| 1 | Attending complaints for checking of existing electrical points wiring upto size 6 sqmm in any Buildings for continuity ,no light including carrying out minor repairs etc as required to make the item functional and replacing burnt wire ends, small pieces of wire, tightning of loose connections etc all as specified.Note - Contractor has to deploy Qualified Electrician and Helper with all necessary tools on all days to the complaint cell and complaints will be attended on the same day itself. Recovery for non attending complaints will be three times rate quoted by the Contractor. Note : a) Contractor shall provide his Electician and Helper along with necesary tools to rectify defects from 0830 to 1700 Hrs on all days incl holiday & sundayb) S&F of elevant items in Sch items will not be considered in this job.c) The contractor shall depute ITI holder electrician & skiilled helper to attend complaits, with proper uniform as finalised by Engr-in-Charge, with name tag. |
| 2 | M&L for point wiring for light/fan/Bell with FRLS cable 1.5 sqmm PVC insulated (red for phase and black for neutral) unsheathed, multi stranded copper conductor 1100 volt grade in and incl not less than 2mm thick PVC casing caping/concealed with PVC conduit as per site requirment with all accessories and 1.50 sqmm green in colour PVC copper conductor cable for earth continuity connected to common earth dolly incl PVC box surface/modular sunken box type with PVC sheet for mounting fittings such as switches, sockets, fan regulators etc including taking down copper/aluminium point wiring (light, fan, bell, sockets or power) complete,incl fitting and fixtures such as switches, ceiling rose, pendents, regulators, sockets, lights fittings complete all as specified and directed for one light/fan /bell point controlled by one switch & making good to disturbed surface of wall etc |
| 3 | All as per item No.2 above but with 2.5 sqmm cable for one multipin 5 amps socket outlet on same board incl taking down same one. |
| 4 | All as per item No.2 above but with 2.5 sqmm cable and 2.5 sqmm for earth continuity for multipin 5 amps socket outlet flush type on independent board incl taking down same one. |
| 5 | All as per item No. 2 above but with 2.5 sqmm cable and 2.5 sqmm for earth continuity for multipin 15 amps socket outlet flush type on independent board incl taking down same one. |
| 6 | S&F in switch piano button flush type, single pole one way 5 amps incl taking down old unserviceable one. |
| 7 | S&F in switch bell push piano flush button single pole one way 5 amps incl taking down old unserviceable one. |
| 8 | S&F in piano switch two way flush button 5 amps incl taking down old unserviceable one. |
| 9 | S&F in 5 pin single socket outlet 2 in 1, 5 pin, 5 amps flush type incl taking down old unserviceable one. |
| 10 | S&F in 5 pin switch socket combination 2 in 1, 5 amps flush type incl taking down old unserviceable one. |
| 11 | S&F in Switch socket combination 5 in 1, 5 and 15 Amp flush type controlled by one switch incl taking down old unserviceable one.. |
| 12 | S&F in ceiling rose, 3 phase on PVC square blocks surface bakelite 65 x 50 mm, 3 terminal incl taking down old unserviceable one. |
| 13 | S&F in Lamp holder, PVC/Polycarbonate type with back plate for batten fittings complete incl taking down old unserviceable one.. |
| 14 | S&F in flush type fan regulator 230V, electronic rotary stepped increase incl taking down old unserviceable one. |
| 15 | S&F Call bell ding dong AC, 23 Volts, single pole type incl taking down old unserviceable one.. |
| 16 | S&F Switch Modular (piano) flush button single pole one way 6 amps 1 module with suitable plate and cover complete all as specified and directed. |
| 17 | S&F Switch Modular (piano) flush button single pole one way 16 amps with suitable plate and cover complete all as specified and directed. |
| 18 | S&F Socket outlet flush modular (piano) type 5 pin 6 Amps with suitable plate and cover complete all as specified and directed. |
| 19 | S&F Electronic Modular Fan regulator step type not less than 100/120 watt with suitable plate and cover complete all as specified and directed. |
| 20 | S&F three modular sheet fitting complete all as specified and as directed by Engr-in-Charge. |
| 21 | S&F four modular sheet fitting complete all as specified and as directed by Engr-in-Charge. |
| 22 | S&F Six modular sheet fitting complete all as specified and as directed by Engr-in-Charge |
