) MCCB 100 Amps, 4 Poles, 16 KA rupturing capacity - 01 No (outgoing) (iv)MCCB 63 Amps, 4 Poles, 16 KA rupturing capacity - 03 No (outgoing) (v) MCCB 40A, 4 Pole, 10KA rupturing capacity - 01 No (Outgoing)(vi) Indicating lamp LED RYB set of three with colour codeing - 1 No. Note : Unit rate of this item also includes the following :- (a) For fixing the Panel excavation and earthwork involved shall be carried out by the contractor as directed.(b) After errection / fixing of panels, all connection shall be made by the contractor as directed. |
| 99 | Supply, install, testing and commissioning as in replacement outdoor type factory made, made out of 3.00mm thick CRCA Sheet CPRI test certified, platform mounted Street light panel board to accommodate the following items and built upon angle iron frame suitable size compartmentalized design work, duly powder coated with gray paint and suitable size of cable glands chromium plated and aluminium busbars TPN, 200 Amps,415 V,50 Hz complete as following :- (i) MCCB 60 Amps, 4 Poles, 16 KA rupturing capacity - 01 No (ii) MCCB 40 Amps, 4 Poles, 16 KA rupturing capacity - 01 No (iv) 3 Ph Digital timer switch for street light/highmast light (v) Power Contactor 3 Pole 40Amps 415 Volts 50HZ (iv) Indicating lamp LED RYB set of three with colour codeing - 1 No. Note : Unit rate of this item also includes the following :- (a) For fixing the Panel excavation and earthwork involved shall be carried out by the contractor as directed.(b) After errection / fixing of panels, all connection shall be made by the contractor as directed. |
| 100 | Material and labour for painting above the copping upto 1.5 mtr in alternatively black and white strips of 30 cm each & rest of the portion with two coats of silver/ aluminum paint on steel tubular LT pole of any height after scrapping/removing the existing paint and the preparation the surface of steel tubular pole LT including painting of the channel cross arms, nut, bolts & washer, street light bracket and clamps complete all as specified and directed |
| 101 | Material and labour for Spray painting front and back side of panel size n.exc 1.20mX1.20m and two side of size 1.20mX0.50m and top surface of LT panels with two coats of synthetic enamel paint after scraping, removing of old paint complete all as specified and directed. |
| 102 | Supply and fixing in repair PVC cable end terminal box outdoor type, 14 x 14 cm, PVC door, provision for cable incoming and outgoing from bottom , comprising of one MCB SP 6-32 Amps ,cable glands suitable size and aluminium busbar (4Nos) four way complete fixed on wall/pole complete all as specified and as directed. |
| 103 | Repair/maint of high mast pole,checking of control panel, motor stater, control wiring, gear box, switches for Up / down travel light frame,rope and gear box etc including oiling, greasing, welding of shaft etc complete if required complete all as specified and directed by Engineer-In-Charge. |
| 104 | Supply and fix in replacement of steel wire rope 6 mm dia complete all as specified and directed by Engineer-in-Charge. |
| 105 | Taking out electric motor 1.0 HP 3 Phase 415 V dismantling , taking out burnt winding wire and rewinding with new supper enamelled copper wire baking, varnishing etc and reassembling testing complete all as specified and as directed by Engineer-in-Charge. |
| 106 | Supply and fix in replacement of bearing suitable for 1.0 HP 3 Phase 415 V motor complete all as specified and as directed by Engineer-in-Charge. |
| 107 | Supply and fix in replacement of irreversible DOL motor starter 3 Phase 415V relay range 2.0 to 3.0 Amp suitable for 1.0 to 1.5 HP motor E-in-C Approved make complete all as specified and as directed by Engineer-in-Charge. |
| 108 | M & L Unsheated 2.5 sqmm insulated, Unarmoured, heavy duty electric cable with Copper conductor, 3 run for phase, 1 run for neutral and 1 run for earth 1100 Volts grade suitable for High Mast light, complete all as specified and as directed.Note : 5 run of cable measured as one unit length |
| 109 | Supply and fix 1.5 Sqmm, single core Two runs PVC insulated and unsheathed FRLSH cable 1100 Volts grade with multistranded copper conductor and one run of 1.5 Sqmm cable for common earth dolly drawn through heavy duty PVC conduit for street light pole including connection from kiosk box to street light fittings complete all as specified and directed.Note : 3 run of cable measured as one unit length |
| 110 | M&L for air termination, single pointed aluminium rod 12mm dia and 300 mm long complete all as specified and directed. |
| 111 | M&L for test point terminal block made of gun metal or phrosphrous bronze 75x75x25mm, drilled and screwed including 3 Nos, 8mm dia 25mm long hexagonal head brass screws including necessary MS box with locking arrangements complete all as specified and directed. |
| 112 | M&L for Aluminium strip 25 x 3mm fixed on epoxy insulator with saddles and fixing screws etc., for roof conductors and down conductors above ground complete all as specified and directed. |
| 113 | M&L for galvanised iron strip 32 x 6mm burried in ground or drawn in pipe or any other situation complete all as specified and as directed. |
| 114 | Comprehensive monthly maintenance of 300KVA UPS system, Make : Vertiv, installed in the AOR of AF Stn Bikaner, complete all as specified and directed by Engineer-in-Charge. The detail scope of work consists of the following:-(i) Execute diagnostics and physical checks.(ii) Examine, clean, test, all equipment as required and repair parts as and when required.(iii) Measurement of UPS parameters like input/output voltage, frequency, current, frequency, room temperature tec. (iv) Battery parameters like voltage, current and other relevant parameters.(v) The corrective maintenance may require multiple visits to site. (vi) Check all equipment LED/LCD display board if any fault found to be rectified. (vii) Checking UPS fuse and replace if found unserviceable. (viii) Keeping of servicibility of UPS is the responsibility of the contractor fir the entire contract period. (ix) Cleaning up of unit, visual inspection to check any deformation. (x) Checking and Adjustment (if needed) of control parameters on different PCBs. (xi) Tightness of all connection. (xii) Functional checking up of Rectifier section. (xiii) Functional checking up of inverter section. (xiv) Functional checking up of static switch section. (xv) Perform operational test of the system including unit transfer and battery discharge. Note : (i) The comprehensive maintenance done from the OEM only i.e. Vertiv Energy Pvt Ltd. (ii) The contractor advised to take quotation from Vertiv befor quoting rate. (iii) Response time should not be more than 12 hourse from the time of receipt of complaint around the clock, 7 days/week. (iv) In case of any delay in attending the complaint more than 12 hrs after given the complaint the contractor shall be liable to pay Rs. 1000 per day as penalty. |
| 115 | S&F in repairs lead acid battery of 12 V 200 AH complete with copper lead and terminal for connection complete all as specified and directed Please Enable Macros to View BoQ information |
| 116 | S&F in repairs lead acid battery of 12 V 200 AH complete with copper lead and terminal for connection complete all as specified and directed Please Enable Macros to View BoQ information |