| 23 | S&F Eight modular sheet fitting complete all as specified and as directed by Engr-in-Charge. |
| 24 | S&F twelve modular sheet fitting complete all as specified and as directed by Engr-in-Charge. |
| 25 | S&F modular 16 Amps socket complete all as specified and as directed by Engr-in-Charge. |
| 26 | S&F Fan Fastner nut and bolt with complete of size 10 mm complete all as specified and as directed by Engr-in-Charge. |
| 27 | Supply only copper wire 1.5 Sqmm FRLS green/red colour single core complete all as specified and as directed by Engr-in-Charge. |
| 28 | Supply only copper wire 2.5 Sqmm FRLS green/red/black colour single corecomplete all as specified and as directed by Engr-in-Charge. |
| 29 | S&F PVC exhaust fan 200 MM complete acessories with suitable copper wire including taking down old unserviceable / burnt exhaust fan complete all as specified directed by Engr-in-charge. |
| 30 | S&F PVC exhaust fan 250 MM complete acessories with suitable copper wire including taking down old unserviceable / burnt exhaust fan complete all as specified directed by Engr-in-charge. |
| 31 | M&L for sub main wiring with two run of 6 sqmm single core multi stranded PVC insulated and unsheathed copper conductor (red for phase and black for neutral) of grade 1100 volt FRLS cable in and including electrical grade PVC conduits of desired colour not less than1.2 mm thick and 25 mm wide & 6 sqmm copper conductor cable PVC unsheathed green coloured for earthing with complete accessories duly connected with earth dolly complete all as specified and as directed incl taking down old unserviceable one.complete all as specified and as directed by Engr-in-Charge. |
| 32 | Ditto- as per item No.31 above but size 4 Sqmm two runs and with 4 sqmm FRLS copper wire for earth continuity. complete all as specified and as directed by Engr-in-Charge. |
| 33 | Ditto- as per item No.31 above but size 2.5 Sqmm two runs and with 2.5 Sqmm FRLS copper wire for earth continuity. complete all as specified and as directed by Engr-in-Charge. |
| 34 | S&F LED 9/12 Watt Indoor ceiling spot light/focus light/ track light warm white/ cool day white complete all as specified directed by Engr-in-charge |
| 35 | S&F LED tube light fitting 18/20 watt wall mounted LED batten with aluminum housing & integrated electronic driver incl taking down old UNSV. complete all as specified and as directed by Engr-in-Charge. |
| 36 | S&F LED tube light fitting 9/10 watt wall mounted LED batten with aluminum housing & integrated electronic driver incl taking down old UNSV.complete all as specified and as directed by Engr-in-Charge. |
| 37 | S&F 12 watts Emergency Bulb Back up 4 hrs cool day light/warm white complete all as specified and as directed by Engr-in-Charge. |
| 38 | S&F 20 watts Emergency LED Tube Lights Back up 4 hrs cool day light/warm white complete all as specified and as directed by Engr-in-Charge. |
| 39 | S&F By Flushing to walls MCB distribution board Double door SPN 230 volts 12 way with 200 amps rated bus bar and making good to disturbed surfaces of floors/walls etc incl taking down the old DBs incl taking down old unserviceable complete all as specified and as directed by Engr-in-Charge. |
| 40 | S&F By Flushing to walls MCB distribution board Double door SPN 230 volts 8 way with 200 amps rated bus bar and making good to disturbed surfaces of floors walls etc incl taking down the old DBs incl taking down old unserviceable complete all as specified and as directed by Engr-in-Charge. |
| 41 | S&F By Flushing to walls MCB distribution board Double door SPN 230 volts 6 way with making good to disturbed surfaces of floors walls etc incl taking down the old DBs incl taking down old unserviceable complete all as specified and as directed by Engr-in-Charge. |
| 42 | S&F By Flushing to walls MCB distribution board double door 240 volts 4 way with 200 amps rated bus bar and making good to disturbed surfaces of floors walls incl taking down the old DBs etc. complete all as specified and as directed by Engr-in-Charge. |
| 43 | S&F By Flushing to walls MCB distribution board double door 240 volts 2 way making good to disturbed surfaces of floors walls incl taking down the old DBs etc. complete all as specified and as directed by Engr-in-Charge. |
| 44 | Distribution board iron clad TPN DB, double door with IP-43 1K-09 protection suitable for MCCB as incommer and MCB as outgoing 415 Volts 3 phase 50 C/s 4 way, complete with appropriate size copper bus bar including cutting chases to wall for fixing DB and making good the disturbed wall surface all as required at site or directed by Engr-in-Charge (Note: MCB's and MCCB will be measured and paid seperately under relevent items) |
| 45 | S&F MCB SP 5 to 32 Amps, 240 Volts complete incl taking down old unserviceable .complete all as specified and as directed by Engr-in-Charge. |
| 46 | S&F MCB SPN upto 32 Amps ,240 Volts complete incl taking down old unserviceable.complete all as specified and as directed by Engr-in-Charge. |
| 47 | S&F 9 watt LED wall light/ceiling light ,body colour white and black voltage AC85-240 50 Hz Model No -LX135WL/9W complete all as specified and as directed by Engr-in-Charge. |
| 48 | S&F MCCB TPN 100 Amps ,415 Volts complete incl taking down old unserviceable.complete all as specified and as directed by Engr-in-Charge. |
| 49 | S&F MCCB TPN 125 Amps ,415 Volts complete incl taking down old unserviceable one.. complete all as specified and as directed by Engr-in-Charge. |
| 50 | S&F in replacement MCB SPN 63 Amps, 230 V,AC incl taking down old unserviceablecomplete all as specified and as directed by Engr-in-Charge. |
| 51 | S&F in replacement TPN 63 Amps 415 V incl taking down old unserviceable complete all as specified and as directed by Engr-in-Charge. |
| 52 | M&L in replacement of condenser 2.5 mfd, 250 V incl taking down old unserviceable one. and connecting complete all as specified and as directed by Engr-in-Charge. |
| 53 | All as per Srl No 52 above, but 4 mfd incl taking down old unserviceable complete all as specified and as directed by Engr-in-Charge.one. |
| 54 | All as per Srl No 52above, but 3.5 mfd incl taking down old unserviceable one.complete all as specified and as directed by Engr-in-Charge. |
| 55 | M&L for industrial type metal socket enclosure with 240 volt MCB 20 Amps, with metal plug top taking down old unserviceable one. complete all as specified and as directed by Engr-in-Charge. |
| 56 | S&F of 10 Watt energy efficient wall mouted LED Bulk head luminaire with opal diffuser IP 65 all incl taking down old UNSV.complete all as specified and as directed by Engr-in-Charge. |
| 57 | Hanging only ceiling fans in repairs any size, any make, and necessary connection as directed by Engineer-In-Charge. |
| 58 | Hanging only Exhaust fans in repairs any size, any make, and necessary connection as directed by Engineer-In-Charge. |
| 59 | S&F 36 watts recess /pendant mounting ultraslim LED flat panel 2' X 2' made of extruded aluminium frame with high LEDs & glare free opal diffuser IP20. LCTLRNE-36-FO-CDL of Crompton equivalent of Philips/Wipro incl taking down old UNSV.complete all as specified and as directed by Engr-in-Charge. |
| 60 | S&F round sheet for blank area 2.5 \\" dia and 3 \\" complete all as specified and as directed by Engr-in-Charge. |
| 61 | S&F Digital Electric Meter single phase 240 volts with capacity of 10 to 60Amps complete with all acessories complete all as specified and as directed by Engr-in-Charge. |
| 62 | S&F Hylam sheet 4X4 inches complete all as specified and as directed by Engr-in-Charge. |
| 63 | S&F Hylam sheet 4X7 inches complete all as specified and as directed by Engr-in-Charge. |
| 64 | S&F Hylam sheet 8X10nches complete all as specified and as directed by Engr-in-Charge. |
| 65 | S&F flexible pipe white colour dia 3/4\\" and 1'' complete all as specified and as directed by Engr-in-Charge. |
| 66 | S&F PVC Gang box two way or one way for shifting of 5A/15 Amps switch & socket etc complete all as specified and as directed by Engr-in-Charge. |
| 67 | M&L for earthing complete with galvanized steel earth plate electrode 60 x 60cm x 6 mm thick burried directly in ground vertically to a depth not less than 2.25 mtr deep below GL with top edge of the plate not less than 1.5 mtr below normal GL and connected to earth plate surrounded by 15 cm thick packed layers of charcoal dust and common salt and connected to earth lead galvanised iron 4mm dia wire by means of bolts, nuts, check nuts and washers of galvd iron or steel and thimbles and other end of the earth wire connected to DB and protected by galvd iron or steel pipe light grade 15 mm bore and water pipe 20mm bore GI light grade with funnel and wire mesh, including all necessary excavation and earth work PCC chamber in cement concrete 1:3:6 type C-2 and RCC cover and all as shown in electrical plate No 3 of MES schedule Pt I of 2009. Note : RCC pit cover shall be pre-cast of RCC (1:2:4) type B-I , 80mm thick reinforced with XPM weighting not less than 4 KG/sqmm in lieu of CI cover. complete all as specified and as directed by Engr-in-Charge. |
| 68 | Taking out unserviceable service wire and S&F 1100 volts grade heavy duty cable PVC insulated aluminium conductor seved with inner sheathing of PVC sheathed in service connections twin core cable flat of size 10 Sqmm all as specified and directed by Engr in charge complete all as specified and as directed by Engr-in-Charge. |
| 69 | Taking out unserviceable service wire and S&F 1100 volts grade heavy duty cable PVC insulated aluminium conductor seved with inner sheathing of PVC sheathed in service connections twin core cable flat of size 16 Sqmm complete all as specified and as directed by Engr-in-Charge. |
| 70 | S&F 18 way modular box complete all as specified and as directed by Engr-in-Charge. |
| 71 | S&F 14 way modular box complete all as specified and as directed by Engr-in-Charge. |
| 72 | S&F 12 way modular boxcomplete all as specified and as directed by Engr-in-Charge. |
| 73 | S&F 6 way modular boxcomplete all as specified and as directed by Engr-in-Charge. |
| 74 | S&F 4 way modular box complete all as specified and as directed by Engr-in-Charge. |
| 75 | S&F 3 way modular boxcomplete all as specified and as directed by Engr-in-Charge. |
| 76 | Taking down carefully UNSV exhaust fan any size and any company including accesseries and ceiling fan any size any make complete materials to store for keeping in safe custody in store keeper at E/M store yard.complete all as specified and as directed by Engr-in-Charge. |
| 77 | M&L for rewinding of ceiling fans 1200/1400mm sweep of any make/model, including removal of existing burnt windings carefully from the slots,cleaning the slots thoroughly with necessary cleaning agent, applying slot insulation and rewinding with super enmelled copper winding wire of same gauge/same number of turns as that of existing and connecting the coils suitable to operate on 230 volts single-phase AC supply permanent capacitor type, tying the windings and applying air dry insulating varnish and drying the windings including replacing the defective components such as bearing, gun metal bush,rubber bush/bolt, capacitor,flexible cord, shaft and painting including assembling after lubricating movable components complete including testingcomplete all as specified and as directed by Engr-in-Charge. :- Note :-(1) Fan will be issued from AGE E/M store yard through gate pass.(2) Bearing/ Gunmetal bush/ rubber bush bolt/ capacitor / cord flexiable / stator/rotor and painting only will be measured and paid separately under respective item. |
| 78 | S&F ceiling fans complete with aluminium blades, down rods, 230 V, 1200 mm sweep. Min air delivery 210 CFM with service value 6.00 BEE. Five star rated with brushless direct current motor (BLDC)as specified, complete all as specified and directed by Engr-in-charge. |
| 79 | M&L for rewinding of Exhaust fans 200 to 325mm sweep of any make/model, including removal of existing burnt windings carefully from the slots,cleaning the slots thoroughly with necessary cleaning agent, applying slot insulation and rewinding with super enmelled copper winding wire of same gauge/same number of turns as that of existing and connecting the coils suitable to operate on 230 volts single-phase AC supply permanent capacitor type, tying the windings and applying air dry insulating varnish and drying the windings including replacing the defective components such as bearing, gun metal bush,rubber bush/bolt, capacitor,flexible cord, shaft and painting including assembling after lubricating movable components complete including testingcomplete all as specified and as directed by Engr-in-Charge. :- Note :-(1) Exhaust Fan will be issued from AGE E/M store yard through gate pass.(2) Bearing/ Gunmetal bush/ rubber bush bolt/ capacitor / cord flexiable / stator/rotor and painting only will be measured and paid separately under respective item. |
| 80 | Supply only PVC canopies of suitable size for ceiling fan of any make/model(set of two) with screws complete all as specified and as directed by Engr-in-Charge. |
| 81 | Supply only U clamps with rubber reel and nuts/bolts of suitable size with pinscomplete all as specified and as directed by Engr-in-Charge. |
| 82 | Supply only of down rods upto 30 cm long heavy duty of any size with gudgeon pins complete all as specified and as directed by Engr-in-Charge. |
| 83 | Supply and replacement of fan blade assy suitable for 1200mm sweep ceiling fan (set of three) of any model/make complete all as specified and as directed by Engr-in-Charge. |
| 84 | Supply and only of fan blade assy suitable for 1400mm sweep ceiling fan (set of three) of any model/make complete all as specified and as directed by Engr-in-Charge. |
| 85 | Supply and replacement of fan blade assy suitable for 300mm sweep exhaust fan (set of three) of any model/make complete all as specified and as directed by Engr-in-Charge. |
| 86 | S&F of 3, 2X 3 way modular pop up box push and slide locking system including switches and socket 15 amps two nos to avoid accidental opening by feet to be equipped with Arteor outlet complete suitable for raised floor, flush floor & false ceiling and wall etccomplete all as specified and as directed by Engr-in-Charge. |
| 87 | S&F XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area but size of cable 16 Sqmm 4 Core complete all as specified and as directed by Engr-in-Charge. |
| 88 | Dito as per item No 87 but XLPE size of cable 16 Sqmm 2 Core complete all as specified and as directed by Engr-in-Charge. |
| 89 | Supply only 12 watts LED Bulb complete all as specified and as directed by Engr-in-Charge. |
| 90 | Supply only 9 watts LED Bulb complete all as specified and as directed by Engr-in-Charge. |
| 91 | Supply only 9 watts LED Bulb base E27 warm white/ cool day white complete all as specified and as directed by Engr-in-Charge. |
| 92 | S&F Three Pin 15 Amp plug top 240 Volts complete all as specified and directed by Engr-in-Charge. |
| 93 | S&F Three Pin 5 Amp plug top 240 Volts complete all as specified and directed by Engr-in-Charge. |
| 94 | S&F steel body heavy duty Exhaust fan 300 MM complete acessories with suitable copper wire including taking down old unserviceable / burnt exhaust fan complete all as specified and as directed by Engr-in-Charge. |
| 95 | S&F front gate decorative lights as per requirement at site and complete all as specified directed by Engr-in-Charge |
| 96 | S&F galvanised/aluminium metal sheet frame Exhaust fan flappe shutter outdoor type of size 20x20 inches it has no chance for rusting during rain incl nut, bolts, screw etc flappe are fitted at any height any floor of buildings complete all as specified directed by Engr-in-Charge. |
| 97 | Taking down the defective ceiling fan BLDC /Normal of any sweep and make after disconnecting electrically & mechanically and transporting to the work shop dismantling, examine & carry out the repairs as required and brought back to site, re-fixing, testing in all respect for smooth running and comprising of the following:-(a) Servicing/overhauling the ceiling fan by thoroughly cleaning the bearing, shaft, stator, rotor & applying the lubricant / grease to the bearing including applying one coat of super enameled varnish over the winding to improve the insulation value complete.(b) M& L for opening, cleaning, drying and re-winding or BLDC Circuit plate the burnt/short circuited PCB or winding with same guage supper enameled copper wire to maintain speed at load. (c) M&L for preparing surface scrabing, finishing and Painting of ceiling fan by applying one coats of synthetic enamel paint after preparation of surface complete. (d) Replacement of ball bearing suitable for ceiling fans existing sweep & Make/Model complete all as specified directed by Engr-in-Charge. |
| 98 | Supply only copper wire 4 Sqmm FRLS green/red/black colour single core complete all as specified and as directed by Engr-in-Charge. |
| 99 | Supply only copper wire 6 Sqmm FRLS green/red/black colour single core complete all as specified and as directed by Engr-in-Charge. |
| 100 | Repair maintaince of 230 volts modular kitchen chimney checking the servicablitiy of the chimney including fixing of any item in the chimney for repair or making it servicable complete all as specified directed by Engr-in-Charge. |
| 101 | SCHEDULE 'A' PART-II (Schedule of credit) Credit amount of Rs (Refer schedule of credit) for retrieved material mentioned in Sch 'A' Part-II of Tender documents in PDF form will be deducted offline during acceptance of tender of lowest bidder. Please Enable Macros to View BoQ information |